9. Basic functions
9-15
SV-iC5
9.5 V/F control
Linear V/F operation
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Function
group 1
F22
[Base frequency]
-
30/400
60.0
Hz
F23
[Start frequency]
-
0.1/10.0
0.5
Hz
F30
[V/F pattern]
0
0/2
0
Set F30 to 0 {Linear}.
This pattern maintains a linear Volts/frequency ratio from F23 - [Start frequency] to F22- [Base frequency]. This
is appropriate for constant torque applications.
F22 – [Base frequency] : Inverter outputs its rated voltage at this level. Enter the motor nameplate
frequency.
F23 – [Start frequency] : Inverter starts to output its voltage at this level.
Square V/F operation
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Function
group 1
F30
[V/F pattern]
1
0/2
0
Set F30 to 1{Square}.
This pattern maintains squared volts/hertz ratio. Appropriate applications are fans, pumps, etc.
Run
command
Freq.
Start freq.
Base freq.
Voltage
Inverter rated
voltage
Freq.
Base freq.
100%
Voltage