I185 GB 06 15
LRX D01
42
TIMER MODE 3 (OFF-DELAY)
Mode 3 Timer is an OFF-Delay with reset that will time up to a fixed preset value and stop timing when the current time is equal to the preset
value. Additionally, the Timer current value will reset to zero when Timer is disabled. In the example below, the timer reset input is Input
I01.Timer status bit T01 will be ON immediately when its rung is true. The timer will only begin timing up when its rung changes to false. Timer
status bit T01 will turn OFF when the current time value reaches its preset value of 10 seconds.
2
1
4
5
3
6
– T0E and T0F keep their current value after a loss of power to the LRD if “M Keep” is active, but the others' reset to 0.