Installation & Operation Manual
Table 3J
Approved PolypropyleneTerminations
Polypropylene
This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 3H.
All terminations must comply with listed options in this
manual and be a single-wall vent offering.
For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.
When determining equivalent combustion air and vent length
for polypropylene single-wall piping:
•
1 foot of Duravent 4 inch single-wall pipe is equivalent
to 1 foot of piping
Flexible polypropylene
For use of flex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations (FIG. 3-3).
Use only the adapters and vent system listed in
Tables 3H and 3I. DO NOT mix vent systems
of different types or manufacturers. Failure to
comply could result in severe personal injury,
death, or substantial property damage.
⚠
WARNING
Installations must comply with applicable
national, state, and local codes. For Canadian
installation, polypropylene vent must be listed
as a ULC-S636 approved system.
Installation of a polypropylene vent system
should adhere to the vent manufacturer’s
installation instructions supplied with the
vent system.
⚠
WARNING
Insulation should not be used on polypropylene
venting materials. The use of insulation will
cause increased vent wall temperatures, which
could result in vent pipe failure.
The installer must use a specific vent starter
adapter at the flue collar connection. The
adapter is supplied by the vent manufacturer
to adapt to its vent system. See Table 3H
for approved vent adapters. Discard CPVC
starter piece.
NOTICE
All vent connections MUST be secured by
the vent manufacturer's joint connector
(FIG. 3-4).
NOTICE
IMG00840
*NOTES: 1) FLEX PIPE MAY ONLY BE RUN IN A VERTICAL ORIENTATION
2) ALL VENT LENGTHS REPRESENTED IN ABOVE CHARTS ARE
EQUIVALENT LENGTHS.
3) SECTION A IS EQUIVALENT FEET OF RIGID PIPE, WHICH MAY
INCLUDE 45 AND 90° ELBOWS. PLEASE SEE SIZING SECTION
FOR DETERMINING EQUIVALENT FEET.
“B” DIM
3” RIGID 3” FLEX 4” FLEX
Duravent 3”
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
60 FT
53 FT
47 FT
40 FT
33 FT
27 FT
20 FT
13 FT
7 FT
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
30 FT
27 FT
23 FT
20 FT
17 FT
13 FT
10 FT
7 FT
3 FT
“A” DIM
“B” DIM
Duravent 4”
“A” DIM
4” RIGID 4” FLEX
“B” DIM
3” RIGID 3” FLEX 4” FLEX
Centrotherm 3”
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
45 FT
40 FT
35 FT
30 FT
25 FT
20 FT
15 FT
10 FT
5 FT
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
“A” DIM
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
33 FT
29 FT
26 FT
22 FT
18 FT
15 FT
11 FT
7 FT
4 FT
“B” DIM
Centrotherm 4”
“A” DIM
4” RIGID 4” FLEX
CHIMNEY
CAP
A
B
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
5” FLEX
Figure 3-3
Near Boiler Flexible Polypropylene Venting
Figure 3-4
Near Boiler Polypropylene Venting
NOTICE
NOTICE
DIR #2000536703 00
CPVC
STARTER
DURAVENT
ADAPTER
JOINT CONNECTION
REQUIRED AT ALL
COMPONENT
CONNECTIONS OF
VENT SYSTEM
CPVC XF
POLYPRO ADAPTER
Model
DuraVent Polypro
* These parts are only needed if the sidewall termination assembly is
used (see FIG. 4-5B).
Polypropylene
Adapter
Joint
Connector
Sidewall Kit*
400-500
4PPS-AD-M
4PPS-LB
4PPS-HLK
650-1000
6PPS-06PVCM-6PPF Not Required
6PPS-HLK
Approved Polypropylene Vent Manufacturers
Make
Model
Centrotherm Eco Systems
InnoFlue SW/Flex
Duravent (M & G Group) PolyPro Single-Wall / PolyPro Flex
Table 3I
Polypropylene Vent Pipe and Fittings
Model
Centrotherm InnoFlue SW
Polypropylene
Adapter
Joint Connector Sidewall Retaining
Bracket*
Sidewall Adapter*
Low Profile Wall
Termination
Concentric Wall
Termination
400-500
ISAAL0404
IANS04
IATP0404
ISTAGL0404
ISLPT0404
ICWT462 & ICT0446
650-1000
ISAAL0606
Not Required
IATP0606
ISTAGL0606
ISLPT0606
ICWT610 & ICTC06610