Wiring of LRE02AD024 module
Characteristics
Specifications
(Analog output unit, 2 voltage/current output channels)
Voltage
Current
Analog output range
0~10V
0~20mA
Impedance of the external load
Impedance of the external load
should be more than 500
Ω
should be less than 500
Ω
Resolution
10mV
40
µ
A
Digital output
0.00V~10.00V
0.00mA~20.00mA
Accuracy ±2,5%
±2.5%
Total number of channels
2
2
C1~C2
V1~V2 or I1~I2 input available
V1~V2
Voltage output terminal;
––
output of the voltage signal from V and C
Terminal block
I1~I2
––
Current output terminal;
output of the voltage signal from I and C
+
+24VDC power supply input ter)
–
+24VDC power supply input terminals(-)
Auxiliary power supply
24VDC
Ambient operating temperature
-20°C…+55°C
The output mode can be set by LRD… base module with DR register values (current mode):
Number
Meaning
Data definition
DRD0
Output mode AQ01
0: Voltage mode
AQ output value is 0 when LRD is in STOP mode.
DRD1
Output mode AQ02
1: Current mode
AQ output value is 0 when LRD is in STOP mode.
DRD2
Output mode AQ03
0: Voltage mode
AQ maintains the output value when LRD is in STOP mode.
DRD3
Output mode AQ04
1: Current mode
AQ maintains the output value when LRD is in STOP mode.
N.B. The value is considered as 0 if DR is out of the 0
∼
3 range.
Wiring of LRE04AD024 module
External
equipment
External
equipment
External
equipment
External
equipment
-
24V
+
-
24V
+
Voltage output
Current output
V2
I2
C2 PE
3
4
1
PE
PE
PE
2
PE
-
24V
+
V2
I2
C2 PE
3
4
1
PE
PE
PE
2
PE
-
24V
+
0-10V Analog
4-20mA Analog
1A fast acting fuse, circuit
breaker and circuit protection.
Transient voltage surge
suppressor (43VDC cut-off
voltage).
1A fast acting fuse, circuit
breaker and circuit protection.
Transient voltage surge
suppressor (43VDC cut-off
voltage).