TIMER MODE 6 (FLASH WITH RESET)
Mode 6 Timer is a Flash timer with reset that will time up to a fixed preset value and then change the state of its status bit. Additionally, the
Timer current value will reset to zero when Timer is disabled. In the example below, the timer reset input is Input I01. Timer status bit T01 will
be ON immediately when its rung is true and begins its timing sequence. Timer status bit T01 will turn OFF when the current time value reaches
its preset of 10 seconds. This Flash sequence of the timer status bit T01 will continue as long as its rung remains true.
2
1
4
5
3
6
– The current value of Timer cannot be kept on a loss of power to LRD.