When the termination switch is set to BUS, 100Ω 1/8W termination resistance is connected between communication
terminals A and B.
For a free topology network connection, terminate one module on the network. When the termination switch is set to
FT, 50Ω 1/8W termination resistance is connected between communication terminals A and B.
The following table describes the type and feature of the termination resistance for each switch position.
<Termination Switch Configuration for the H100 LonWorks communication module>
Switch Position
Termination Type
FT
For use with a free topology network
50Ω terminal resistance
Terminate one module on the network.
NO
Termination is not used.
BUS
For use with a bus topology
100Ω terminal resistance
Terminate two modules at the ends of the network.
①
NO
③ BUS
Bus Topology
(100
Ω
)
② FT
Free Topology
(50
Ω
)
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4