TECHNICAL DATA
Model Number
EKB45CE
EKB60CE
EKB85CE
EKB115CE
EKB145CE
EKB175CE
EKB205CE
EKB235CE
GENERAL DATA
Input (gross) – kW
44.0
61.5
83.5
116.9
146.5
175.8
205.2
234.5
Input (net) – kW
39.6
55.4
75.2
105.3
132.0
158.4
184.9
211.3
Output – kW (50º/30º)
41.2
58.7
79.7
110.6
141.1
168.9
197.8
228.4
Output – kW (80º/60º)
38.5
53.2
71.0
101.1
126.5
151.9
176.3
200.7
Seasonal Efficiency – %
96.4
95.6
95.6
93.2
96.7
95.0
95.1
95.3
Shipping Weight – kg
75
79
102
129
138
154
168
184
NO
X
Class
5
GAS DATA – G20
Nominal gas inlet pressure – mbar
20.0
Maximum gas inlet pressure – mbar
25.0
Minimum gas inlet pressure – mbar
17.5
Gas flow rate – m
3
/hr
4.2
5.9
8.0
11.1
14.0
16.8
19.6
22.3
Flue gas mass rate – g/sec
(@ 9.0% CO
2
)
16.0
22.3
30.4
42.5
53.2
63.9
74.6
85.2
Gas inlet connection size – “ BSP
½
¾
1
GAS DATA – G31
Nominal gas inlet pressure – mbar
37.0
Maximum gas inlet pressure – mbar
45.0
Minimum gas inlet pressure – mbar
27.0
Gas flow rate – m
3
/hr
1.7
2.3
3.1
4.4
5.5
6.6
7.7
8.8
Flue gas mass rate – g/sec
(@ 10.5% CO
2
)
16.7
23.2
31.6
44.2
55.4
66.6
77.6
88.8
Gas inlet connection size – “ BSP
½
¾
1
WATER DATA
Water content – litres
4.9
6.4
9.1
12.9
15.9
15.9
18.9
21.6
Water connections (F & R) – “ BSP
1 ¼
2
Max. water pressure (PMS) – bar
11.0
Min. water pressure – bar
0.5
Test pressure – bar
16.5
Maximum water temperature –
C
88
FLUE DATA TYPE B
23
Nominal flue diameter – mm
80
100
150
Maximum flue gas temp. –
C
120
Maximum equivalent length – m
60
Equivalent length 90
bend – mm
1000
1500
Equivalent length 45
bend – mm
500
900
Flue gas temperature –
C
70
Flue draught requirements – mbar
-0.03 to -0.1
FLUE DATA TYPE C
13
& C
33
Nominal flue diameter – mm
80/125
100/150
150/220
Maximum flue gas temp. –
C
120
Maximum equivalent length – m
30
13
30‡
Equivalent length 90
bend – mm
1000
1500
Equivalent length 45
bend – mm
500
900
FLUE DATA TYPE C
43
& C
53
Nominal flue diameter – mm
80
100
150
Average flue gas temp. –
C
(80/60 Flow/Return)
70
Maximum flue gas temp. –
C
120
Maximum equivalent length – m
60*
Equivalent length 90
bend – mm
1000
1500
Equivalent length 45
bend – mm
500
900
TABLE 3.1
TECHNICAL DATA
‡
EKB175CE, EKB205CE and EKB235CE use a concentric terminal only. The remainder of the flue system is
to be constructed from 150mm single wall components.
*
On twin pipe systems, the maximum equivalent length is the sum the air inlet components and the exhaust
components.