11
GIPAM User Manual
4) FUNC+W: It displays a settled own address at telecommunication part of main board.
5) FUNC+Var: It displays the number of operation time of the circuit breaker
which is connected to CB ON input contact.
6) FUNC+PF: It displays all the measured data by the following sequence in a
row(V → A → W → VAR → WH → VARH → F → PF, Voltage/Current: every
phases have been measured.)
7) FUNC+Wh: It displays the let through time(Hour unit) of the CB which is connected
to the CB ON input contact. When the time is over 9999hours, it displays the time
by the bargraph on the 10000 hours unit.
8) FUNC+VARH: It displays Vo with N1 and Vo max. with N2.
6-1-4. CB operation and local or remote control
1) LOCAL: It is the key for the local operation . If press this button, local output
contact will be on and it makes possible to operate C/B on or off by pressing the
keys on the front.
2) Remote: It is the key for the remote control . If press this button, remote output
contact will be on and it can be possible to operate C/B on or off by
telecommunication at host computer.
3) CB ON/OFF: If press the ON/OFF switch, output contact will be conducted during
from 0.5 to 0.6 seconds. It makes operate CB(ON/OFF Operation) when local
operation switch is selected.
6-1-5. Others
1) Clear switch
. The clear switch in the back plate reset the WH & VARH value to
“
0
”
. The users should press the reset button when you first install the system.
2) CPU Reset button
. The CPU reset switch in the back plate clear all the data in the CPU. When you
found the operations of the equipment is unusual, you can press and restart.
3) COMM LED
During the communication with monitoring computer, it is go on and off.
Summary of Contents for GIMAC-II
Page 2: ...GIPAM USER MANUAL Digital Integrated Protection Monitoring Equipment GIPAM User Manual...
Page 16: ...15 GIPAM User Manual...
Page 17: ...16 GIPAM User Manual...
Page 18: ...17 GIPAM User Manual...
Page 19: ...18 GIPAM User Manual...
Page 20: ...19 GIPAM User Manual...
Page 21: ...20 GIPAM User Manual...
Page 25: ...24 GIPAM User Manual 2 VI Very Inverse Time OCR OCGR t TL TL 0 05 1 00 13 5 I Is 1...
Page 26: ...25 GIPAM User Manual 3 EI Extremely Inverse Time OCR OCGR t TL TL 0 05 1 00 80 I Is 2 1...
Page 27: ...26 GIPAM User Manual 4 LI Long Inverse Time OCR OCGR t TL TL 0 05 1 00 120 I Is 1...
Page 33: ...32 GIPAM User Manual 4 Three Phase Three Wire System with 3 CTs with 3PTs...
Page 36: ...35 GIPAM User Manual 3 Terminal Block 7 7 External Dimension mm...
Page 44: ...GIMAC II USER MANUAL Digital Integrated Metering Control Equipment GIMAC II User Manual...
Page 53: ...10 A57 IgYf AUbiU 5 2 Wiring...
Page 54: ...11 A57 IgYf AUbiU 1 3P4W 3 CT 2 3P3W 3CT With 3PTs...
Page 55: ...12 A57 IgYf AUbiU 3 3P3W 2CT 4 1P3W...
Page 56: ...13 A57 IgYf AUbiU 5 1P2W 6 Odering Information...
Page 57: ...GMPC III USER MANUAL Protocol converter III GMPC III User Manual...