Flexible Sensor 1
High
When controller detects the sensor value is higher than the max. set value, it
will send stop signal.
25
Flexible Sensor 1
Low
When controller detects the sensor value is lower than the min. set value, it will
send stop signal.
26
Flexible Sensor 2
Open
When controller detects sensor is open circuit, and the action select
“shutdown”, it will send a stop signal.
27
Flexible Sensor 2
High
When controller detects the sensor value is higher than the max. set value, it
will send stop signal.
28
Flexible Sensor 2
Low
When controller detects the sensor value is lower than the min. set value, it will
send stop signal.
29
Digital Input Port
1-8
When digital input port 1-8 is set as shutdown, and the action is active, it will
send a shutdown signal.
30
D + Open
shutdown
Generator starting on the D+ connected to detect if an alarm when open.
9.2.
9.2.
9.2.
9.2. T
T
T
Trip
rip
rip
rip and
and
and
and stop
stop
stop
stop alarm
alarm
alarm
alarm
When controller detects shutdown alarm signal, it will shutdown generator quickly and stop after high
speed cooling.
Trip and stop alarm as following:
Trip
Trip
Trip
Trip and
and
and
and stop
stop
stop
stop alarm
alarm
alarm
alarm
No.
No.
No.
No.
Type
Type
Type
Type
Description
Description
Description
Description
1
Over Current
When controller detects the value is higher than the set value, and the
action select “trip and shutdown”, it will send trip and stop signal.
2
Current Negative
Phase Sequence
When the generator is three-phase load imbalance between the current
and larger than the set value, generating a trip and downtime.
3
Maintenance1-3
When count down time is 0 and the action select “trip and shutdown”, it
will send a trip and stop signal.
6
Reverse Power
When controller detects reverse power value (power is negative) is lower
than the set value, and the action select“trip and shutdown”, it will send a
trip and stop signal.
7
Over Power
When controller detects the over power value (power is positive) is higher
than the set value, and the action select“trip and shutdown”, it will send a
trip and stop signal.
8
Low Fuel
When a trip is generated when the fuel level is low and shut down.
9
Digital Input Ports 1-8
When digital input port1-8 is set as “trip and shutdown”, and the action is
active, it will send a trip and stop signal.