No.
Functions
Functio
ns
Remark
1
DC input B-
2.5mm
DC Power Supply negative input,external starter battery’s
negative.
2
DC input B+
2.5mm
DC Power Supply positive input of the the external starter
battery positive, it is recommended to use 20A fuse.
3
Emergency stop
2.5mm
DC voltage through the emergency stop button connected
equipment supplied to the fuel and starter relay output,
recommended maximum 30A fuse.
4
Fuel relay output
1.5mm
By the 3-terminal DC voltage supply, rated current 16A
5
Start relay output
1.5mm
By the 3-terminal DC voltage supply, rated current 16A
6
Aux. Output 1
1.5mm
By the B + supply output Rated current 7A
7
Aux. Output 2
1.5mm
8
Aux. Output 3
1.5mm
9
Charger(D+)
1.0mm
Connect to charge generators D+ (WL) terminals. Being hang
up If there is no the terminal.
10
Aux. Output 4
1.5mm
Normally close outputs, rated 7A
11
1.5mm
Public points of relay
12
1.5mm
Normally open outputs, rated 7A.
13
Genset A-phase voltage
sensing input
1.0mm
Genset A-phase voltage sensing input
14
Genset B-phase voltage
sensing input
1.0mm
Connect to B-phase of gen-set (2A fuse is recommended).
15
Genset C-phase voltage
sensing input
1.0mm
Connect to C-phase of gen-set (2A fuse is recommended).
16 Gen-set N-wire input
1.0mm
Connected to N-wire of gen-set
17
Mains A-phase voltage
sensing input
1.0mm
Connect to A-phase of mains (2A fuse is recommended)
(LXC9210 without).
18
Mains B-phase voltage
sensing input
1.0mm
Connect to B-phase of mains (2A fuse is
recommended)(LXC9210 without).
19
Mains C-phase voltage
sensing input
1.0mm
Connect to C-phase of mains (2A fuse is
recommended)(LXC9210 without).
20 Mains N-wire input
1.0mm
Connected to N-wire of mains (LXC9210 without).
27 Spare
28 CAN+
0.5mm
Impedance-120Ω shielding wire is recommended, its
single-end earthed.
(controllers without RS485 don t have this terminal)
29 CAN-
0.5mm
30 CAN COM
0.5mm
31 RS485-
0.5mm
32 RS485+
0.5mm
33 RS485 COM
0.5mm
34
Aux. Output 5
(7A250VAC)
1.5mm
Normally close outputs, rated 7A
35
1.5mm
Normally open outputs, rated 7A.
36
1.5mm
Public points of relay
37 Aux. Output 6
(7A250VAC)
1.5mm
Normally open outputs, rated 7A.
38
1.5mm
Public points of relay
39 Aux. Input 1
1.0mm
Ground connected is active (B-).
40 Aux. Input 2
1.0mm
41 Aux. Input 3
1.0mm
42 Aux. Input 4
1.0mm