I185 GB 06 15
LRX D01
71
AQ (ANALOG OUTPUT)
The default output mode of AQ is 0-10V voltage; the corresponding value of AQ is 0~1000. It also can be set as 0-20mA current; the
corresponding value of AQ is 0~500. The output mode of AQ is set by the current value of DRD0~DRD3 as shown below.
It will be considered as 0 if the value of DR is not in the range of 0~3. That means the output mode of AQ is mode 1. AQ displays preset value
(constant of code of other data) under STOP mode, displays current value under RUN mode. AQ preset value can be a constant or other function
current value.
AQ DISPLAY
AQ displays the preset value under STOP mode, and displays the current value under RUN mode.
2 number of expansion analog output 2AO; AQ01_AQ04
The value will be considered if in over-flow when writing AQ preset value or current value through PC communication. So, output mode
information should be written before preset value.
AQ–current_value: 500 = AQ_display_value : 20.00mA
AQ current value is different from display value and current value is used in operation and storage. AQ display is shown below.
A Q 0 1 = 0 1 . 2 3 V
A Q 0 2 = 0 8 . 9 2 m A
A Q 0 3 =
A 0 1 V
A Q 0 4 = D R 3 F
m A
Number
Meaning
Mode
DRD0~DRD3 data definition
DRD0
Setting the output of AQ01
1
0: voltage mode, AQ output value is 0 under STOP mode
DRD1
Setting the output of AQ02
2
1: current mode, AQ output value is 0 under STOP mode
DRD2
Setting the output of AQ03
3
2: voltage mode, AQ keeps output value under STOP mode
DRD3
Setting the output of AQ04
4
3: current mode, AQ keeps output value under STOP mode
0 ~ 10VDC voltage mode (AQ value: 0_1000), depending on DRD0
0 ~ 20mA current mode (AQ value: 0_500), depending on DRD1