Maintenance schedule

Maintenance procedures

Boiler must be serviced and maintained

 WARNING

The boiler must be inspected and started 
annually at the beginning of the heating 
season by a qualified service technician.  
In addition, the maintenance and care 
of the boiler designated on page 5 of this 
manual and explained on pages 6 through 
7 must be performed to assure maximum 
boiler efficiency and reliability.  Failure to 
service and maintain the boiler and system 
could result in equipment failure, causing 
possible severe personal injury, death, or 
substantial property damage.

 NOTICE

The following information provides 
detailed instructions for completing 
the maintenance items listed in the 
maintenance schedule on page 5.  In 
addition to this maintenance, the boiler 
must be serviced and started up at the 
beginning of each heating season by a 
qualified service technician.

Check boiler area

 WARNING

To prevent potential of severe personal 
injury, death, or substantial property 
damage, eliminate all materials discussed 
below from the boiler vicinity and the 
vicinity of the boiler combustion air inlet.  
If contaminants are found:

Remove products immediately from the 
area.  If they have been there for an 
extended period, call a qualified service 
technician to inspect the boiler for possible 
damage from acid corrosion.

If products cannot be removed, 
immediately call a qualified service 
technician to re-pipe vent and air piping 
and locate vent termination/air intake 
away from contaminated areas.

1.  Combustible/flammable materials -- Do not store 
 

combustible materials, gasoline or any other flammable 

 

vapors or liquids near the boiler.  Remove immediately if 

 found.

2.  Air contaminants -- Products containing chlorine or 
 

fluorine, if allowed to contaminate the boiler intake air, 

 

will cause acidic condensate in the boiler.  This will cause 

 

significant damage to the boiler if allowed to continue.   

 

Read the list of potential materials listed in Table 1A on 

 

page 4 of this manual.  If any of these products are in the 

 

room from which the boiler takes its combustion air, they 

 

must be removed immediately or the boiler combustion 

 

air (and vent termination) must be relocated to another 

 area.

Check pressure/temperature gauge

1.  Make sure the pressure reading on the boiler pressure/ 
 

temperature gauge does not exceed 24 psi (165.5 kPa).  

 

Higher pressure may indicate a problem with the 

 expansion 

tank.

2.  Contact a qualified service technician if problem persists.

Check vent piping

1.  Visually inspect the flue gas vent piping for any signs of 
 

blockage, leakage, or deterioration of the piping.  Notify 

 

your qualified service technician at once if you find any 

 problems.

 WARNING

Failure to inspect the vent system as noted 
above and have it repaired by a qualified 
service technician can result in vent system 
failure, causing severe personal injury or 
death.

Check air piping

1.  Visually inspect the air inlet elbow to be sure it is 
 

unobstructed.  Inspect the entire length of air piping to 

 

ensure piping is intact and all joints are properly sealed.

2.  Call your qualified service technician if you notice any 
 problems.

Check relief valve

1.  Inspect the boiler relief valve and the relief valve 
 

discharge pipe for signs of weeping or leakage.

2.  If the relief valve often weeps, the expansion tank may 
 

not be working properly.  Immediately contact your 

 

qualified service technician to inspect the boiler and 

 system.

Check condensate drain system

1.  Inspect the condensate drain line, vent line, condensate 
 

PVC fittings, and condensate trap.

Flush condensate trap with water

1.  Remove the four (4) screws securing the top cover to the 

condensate trap and remove the cover (FIG. 2-1).

2.  Locate the plastic ball inside the float tube.  Verify there 
 

is nothing under the ball causing it to not seat properly.

3.  Replace the top cover and the screws removed in Step 1.

          

User’s Information Manual 

Summary of Contents for Power-fin 1002

Page 1: ...er s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the i...

Page 2: ...tially hazardous situation which if not avoided may result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to perso...

Page 3: ...er can cause internal corrosion in system components Leaks in boiler or piping must be repaired at once to prevent the need for makeup water Freeze protection fluids NEVER use automotive antifreeze Us...

Page 4: ...s Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building cons...

Page 5: ...nd flame sense electrodes sand off any deposits clean and reposition Check wiring and connections Perform start up checkout and performance verification per Section 9 Flame inspection stable uniform C...

Page 6: ...will cause significant damage to the boiler if allowed to continue Read the list of potential materials listed in Table 1A on page 4 of this manual If any of these products are in the room from which...

Page 7: ...wn boilers used for domestic water heating they must operate year round 3 Replace the front access door Test low water cutoff if installed 1 If the system is equipped with a low water cutoff test the...

Page 8: ...call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety...

Page 9: ...e bottom right of the screen and displays both factory installed and field installed sensor including Outdoor Air Hot Water Temperature System Supply System Return Inlet Water Delta T Outlet Water Flu...

Page 10: ...10 Notes User s Information Manual...

Page 11: ...11 Notes User s Information Manual...

Page 12: ...reflects an update to the maintenance information for the service technician on page 5 Revision C PCP 3000028200 CN 500017830 reflects an update to the Home Screen information Revision D PCP 300003085...

Reviews: