Lindab WH45 Series Installation Booklet Download Page 10

10

/14

 

„

Construction supports characteristics

The European standard for fire dampers foresees a precise correlation 

between the wall/floor characteristics and the fire resistance class 

obtained, as well as the correlation between wall/floor used for the 

test and wall/floor used for the actual installation.

The test results obtained on a type of wall/floor are valid also for wal-

ls/floor of the same type but with greater thickness and/or density 

than those used in the test.

For plasterboard walls, the test results are also valid for walls with a 

greater number of plasterboard layers on each side.

As a result, the indicated thickness and density characteristics are to 

be considered as minimum values.

The wall/floor in which the fire dampers are installed must be fire 

class certified according to the standards foreseen for the structure.

 

†

Rigid walls

Can be made with aerated concrete blocks, poured concrete, concre-

te panels, perforated cell elements in concrete or brick in accordance 

with the following characteristics:

•  minimum thickness 100 mm;

•  minimum density 500 kg/m³.

The use of a reinforcing beam above the opening is recommended 

for walls made from concrete blocks, bricks or in concrete cell ele-

ments.

For walls built with perforated elements, it is also recommended that 

the area of the opening be made from full elements (for example 

aerated concrete blocks) to guarantee the correct adhesion of the 

mortar.

1.  Reinforcing beam

 

†

Light plasterboard vertical walls

During testing, light plasterboard walls have been used with the fol-

lowing characteristics:

•  U-shaped horizontal metal frame (50 mm) and C-shaped vertical 

frame (49 mm) made from 0,6 mm thick sheet metal;

•  Vertical profiles placed with a maximum spacing of 625 mm 

between each other;

•  Filling made of rock wool with density up to 100 kg/m³ (optional);

•  Each side is made from two plasterboard layers 12,5 mm thick, una-

linged to avoid alignment between the joints of the layer above 

and below.

The following indications are given for the installation walls:

•  metal profiles minimum width: 49 mm;

•  metal profiles minimum thickness: 0,6 mm;

•  vertical profiles placed with a maximum spacing of 625 mm 

between each other;

•  vertical profile fixing with selfthreading screws or by clinching to 

the bottom horizontal profile and insertion in the top horizontal 

profile;

•  profiles fixed using self-threading screws or by clinching on every 

intersection.

•  installation of a frame around the damper with base and height 

where shown in the installation instructions;

•  Filling made of rock wool with density up to 100 kg/m³ (optional);

•  each side is made from two plasterboard layers 12,5 mm minu-

mum thick, unalinged to avoid alignment between the joints of 

the layer above and below.

•  the front plasterboards layers are fixed using long enough screws 

to pass through the lower plasterboard and attach to the steel pro-

file underneath.

1.  Plasterboard thickness 12,5 mm

2.  Rock wool density up to 100 kg/m³ (optional)

3.  Horizontal U-shaped profile

4.  Vertical C-shaped profile

5.  Self-drilling screw Ø 3,5 X 25 mm

6.  Self-drilling screw Ø 3,5 X 35 mm

 

†

Light plasterboard vertical walls with steel reinforcement

During testing, light plasterboard walls have been used with the fol-

lowing characteristics:

•  U-shaped horizontal metal frame (50 mm) and C-shaped vertical 

frame (49 mm) made from 0,6 mm thick sheet metal;

•  Vertical profiles placed with a maximum spacing of 312,5 mm 

between each other;

•  reinforcement sheet;

•  Filling made of rock wool with density up to 100 kg/m³ (optional);

•  Each side is made from two plasterboard layers 12,5 mm thick, una-

linged to avoid alignment between the joints of the layer above 

and below.

The following indications are given for the installation walls:

•  metal profiles minimum width: 49 mm;

•  metal profiles minimum thickness: 0,6 mm;

•  vertical profiles placed with a maximum spacing of 312,5mm 

between each other;

•  vertical profile fixing with selfthreading screws or by clinching to 

the bottom horizontal profile and insertion in the top horizontal 

profile;

•  profiles fixed using self-threading screws or by clinching on every 

intersection.

•  installation of a frame around the damper with base and height 

where shown in the installation instructions;

•  Filling made of rock wool with density up to 100 kg/m³ (optional);

•  each side is made from two plasterboard layers 12,5 mm minu-

mum thick, unalinged to avoid alignment between the joints of 

the layer above and below.

rev 20-10

10

We reserve the right to make changes without prior notice

Summary of Contents for WH45 Series

Page 1: ...ww mp3 italia it 1MUBWH45EN rev 20 10 1MUBWH45EN WH45 WH45 l indab we simplify co nstruc tio n www lindab com Fire dampers are manufactured by MP3 Srl www mp3 italia it 1MUBWH45EN LIND rev 20 10 1MUBW...

Page 2: ...cal light wall gypsum blocks wall Wall minimum thickness 70 mm Wall minimum density 995 kg m Plaster putty sealing ve i o W min 200 max 800 min 200 max 800 min 200 max 800 EI 120 S Installation within...

Page 3: ...ade position open or closed Refer to Electrical connections paragraph for more details Closing by remote control With power supply input or interruption magnet WH45M version only Temperature calibrati...

Page 4: ...sup plied to the motor Position indication microswitches The motorized versions are supplied with two microswitches to show the blade s position open or closed Refer to the section Electrical connect...

Page 5: ...ollows Check that the voltage and electrical frequency are equivalent to those of the motor of the servomotor check the motor s informa tion label Make the connections as shown in the below diagram 1...

Page 6: ...W Motor 230V AC WH45DPS WH45DSS Siemens GNA326 GRA326 Opening 4 5 W In stand by 3 5 W 24V AC DC motor WH45VGS Siemens GGA126 Opening 6 W In stand by 1 5 W 230V AC motor WH45DGS Siemens GGA326 Opening...

Page 7: ...ance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 INSTALLATION The sizes shown are in mm It is recommended to perform a functional test before Insta...

Page 8: ...echanism side 2 Mechanism opposite side 3 End cap with mesh L1 End cap length mechanism side L2 End cap length mechanism opposite side Fire damper nominal diameter Length of end cap with mesh dependin...

Page 9: ...floor Installation a mm b mm c mm d mm Rigid wall EI 90 S Installation within vertical rigid wall Plasterboard and rock wool 100 kg m sealing 50 75 EI 120 S Installation within vertical rigid wall Mor...

Page 10: ...pacing of 625 mm between each other vertical profile fixing with selfthreading screws or by clinching to the bottom horizontal profile and insertion in the top horizontal profile profiles fixed using...

Page 11: ...ol lowing characteristics minimum thickness 100 or 150 mm according to the resistance class required minimum density 2200 kg m Installations within vertical rigid wall Refer to the section Constructio...

Page 12: ...for further information Wall opening A opening must be provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the...

Page 13: ...l as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the table and in the drawing Clos...

Page 14: ...he drawing Sealing with concrete is not allowed Fire resistance classification D hole size mm Damper protrusion from the floor E mm Floor minimum thickness S mm Sealing EI 90 S Installation within flo...

Reviews: