Detailed operation by function groups
135
O
p
er
ati
o
n
D
etai
ls
6.1.2 User defined information (DIS_01, 02, 03)
You can configure codes DIS_01, 02, and 03 to choose to display on the keypad
one of the following information listed in the following table.
By default, DIS_01 is set to “Out Volt rms,” DIS_02 to “Flux Cur Red,” and
DIS_03 to “DC Bus Volt.”
Code
Keypad
display
Name
Unit
Description
DIS_01
-
DIS_03
Ai1 Value –
Ai2 Value
Multi-function
analog
%
Multifunction analog input value is displayed
in a percentage (10 V/100%, 20 mA /100%)
PreRamp Ref
Speed reference
before
acceleration or
deceleration
Hz/
rpm
Displays motor rpm reference before an
acceleration/deceleration routine.
PostRamp
Ref
Speed reference
after acceleration
or deceleration
Hz/
rpm
Displays motor rpm reference after an
acceleration/deceleration routine.
ASR Inp Ref
Speed controller
input reference
Hz/
rpm
Displays the actual reference that is given
to the speed controller.
Output Freq
Output
frequency
Hz/
rpm
Displays the inverter output frequency.
Motor Speed
Motor Rotation
speed
rpm
Displays the actual motor rotation speed.
Speed Dev
Speed deviation
rpm
Displays the difference between the speed
reference and the actual motor rotation.
ASR Out
Speed controller
output
%
Displays the speed controller output in a
percentage to the rated torque.
Torque Bias
Torque bias
%
Displays the torque bias in a percentage to
the rated torque.
PosTrq Limit
Forward torque
limit
%
Displays the forward torque limit in a
percentage to the rated torque.