![Lonworks CLON-H100 User Manual Download Page 21](http://html1.mh-extra.com/html/lonworks/clon-h100/clon-h100_user-manual_1938830021.webp)
H100LonWorksManual
21
4.2 Drive Object
Mandatory
Network
Variables
nviDrvSpeedStpt
SNVT_switch
nv1
nvoDrvSpeed
SNVT_lev_percent
nv4
Variable Speed Motor
Drive (6010)
Optional
Network
Variables
nviDrvSpeedScale
SNVT_lev_percent
nv2
nvoDrvCurrent
SNVT_amp
nv3
nvoDrvVolt
SNVT_volt
nv5
nvoDrvPwr
SNVT_power_kilo
nv6
nvoDrvRunHours
SNVT_time_hour
nv7
nc17 nciLocation (Optional)
nc50 nciMaxSpeed (Mandatory)
nc53 nciMinSpeed (Mandatory)
nc48 nciRcvHrtBt (Optional)
nc49 nciSndHrtBt (Mandatory)
nc52 nciMinOutTm (Optional)
nc158 nciNmlSpeed (Mandatory)
nc159 nciNmlFreq (Mandatory)
nc160 nciRampUpTm (Mandatory)
nc161 nciRampDownTm (Mandatory)
nc162 nciDrvSpeedScale (Optional)
Configuration Properties
Input Network
Variable
Output Network
Variable