2.0 Installation
2.1 Mounting the Controller Enclosure
The DC4000 conductivity controller is supplied with integral wall-mounting flanges. It should be mounted with the
display at eye level on a vibration free surface. All accessibe mounting holes should be utilized. The maximum allow
-
able temperature is 122° F [50° C]. This should be considered if installation is in a high-temperature location. Once
the DC4000 is wall mounted, the metering pumps may be located at any distance from the controller. The conductivity
probe should be placed as close to the controller as possible. Consult factory for distance over 30 ft [9 m]. Under 25 ft
[7.6 m] is recommended. Over 30 ft [7.6 m], the cable may need to be isolated or shielded.