![Lonworks CLON-H100 User Manual Download Page 34](http://html1.mh-extra.com/html/lonworks/clon-h100/clon-h100_user-manual_1938830034.webp)
H100LonWorksManual
34
Valid Range
30.0–400.0 (0.1 Hz)
Default
60.0 Hz
Inverter Parameters Related to the ‘nciNmlFreq’ Variable
Code Number/
Common Area Address
Code Description
Default
Range
DRV-18
Base Frequency
60.00 Hz
30.00 – 400.00
4.2.16 Minimum Ramp Up Time (Mandatory)
Definition
Network config input SNVT_time_sec
nciRampUpTm
Description
The ‘nciRampUpTm’ variable is used to configure the inverter’s acceleration time. When the ‘nciRampUpTm’ value is
changed, it is reflected in DRV-03 Acc Time. The default ‘nciRampUpTm’ value is 20.0 sec, which is the default
acceleration time that is set as DRV-03 Acc Time.
Valid Range
0.0–600.0 sec (0.1 sec increments)
Default
20.0 sec
Inverter Parameters Related to the ‘nciRampUpTm’ Variable
Code Number/
Common Area Address
Code Description
Default
Range
0x0007
DRV-03
Acc Time (Acceleration time)
20.0 sec
0.0 – 600.0
4.2.17 Minimum Ramp Down Time (Mandatory)
Definition
Network config input SNVT_time_secnciRampDownTm
Description
The ‘nciRampDownTm’ variable is used to configure the inverter’s deceleration time. When the ‘nciRampDownTm’
value is changed, it is reflected in DRV-04 Dec Time. The default ‘nciRampDownTm’ value is 30.0 sec, which is the
default acceleration time set at DRV-04 Dec Time.
Valid Range
0.0–600.0 sec (0.1 sec increments)
Default
30.0 sec