When using the feedback output, it is important to use the right connection setup.
Attention should be paid to the two ground connections. Power GND in the Power connector and Signal GND
in the Control connector. When using either 0-10V, Hall or PWM feedback, the Signal GND must be used. For
optimal accuracy, the Signal GND is connected to the Power GND as close as possible to the feedback input
equipment.
FEEDBACK
SIGNAL GND
50%
50%
Hall
0-10V
PWM
4-20mA
Power
supply
Feedback
input
Power connector
Control connector
POWER
POWER GND
LA37 IC actuator
WHITE
VIOLET
BROWN
BLUE
Correct wiring of Power GND and Sinal GND for IC Basic and IC Advanced
Please note that this section only applies for the following feedback options: 0-10V, Hall and PWM.