3.2.13 Operation Options for a Lost Command– Lost Cmd Mode (PRT-12)
DRV-06
Cmd Source
DRV-07
Freq Ref Src
PRT-12
Lost Cmd Mode
PRT-13
Lost Cmd Time
PRT-14
Lost Preset F
This parameter is used to select an operation mode to be used when the command is lost. When remote command
via network is lost for the ‘lost command decision time’, the inverter decides that the command is lost.
This feature is available only when DRV-06 is set to ‘4.Fieldbus,’ or when DRV-07 is set to ‘7.Fieldbus.’
With this feature enabled, the selected operation mode is used when the network command is lost.
Settings
Description
0
None
Keeps the inverter operation at lost command.
1
Free-Run
The inverter blocks output. The motor performs a free-run stop.
2
Dec
The motor decelerates and then stops at the time set at PRT-07 Trip Dec
Time.
3
Hold Input
The inverter calculates the average input value for 10 sec before the loss of
the speed command and uses it as the speed reference.
4
Hold Output
The inverter calculates the average output value for 10 sec before the loss
of the speed command and uses it as the speed reference.
5
Lost Preset
The inverter operates at the frequency set at PRT-14 Lost Preset F.