Detailed operation by function groups
203
O
p
er
ati
o
n
D
etai
ls
6.4.2.4 Lost command conditions for multifunction analog input
Ai1 (AIO_12)
The following table lists lost command options available for multifunction analog
input terminal V1.
Code
Keypad display
Function
Range Unit Description
AIO_12 Ai1 Wbroken
Lost
command
conditions
for multi-
function
analog
input Ai1
0
(None)
Do not use analog input lost command
options.
1 (half
of x1)
Analog input lost command is decided when
analog input based on AIO_02 (Ai1 source)
is in the following range.
0
→ 10 V
0–(AIO_03 Ai1 In X1)/2
10 → 0 V
0–(AIO_03 Ai1 In X1)/2
-
10 → 10 V
(AIO_07 Ai1 -In X1)/2
– (AIO_03 Ai1 In X1)/2
10 →
-10 V
(AIO_07 Ai1 -In X1)/2
– (AIO_03 Ai1 In X1)/2
2
(Below
x1)
Analog input lost command is decided when
analog input based on AIO_02 (Ai1 source)
is in the following range.
0 → 10 V
0–(AIO_03 Ai1 In X1)
10 → 0 V
0–(AIO_03 Ai1 In X1)
-
10 → 10 V
(AIO_07 Ai1 -In X1)
– (AIO_03 Ai1 In X1)
10 →
-10 V
(AIO_07 Ai1 -In X1)
– (AIO_03 Ai1 In X1)
6.4.2.5 Lost command conditions for multifunction analog input
Ai2 (AIO_24)
The following table lists lost command options available for multifunction analog
input terminal I1.
Code
Keypad display
Function
Range Unit Description
AIO_2
4
Ai2 Wbroken
Lost
command
0
(None)
Do not use analog input lost command
options.