G. The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset 
control shall not cause the operator to start. 
H. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily 
visible. 

 

I. For a gate operator utilizing a non-contact sensor in accordance Usage Class: 
1) See instructions on the placement of non-contact sensors for each Type of application, 
2) Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor 
while the gate is still moving in the opening direction. 
3) One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, 
such as the perimeter reachable by a moving gate or barrier. 
J. For a gate operator utilizing a contact sensor in accordance with Usage Class: 
1) One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as 
at the leading edge, trailing edge, and post-mounted both inside and outside of a vehicular horizontal slide 
gate. 
2) One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate. 
3) One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate. 
4) A hardwired contact sensor shall be located and its wiring arranged so that the communication between 
the sensor and the gate operator is not subjected to mechanical damage. 
5) A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for 
entrapment protection functions shall be located where the transmission of the signals are not obstructed or 
impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall 
function under the intended end-use conditions. 
6) One or more contact sensors shall be located on the inside and outside leading edge of a sliding gate. 
Additionally, if the bottom edge of a sliding gate is greater than 6 inches (152 mm) above the ground at any 
point in its arc of travel, one or more contact sensors shall be located on the bottom edge. 
7) One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm). 
 

Summary of Contents for SCG 18H

Page 1: ...www WholesaleGateOpener com Rev 11a...

Page 2: ...7 Installation Overview 8 Installation of the Operator 8 Manual Operation 9 Installation of chain and chain brackets 10 Installation of the Limit Switch 11 Connecting of the Control Board 12 Setting...

Page 3: ...carrying out any work on the installation Also disconnect any buffer batteries if fitted Fit an omnipolar or magnetothermal switch on the mains power supply having a contact opening distance equal to...

Page 4: ...lied for exposed rollers B The operator is intended for installation only on gates used for vehicles Pedestrians must be supplied with a separate access opening The pedestrian access opening shall be...

Page 5: ...side and outside of a vehicular horizontal slide gate 2 One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate 3 One or more contact sensors shall be located...

Page 6: ...es not bind or drag on the ground The gate manual operation can be carried out smoothly along its entire run and there is no excessive side slipping The opening and closing gate stops are positioned W...

Page 7: ...6 Parts List...

Page 8: ...rbed power SCG18H 370W SCG21H 550W Gate moving speed 7 9 second 20 cm second Max gate weight SCG18H 800KGS SCG21H 1200KGS Max torque SCG18H 24Nm SCG21H 35Nm Environmental conditions From 15 C to 40 C...

Page 9: ...d result in property damage severe injury and or death Before starting installation ensure that there is no point of friction during the entire movement of the gate and there is no danger of derailmen...

Page 10: ...oncrete become harden 5 Mount the base plate to the concrete Pad It s only temporary installation Further adjustment will be required when install the chain 6 Mount the chain box to the base plate by...

Page 11: ...emporarily Nuts will be further adjusted for a proper chain tension later 3 Connect second chain bolt with another end of chain from chain box then attach bolt to the L bracket on opposite end of gate...

Page 12: ...hand Locate and install the magnet bracket so that the operator will stop at the desired close position when the close limit switch approaches it Push the gate fully open by hand Locate and install th...

Page 13: ...W wire of the limit switches should be connected into the 9 terminal 4 Alarm Lamp One wire of the alarm lamp should be connected into the 4 terminal another should be connected into the 5 terminal 5 P...

Page 14: ...13...

Page 15: ...of the motor in midway mode auto close time of the gate operator and fast change the open close direction which is determined by the position of the gate operator installed DIP Switch 1 2 Running tim...

Page 16: ...other word the stall force level is higher the reversing sensitivity level is lower Put an immobile object along the gate path and then operate the gate to strike it during the open and close cycles...

Page 17: ...citor c The electric component on the control board may be damaged Replace the electric component or replace the control board 2 The gate will not open or close a The power switch is OFF Make sure the...

Page 18: ...close a Photocell is obstructed Remove obstruction b The limit switch is failed Disconnect the limit switches and try it again c The start capacitor of the motor is failed Replace the capacitor d The...

Page 19: ...www WholesaleGateOpener com 7106 S 220th St Kent WA 98032 USA sales WholesaleGateOpener com 2010 2012 LockMaster All Rights Reserved...