7. Function list
7-12
SV-iC5
Function group 2
LED
display
Parameter
Name
Min/Max
Range
Description
Factory
defaults
Adjustable
during run
Page
H37
[Load inertia
rate]
0/2
Select one of the following according to
motor inertia.
0
X
10-6
0
Less than 10 times that of motor
inertia
1
About 10 times that of motor
inertia
2
More than 10 times that of motor
inertia
H39
[Carrier
frequency
select]
1/15
[kHz]
This parameter affects the audible
sound of the motor, noise emission from
the inverter, inverter temp, and leakage
current. If the value is set higher, the
inverter sound is quieter but the noise from
the inverter and leakage current will
become greater.
3
O
10-
16
H40
[Control mode
select]
0/3
0
{Volts/frequency Control}
0
X
9-15
1
{Slip compensation control}
10-6
2
{PID Feedback control}
10-8
3
{Sensorless vector control}
10-11
H41
[Auto tuning]
0/1
If this parameter is set to 1, it
automatically measures parameters of the
H42 and H43.
0
X
10-
10
H42
[Stator
resistance
(Rs)]
0/5.0[
Ω
]
This is the value of the motor stator
resistance.
-
X
H44
[Leakage
inductance
(L
σ
)]
0/300.0
[mH]
This is leakage inductance of the stator
and rotor of the motor.
-
X
H45
1)
Sensorless P
gain
0/32767
P gain for Sensorless control
1000
O
H46
Sensorless I
gain
I gain for Sensorless control
100
O
H50
[PID
Feedback
select]
0/1
0
Terminal I input (0 ~ 20 mA)
0
X
10-8
1
Terminal V1 input (0 ~ 10 V)
1) : Set H40 to 2 (PID control) or 3(Sensorless vector control) to display these parameters.
Summary of Contents for SV iC5 Series
Page 8: ...Table of Contents viii SV iC5...
Page 22: ...3 Wiring 3 6 SV iC5 Notes...
Page 38: ...5 Programming keypad 5 14 SV iC5 Notes...
Page 42: ...6 Basic operation 6 4 SV iC5 Notes...
Page 64: ......
Page 68: ......
Page 108: ...10 Advanced functions 10 20 SV iC5 Notes...
Page 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes...
Page 136: ......
Page 142: ......
Page 143: ......