8
/14
• End cap with mesh shall be mounted on the side not connected
to air duct.
• End cap with mesh is made from galvanized steel sheet.
• End cap with mesh is supplied not installed on the fire damper.
Components (Transfer Application)
1. End cap with mesh (to fix to fire damper with steel screws)
2. Fire damper
Technical data (Transfer Application)
1. Mechanism side
2. Mechanism opposite side
3. End cap with mesh
L1 End cap length mechanism side
L2 End cap length mechanism
opposite side
Ø Fire damper nominal diameter
Length of end cap with mesh depending on fire damper dia-
meter Ø.
Ø
L1
L2
200
60
60
250
60
60
300
60
60
315
60
60
355
60
60
400
80
80
450
80
80
500
80
80
560
80
80
600
80
80
630
80
80
710
120
120
800
170
170
Ø
Fire damper nominal diameter
L1
End cap length mechanism side
L2
End cap length mechanism opposite side
rev 20-10
8
We reserve the right to make changes without prior notice