Draining
40
Instruction manual CH
6
gis
6.1
Draining unvented
installations
Some service activities require the water heater to be drained. The procedure
is as follows:
1. Shut down the appliance by setting the ON/OFF switch on the control panel
to
position 0
.
2. Isolate the water heater from the power supply by putting the isolator
between the appliance and the mains power supply to position 0.
3. Shut off the gas supply (10).
4. Close the stop valve (11) in the hot water pipe.
5. Close the supply valve of the cold water supply (A).
6. Open the drain valve (9).
7. Bleed the appliance (or installation) so that it drains completely.
6.2
Draining vented
installations
Some service activities require the water heater to be drained. The procedure
is as follows:
1. Shut down the appliance by setting the ON/OFF switch on the control panel
to
position 0
.
2. Isolate the water heater from the power supply by putting the isolator
between the appliance and the mains power supply to position 0.
3. Shut off the gas supply (10).
4. Close the stop valve (11) in the hot water pipe.
5. Close the stop valve (4) between the cold water head tank and the cold
water inlet.
6. Open the drain valve (9).
7. Bleed the appliance (or installation) so that it drains completely.
Summary of Contents for CH 100 CE
Page 4: ...4 Instruction manual CH gis...
Page 10: ...Introduction 10 Instruction manual CH 1 gis...
Page 16: ...Working principle of the water heater 16 Instruction manual CH 2 gis...
Page 36: ...Conversion to a different gas category 36 Instruction manual CH 4 is...
Page 44: ...Status of the water heater 44 Instruction manual CH 8 gis...
Page 46: ...Starting the water heater 46 Instruction manual CH 9 gis...
Page 48: ...Shutting down 48 Instruction manual CH 10 gis...
Page 62: ...Electrical diagram 62 Instruction manual CH 14 is...
Page 64: ...Declaration of Conformity 64 Instruction manual CH 15 is...