background image

AF0100 Arc-Flash Relay

GENERATOR APPLICATION GUIDE

8

Littelfuse.com/ArcFlash

© 2017 Littelfuse Products

EFFECT OF GENERATOR GROUNDING ON ARC-FLASH RISK

Ungrounded Generator

A re-striking or arcing ground fault on a generator can result in transient overvoltage, a condition where phase 

voltages can be six to eight times the line-to-line voltage above ground as energy is stored in the capacitance of 

the system instead of discharging through a grounding connection. This results in insulation degradation inside the 

generator and can result in an explosive arc flash as the insulation fails, potentially in multiple locations.
The Littelfuse EL3100 Ground-Fault Relay can detect a grounded phase on ungrounded generators up to 600-V and 

offers both indication and a relay output to alarm or trip the generator.

Solidly Grounded Generator

Generators have low zero-sequence reactance, meaning that ground-fault current on a solidly grounded generator 

can exceed three-phase fault current levels. According to IEEE Std 141-1993 7.2.2, high values of ground-fault current 

can destroy the magnetic core of rotating machinery. High currents also mean that ground faults (which are the most 

common type of electrical fault) can result in an arc flash. Mechanical bracing in generators is also typically rated for 

three-phase fault levels only, resulting in mechanical damage during a ground fault even if the fault is not arcing.

The Littelfuse SE-701 Ground-Fault Relay can monitor for a wide range of current levels and works with any 5-A or 

1-A secondary as well as sensitive Littelfuse CTs for detection down to 50 mA. For applications where there is not 

sufficient space for a CT, the PGR-4300 Ground-Fault Relay connects between the generator and grounding rod to 

detect ground-fault currents from 100 A to 1200 A.

Resistance-Grounded Generator

High-resistance grounding eliminates arc-flash hazards on the first ground fault and reduces burning of stator 

windings during an internal generator ground fault. By adding a neutral-grounding resistor (NGR), the mechanical 

damage from low zero-sequence reactance of generators is also eliminated. Even for uptime-critical generators that 

might normally be ungrounded, it is permissible to continue running a generator on a ground fault so long as the 

current is limited to 10 A and the generator is 4160 V or less. It is critical that the NGR is monitored using an NGR 

monitor to ensure that the generator remains grounded at all times. Littelfuse recommends continuously monitored 

high-resistance grounding for generators. 

Use the Littelfuse SE-704 Ground-Fault Relay for high-resistance grounded generators. As well, ground-fault 

protection can be combined with continuous neutral-grounding resistor monitoring using the Littelfuse SE-325 or  

SE-330 NGR Monitors.

Summary of Contents for AF0100

Page 1: ...GENERATOR APPLICATION GUIDE AF0100 ARC FLASH RELAY...

Page 2: ...ckground 4 Methods 4 GENERATOR PROTECTION USING AF0100 5 Generator To Generator Breaker Connection 5 Transformer Enclosure 5 AF0100 CONNECTION DIAGRAM 6 SENSOR COVERAGE 7 EFFECT OF GENERATOR GROUNDING...

Page 3: ...r maintenance In many cases arc flash calculations limit burn time to two seconds for workers to get clear of the danger In a generator application the personnel are trapped in the enclosure during an...

Page 4: ...An instantaneous trip setting that is less than the available arcing current 6 An instantaneous override that is less than the available arcing current 7 An approved equivalent means ANSI Z10 RISK CON...

Page 5: ...also turn off the generator The latter is usually accomplished by either connecting to the automatic voltage regulator AVR an emergency stop circuit or generator controller Often the voltages require...

Page 6: ...spaces of mobile gensets PC CONNECTION TRIP OUTPUT 1 TRIP OUTPUT 2 100 240 VAC DC SUPPLY 24 48 VDC SUPPLY DIGITAL INPUTS OUTPUTS UNIT HEALTH AF0100 CONNECTION DIAGRAM Generators are often the last li...

Page 7: ...sor design can withstand a detected arc flash event Sensor can be installed up to 50 m 164 ft away from relay electrical cable can be cut and easily re terminated in the field Fiber Optic Light Sensor...

Page 8: ...or three phase fault levels only resulting in mechanical damage during a ground fault even if the fault is not arcing The Littelfuse SE 701 Ground Fault Relay can monitor for a wide range of current l...

Page 9: ...ult relay especially suitable for rental units PGR 4300 Series Generator Ground Fault Relay Generator Ground Fault Relay for solidly grounded generators No CT required Generator ground fault current c...

Page 10: ...tic configuration minimize labor costs Seamless to your customer no customer interaction required with arc flash relay We are a global partner for your global business Global certifications Global dis...

Page 11: ...nit AF0100 Arc Flash Relay Date and Time Synchronize to PC Clock Disabled o Enabled o Disabled Light Sensors Common Settings Light Immunity Lower Limit 10 10 25 klux klux Arc Detection Time Before Tri...

Page 12: ...ns contact our Technical Support Group 800 832 3873 Specifications descriptions and illustrative material in this literature are as accurate as known at the time of publication but are subject to chan...

Reviews: