H100LonWorksManual
42
Keypad-2
V1
Reserved
V2
I2
Int 485
FieldBus
Reserved
Pulse
PRT-12
Lost Cmd Mode
None
None
FreeRun
Dec
Hold Input
Hold Output
Lost Preset
PRT-13
Lost Cmd Time
1.0sec
0.1–120.0sec
Note
When the LonWorks network is used as a command source, the inverter’s lost command time becomes the time set
for the ‘nciUsrRcvHrtBt’ and PRT-13 Lost Cmd Time added together. However, if the ‘nciRcvHrBt’ variable is set to 0.0
sec, the lost command protection feature is disabled.
4.3.4 Send Heart Beat Time for User Object (Mandatory)
Definition
Network config input SNVT_time_sec
nciUsrSndHrtBt
Description
The User Object network output variable ‘nciUsrSndHrtBt’ is used to configure the maximum output times
for‘nvoUsrParaState1 – nvoUsrParaState8’variables.
Typical Range
0.0 – 6553.4 sec
A value of 0xFFFF (6553.5 sec) is invalid data.
Default
0.0 sec (Send Heart Beat is disabled)