LXC9220/LXC9210
Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC9220/LXC9210 Product User Manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
�
:
T:+86-769-23836636
�
:
F:+86-769-23166296
�
:
www.lixise.com
Page
27
of
58
11
Charge Alt Fail
When controller detects the charger voltage is lower than the set
value, it will send warn signal.
12
Battery Over Voltage
When controller detects the battery voltage is higher than the set
value, it will send warn signal.
13
Battery Under Voltage
When controller detects the battery voltage is lower than the set
value, it will send warn signal.
14
Maintenance1-3 warn
When count down time is 0 and the action select “Warn”, it will send
warn signal.
17
Reverse Power
When controller detects the reverse power value (power is negative)
is lower than the set value, it will send warn signal.
18
Over Power
When controller detects the reverse power value (power is positive)
is higher than the set value, it will send warn signal.
19
Gen Loss of Phase
When controller detects the generator loss phase, it will send warn
signal.
20
Gen Phase Sequence
Wrong
When controller detects the reverse phase, it will send warn signal.
21
Gen load Close Fail
When the controller gen start closing state input is detected, the
default close delay is not detected,the issue of closing failure
warning. This warning does not automatically eliminated.
(You can press the mute button to eliminate)
22
Main Load Close Fail
When the controller main start opening state input is detected, the
default open delay is not detected,the issue of opening failure
warning.This warning does not automatically eliminated.(You can
press the mute button to eliminate)
23
Gen Load Open Fail
When the controller gen start opening state input is detected, the
default open delay is not detected,the issue of opening failure
warning.This warning does not automatically eliminated.(You can
press the mute button to eliminate)
24
Main Load Open Fail
When the controller main start opening state input is detected, the
default open delay is not detected,the issue of opening failure
warning.This warning does not automatically eliminated.(You can
press the mute button to eliminate)
25
Temp. Sensor Open
When controller detects the sensor is open circuit, and the action
select“warn”, it will send warn signal.
26
High Temp. Warn
When controller detects the temperature is higher than the set value,
it will send warn signal.
27
Low Temp. Warn
When controller detects the temperature is lower than the set value,
it will send warn signal.
28
Oil Pressure Sensor
Open
When controller detects the sensor is open circuit, and the action
select “warn”, it will send warn signal.
29
Low OP Warn
When controller detects the oil pressure is lower than the set value, it
will send warn signal.
30
Level Sensor Open
When controller detects the sensor is open circuit, and the action
select “warn”, it will send warn signal.
31
Low Level Warn
When controller detects the oil lever is lower than the set value, it will
send warn signal.
32
Flexible Sensor 1 Open
When controller detects the sensor is open circuit, and the action
select “warn”, it will send warn signal.