Lindab WH45 Series Installation Booklet Download Page 2

2

/14

OVER VIEW

 

„

Fire resistance classification according to EN 13501-3-2009

EI 180 S

(500 Pa)

EI 120 S

(500 Pa)

EI 90 S

(500 Pa)

EI 60 S

(500 Pa)

EI 30 S

(500 Pa)

Rigid w

all

EI 120 S Installation within vertical rigid wall 
Wall minimum thickness 100 mm

 Wall minimum density 500 kg/m³

Mortar or plaster putty sealing

ve (i

o)

W

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

EI 90 S Installation within vertical rigid wall 
Wall minimum thickness 100 mm

 Wall minimum density 500 kg/m³

Plasterboard and rock wool 100 kg/m³ sealing

ve (i

o)

D

-

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Fle

xible w

all

EI 90 S Installation within vertical light wall (plasterboard) 
Wall minimum thickness 100 mm

Wall rock wool density up to 100 kg/m³ (optional)

Plasterboard and rock wool 100 kg/m³ sealing

ve (i

o)

D

-

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

EI 120 S Installation within vertical light wall (plasterboard) 
Wall minimum thickness 100 mm

Wall rock wool density up to 100 kg/m³ (optional)

Mortar or plaster putty sealing

ve (i

o)

W

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

EI 90 S Installation within vertical light wall (gypsum blocks wall) 
Wall minimum thickness 70 mm

Wall minimum density 995 kg/m³

Plaster putty sealing

ve (i

o)

W

-

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

EI 120 S Installation within vertical light wall (gypsum blocks wall) 
Wall minimum thickness 100 mm

Wall minimum density 995 kg/m³

Plaster putty sealing

ve (i

o)

W

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Floor

EI 90 S Installation within floor  
Floor minimum thickness 100 mm

 Floor minimum density 650 kg/m³

Mortar sealing

ho (i

o)

W

-

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

EI 120 S Installation within floor 
Floor minimum thickness 150 mm

 Floor minimum density 650 kg/m³

Mortar sealing

ho (i

o)

W

-

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

EI 180 S Installation within floor 
Floor minimum thickness 150 mm

 Floor minimum density 2200 kg/m³

Mortar sealing

ho (i

o)

W

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Ø

min 200

max 800

Ø is the minimum and maximum nominal diameter of fire dampers in mm

ve 

Vertical installation

ho 

Horizontal installation

(i

o)  Origin of fire irrelevant

Pa 

Pascal of depression

E Integrity

Thermal insulation

Smoke seal

Wet method sealing

Dry method sealing

Cert. N° 1812-CPR-1007 EN 15650

rev 20-10

2

We reserve the right to make changes without prior notice

Summary of Contents for WH45 Series

Page 1: ...ww mp3 italia it 1MUBWH45EN rev 20 10 1MUBWH45EN WH45 WH45 l indab we simplify co nstruc tio n www lindab com Fire dampers are manufactured by MP3 Srl www mp3 italia it 1MUBWH45EN LIND rev 20 10 1MUBW...

Page 2: ...cal light wall gypsum blocks wall Wall minimum thickness 70 mm Wall minimum density 995 kg m Plaster putty sealing ve i o W min 200 max 800 min 200 max 800 min 200 max 800 EI 120 S Installation within...

Page 3: ...ade position open or closed Refer to Electrical connections paragraph for more details Closing by remote control With power supply input or interruption magnet WH45M version only Temperature calibrati...

Page 4: ...sup plied to the motor Position indication microswitches The motorized versions are supplied with two microswitches to show the blade s position open or closed Refer to the section Electrical connect...

Page 5: ...ollows Check that the voltage and electrical frequency are equivalent to those of the motor of the servomotor check the motor s informa tion label Make the connections as shown in the below diagram 1...

Page 6: ...W Motor 230V AC WH45DPS WH45DSS Siemens GNA326 GRA326 Opening 4 5 W In stand by 3 5 W 24V AC DC motor WH45VGS Siemens GGA126 Opening 6 W In stand by 1 5 W 230V AC motor WH45DGS Siemens GGA326 Opening...

Page 7: ...ance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 INSTALLATION The sizes shown are in mm It is recommended to perform a functional test before Insta...

Page 8: ...echanism side 2 Mechanism opposite side 3 End cap with mesh L1 End cap length mechanism side L2 End cap length mechanism opposite side Fire damper nominal diameter Length of end cap with mesh dependin...

Page 9: ...floor Installation a mm b mm c mm d mm Rigid wall EI 90 S Installation within vertical rigid wall Plasterboard and rock wool 100 kg m sealing 50 75 EI 120 S Installation within vertical rigid wall Mor...

Page 10: ...pacing of 625 mm between each other vertical profile fixing with selfthreading screws or by clinching to the bottom horizontal profile and insertion in the top horizontal profile profiles fixed using...

Page 11: ...ol lowing characteristics minimum thickness 100 or 150 mm according to the resistance class required minimum density 2200 kg m Installations within vertical rigid wall Refer to the section Constructio...

Page 12: ...for further information Wall opening A opening must be provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the...

Page 13: ...l as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the table and in the drawing Clos...

Page 14: ...he drawing Sealing with concrete is not allowed Fire resistance classification D hole size mm Damper protrusion from the floor E mm Floor minimum thickness S mm Sealing EI 90 S Installation within flo...

Reviews: