background image

AF0100 Arc-Flash Relay

GENERATOR APPLICATION GUIDE

3

Littelfuse.com/ArcFlash

© 2017 Littelfuse Products

GENERATORS

 

Generators are often used to ensure continuity of energy for mission-critical applications. There are five key reasons 

generators are vulnerable to arc flash and this guide explains how to mitigate this risk. 

1. 

The high levels of energy from the generator and low impedance (due to being near the energy source) put 

the generator at risk.

2. 

Many mobile generators are used in cooling applications in warm, humid, and sometimes dusty geographies 

where the increased conductivity of the air that’s insulating the exposed conductors can increase the risk of 

an arc flash.

3. 

Mobile generators used in cold environments are sources of warmth that can attract rodents and small 

animals that burrow into the unit and precipitate an arc flash. 

4. 

Low zero-sequence impedance of generator windings result in arc flash on a ground fault for solidly  

grounded generators.

Generators also pose an increased safety risk due to the nature of their construction. Typically, generators only 

allow a narrow space for personnel to work and perform their maintenance. In many cases, arc flash calculations 

limit burn time to two seconds for workers to get clear of the danger. In a generator application, the personnel 

are trapped in the enclosure during an arc flash and exposed to the arc for an extended amount of time. It is 

necessary for arc-flash calculations in confined spaces to increase the arc duration, resulting in even higher levels 

of incident energy. The arc blast itself can thrust personnel into the walls of the enclosure with enough force to 

be fatal.

 

Challenges Unique to Generators:

 

§

Available space limitations

 

§

Two sources of energy must be disconnected: 

1.  The generator

2.  Bus connecting to parallel generators or utility

 

§

Vibration from generator operation and transport to and from job sites

 

§

Harsh environments with extreme heat and humidity

 

§

Section between the generator and the generator breaker has no overcurrent protection

Generators with breakers that are rated or can be set above 1200 A (even if they are set below that point) require 

a means of arc-flash mitigation. This would apply to a connected substation, switchgear, or other downstream 

equipment, but could also be considered on a generator capable of producing 1200 A or more (250 kW or higher). 

NEC

® 

240.87 (B.4) allows arc-flash relays as a cost-effective means of mitigation.

 

Mobile generator destroyed by arc-flash.

Summary of Contents for AF0100

Page 1: ...GENERATOR APPLICATION GUIDE AF0100 ARC FLASH RELAY...

Page 2: ...ckground 4 Methods 4 GENERATOR PROTECTION USING AF0100 5 Generator To Generator Breaker Connection 5 Transformer Enclosure 5 AF0100 CONNECTION DIAGRAM 6 SENSOR COVERAGE 7 EFFECT OF GENERATOR GROUNDING...

Page 3: ...r maintenance In many cases arc flash calculations limit burn time to two seconds for workers to get clear of the danger In a generator application the personnel are trapped in the enclosure during an...

Page 4: ...An instantaneous trip setting that is less than the available arcing current 6 An instantaneous override that is less than the available arcing current 7 An approved equivalent means ANSI Z10 RISK CON...

Page 5: ...also turn off the generator The latter is usually accomplished by either connecting to the automatic voltage regulator AVR an emergency stop circuit or generator controller Often the voltages require...

Page 6: ...spaces of mobile gensets PC CONNECTION TRIP OUTPUT 1 TRIP OUTPUT 2 100 240 VAC DC SUPPLY 24 48 VDC SUPPLY DIGITAL INPUTS OUTPUTS UNIT HEALTH AF0100 CONNECTION DIAGRAM Generators are often the last li...

Page 7: ...sor design can withstand a detected arc flash event Sensor can be installed up to 50 m 164 ft away from relay electrical cable can be cut and easily re terminated in the field Fiber Optic Light Sensor...

Page 8: ...or three phase fault levels only resulting in mechanical damage during a ground fault even if the fault is not arcing The Littelfuse SE 701 Ground Fault Relay can monitor for a wide range of current l...

Page 9: ...ult relay especially suitable for rental units PGR 4300 Series Generator Ground Fault Relay Generator Ground Fault Relay for solidly grounded generators No CT required Generator ground fault current c...

Page 10: ...tic configuration minimize labor costs Seamless to your customer no customer interaction required with arc flash relay We are a global partner for your global business Global certifications Global dis...

Page 11: ...nit AF0100 Arc Flash Relay Date and Time Synchronize to PC Clock Disabled o Enabled o Disabled Light Sensors Common Settings Light Immunity Lower Limit 10 10 25 klux klux Arc Detection Time Before Tri...

Page 12: ...ns contact our Technical Support Group 800 832 3873 Specifications descriptions and illustrative material in this literature are as accurate as known at the time of publication but are subject to chan...

Reviews: