Page 45 of 80
Actuator configurations available for IC Basic, IC Advanced and Parallel
Pre-configured
Customised range
Description
Soft stop
inwards
0.3 sec. for both soft stop
directions.
0.3 sec. to 30 sec.
0 sec. can be chosen for
hard stop.
It is not possible to con-
figure values between
0.01 sec. to 0.29 sec. This
is due to the back-EMF
from the motor (increas-
ing the voltage).
Be aware that the soft
stop value equals the
deacceleration time after
stop command.
Soft stop
outwards
Soft start
inwards
0.3 sec. for both soft start
directions.
0 sec. to 30 sec.
Be aware that the soft
start value equals the
acceleration time after
start command.
To avoid stress on the
actuator, it is not recom-
mended to use 0 sec. for
soft start, due to higher
inrush current.
Soft start
outwards