Code and description
Cause
Measure
F04
(lock out error)
Ignition error
Three unsuccessful
ignition attempts.
No gas.
-
Make sure that the main gas supply
valve is open. If necessary, open the
valve.
-
Make sure that the manual gas supply
valve, before the gas control valve, is
open. If necessary, open the valve.
-
Make sure that the gas supply
pressure to the gas control valve is
correct, refer to Gas supply pressure
(see 8.9.3).
Air in the gas pipes.
-
Bleed the air out of the gas pipe.
-
Make sure that the gas supply
pressure to the gas control valve is
correct, refer to Gas supply pressure
(see 8.9.3).
Defect in the hot surface igniter circuit.
-
Make sure that the hot surface igniter
is installed correctly.
-
Make sure that the wiring of the hot
surface igniter is not damaged.
-
Measure the resistance across the hot
surface igniter. This must be between
the 36 and 72 Ohm (at room
temperature).
-
Make sure that the hot surface igniter
lights up during ignition.
If necessary, replace the hot surface igniter.
Defect in the ionisation circuit.
-
Make sure that the flame probe is
installed correctly.
-
Make sure that the wiring of the flame
probe is not damaged.
-
Measure the ionisation current. This
current must be a minimum of 3 μA
(parameter
109
).
If necessary, replace the wiring and/or
flame probe.
Supply voltage too low.
-
Make sure that the supply voltage on
the controller is correct.
-
If the supply voltage is below the
stated tolerance and the error
persists, contact your maintenance
and service engineer.
-
Install an isolating transformer.
Bent flame probe is in contact with
metal surface.
-
Make sure that the flame probe is not
bend.
-
If necessary, replace flame probe.
Ceramic part, of the flame probe, is
broken or cracked.
-
Make sure that the ceramic part of the
flame probe is not broken or cracked
in the vicinity of the burner.
-
If necessary, replace flame probe.
0312582_EcoSword_V4.0, 03-05-2021
75
Summary of Contents for EcoSword LGC 160-210 G P CE
Page 11: ...User part 0312582_EcoSword_V4 0 03 05 2021 11 ...
Page 12: ...12 ...
Page 14: ...14 User part ...
Page 16: ...16 User part ...
Page 22: ...22 User part ...
Page 25: ...Installation Maintenance and Service part 0312582_EcoSword_V4 0 03 05 2021 25 ...
Page 26: ...26 User part ...
Page 34: ...34 Installation Maintenance and Service part ...
Page 56: ...56 Installation Maintenance and Service part ...
Page 68: ...68 Installation Maintenance and Service part ...
Page 85: ...13 4 Electrical wiring diagram 0312582_EcoSword_V4 0 03 05 2021 85 ...
Page 90: ...90 Installation Maintenance and Service part ...
Page 93: ......