Lindab WH45 Series Installation Booklet Download Page 3

3

/14

 

„

Mechanism type

 

†

Manual / Manual with magnet

1.  Manual opening lever

2.  Protection box

3.  Lever position when the blade is open

4.  Lever position when the blade is closed

5.  Magnet knob (for magnetic version)

6.  Closed blade indicator

7.  Open blade indicator

8.  Manual closing button

Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that automa-

tically closes the blade when the temperature in the duct exceeds 

70°C (or 95°C for the fire damper with 95°C thermal fuse).

It is possible to close the damper by pressing the indicated button.

If the manual mechanism is equipped with electromagnet it is possi-

ble to remotely close the fire damper.

The manual command mechanism with magnet is equipped with 

an electromagnet which, in case power is interrupted (interuption 

magnet version) or when power is supplied (input magnet version), 

comands the closing of the damper.

Blade opening mode

Make sure that the damper is open before the ventilation system 

start-up, otherwise there is a risk of product malfunction.

In case of closed damper by pressing the closing button or remotely 

by electromagnet (magnetic version), it is possible to manually open 

the fire damper blade by rotating the lever antyclockwise.

For power supply interruption electromagnet, provide power supply 

and pull the magnet knob before opening the fire damper.

In case of closed damper as a result of the action of the thermosen-

sitive element, it is possible to manually reopen the damper by rota-

ting the lever counterclockwise once the element has been replaced.

Position indication microswitches

On request, the fire damper can be supplied with position microswi-

tches (SA/SC/S2 optional) that signal the blade position (open or 

closed). Refer to Electrical connections  paragraph for more details.

Closing by remote control

With power supply input or interruption magnet (WH45M version 

only).

Temperature calibration of thermosensitive element for auto-

matic damper closing

70 °C±7 °C (Standard)

95 °C±9 °C (On request).

 

†

Belimo motorized version

1.  Manual closing switch

2.  Manual opening lever

3.  Position indicator

4.  Blade locking lever

Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that automa-

tically closes the blade when the temperature in the duct or in the 

room exceeds 72°C (or 95°C for the 95°C version).

To close the damper when the motor is connected, press the switch 

on the temperature sensor or cut off the power supply.

Blade opening mode

Make sure that the damper is open before the ventilation system 

start-up, otherwise there is a risk of product malfunction.

To open the damper with the electric motor driven actuator, provi-

de power supply to the motor. Refer to the section Electrical con-

nections  for further information.

To manually open the damper, use the handle supplied and carefully 

rotate clockwise to the 90° indicator. To hold the damper in open 

position operate on the lever indicated in figure.

For VGB/DGB versions to hold the damper in open position, carefully 

rotate the handle counterclockwise.

During the manual opening of the damper, power must not be sup-

plied to the motor.

Position indication microswitches

The motorized versions are supplied with two microswitches to 

show the blade's position (open or closed). Refer to the section 

Electrical connections  for further information.

Closing by remote control

If power to the motor is cut off, the blade will close.

Temperature calibration of thermosensitive element for auto-

matic damper closing

72 °C±7 °C (Standard)

95 °C±9 °C (On request).

rev 20-10

3

We reserve the right to make changes without prior notice

Summary of Contents for WH45 Series

Page 1: ...ww mp3 italia it 1MUBWH45EN rev 20 10 1MUBWH45EN WH45 WH45 l indab we simplify co nstruc tio n www lindab com Fire dampers are manufactured by MP3 Srl www mp3 italia it 1MUBWH45EN LIND rev 20 10 1MUBW...

Page 2: ...cal light wall gypsum blocks wall Wall minimum thickness 70 mm Wall minimum density 995 kg m Plaster putty sealing ve i o W min 200 max 800 min 200 max 800 min 200 max 800 EI 120 S Installation within...

Page 3: ...ade position open or closed Refer to Electrical connections paragraph for more details Closing by remote control With power supply input or interruption magnet WH45M version only Temperature calibrati...

Page 4: ...sup plied to the motor Position indication microswitches The motorized versions are supplied with two microswitches to show the blade s position open or closed Refer to the section Electrical connect...

Page 5: ...ollows Check that the voltage and electrical frequency are equivalent to those of the motor of the servomotor check the motor s informa tion label Make the connections as shown in the below diagram 1...

Page 6: ...W Motor 230V AC WH45DPS WH45DSS Siemens GNA326 GRA326 Opening 4 5 W In stand by 3 5 W 24V AC DC motor WH45VGS Siemens GGA126 Opening 6 W In stand by 1 5 W 230V AC motor WH45DGS Siemens GGA326 Opening...

Page 7: ...ance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 INSTALLATION The sizes shown are in mm It is recommended to perform a functional test before Insta...

Page 8: ...echanism side 2 Mechanism opposite side 3 End cap with mesh L1 End cap length mechanism side L2 End cap length mechanism opposite side Fire damper nominal diameter Length of end cap with mesh dependin...

Page 9: ...floor Installation a mm b mm c mm d mm Rigid wall EI 90 S Installation within vertical rigid wall Plasterboard and rock wool 100 kg m sealing 50 75 EI 120 S Installation within vertical rigid wall Mor...

Page 10: ...pacing of 625 mm between each other vertical profile fixing with selfthreading screws or by clinching to the bottom horizontal profile and insertion in the top horizontal profile profiles fixed using...

Page 11: ...ol lowing characteristics minimum thickness 100 or 150 mm according to the resistance class required minimum density 2200 kg m Installations within vertical rigid wall Refer to the section Constructio...

Page 12: ...for further information Wall opening A opening must be provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the...

Page 13: ...l as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the table and in the drawing Clos...

Page 14: ...he drawing Sealing with concrete is not allowed Fire resistance classification D hole size mm Damper protrusion from the floor E mm Floor minimum thickness S mm Sealing EI 90 S Installation within flo...

Reviews: