Detailed operation by function groups
149
O
p
er
ati
o
n
D
etai
ls
Code
Keypad display Name
Range
Unit
Default setting
PAR_10
UserMotorSel
User-defined motor
capacity
2.2–22.0
kW
7.5
6.2.3.4 Setting the maximum motor speed (PAR_11)
Set PAR_11 to define the maximum motor speed. The maximum motor speed is
the maximum output for the maximum speed reference.
Code
Keypad display
Name
Range
Unit
Default setting
PAR_11 Max. Speed
Maximum motor
speed
V/F, Slip : 30.00-120.00
IM : 10.0-3600.0
PM : 10.0-680.0
Hz
rpm
rpm
V/F, Slip : 60.00
IM : 1800.0
PM : 100.0
6.2.3.5 Setting the minimum motor speed (PAR_12)
This code is displayed when PAR_07 is set to “V/F” or “Slip Comp” mode. Once
the minimum motor speed is set, the inverter only operates when it receives a
speed reference that is equal to, or greater than this minimum motor speed. If a
speed reference smaller than the minimum motor speed is received during
operation, the inverter recognizes it as a stop command, and performs a
decelerating stop.
Code
Keypad display
Name
Range
Unit
Default setting
PAR_12
Min. Speed
Minimum motor speed
0.5–10.00
Hz
0.5