IF55 ROT CANopen®
02 Transmission type
[Unsigned8, rw]
Transmission type
PDO transmission
00h (0)
Acyclic, synchronous
not implemented
01h … F0h (1 … 240)
Cyclic, synchronous
implemented
F1h … FBh (241 … 251)
not implemented - reserved
FCh (252)
Synchronous, RTR only
not implemented
FDh (253)
Asynchronous, RTR only
not implemented
FEh (254)
Asynchronous,
manufacturer specific
implemented
FFh (255)
Asynchronous, device
profile specific
not implemented
Default = 01h (synchronous transmission at each SYNC command)
The position value is transmitted after the set number of SYNC
commands.
The interval between the SYNC commands must be set next to this
, sub 2 object.
WARNING
Following an attempt to set the
Transmission Type
to 0, the value is
accepted but the PDO message is not sent; following an attempt to
change the
Transmission Type
to any other value that is not supported
by the device, an abort message (abort code = 0609 0030h:
Invalid
value for parameter
) is generated.
If the value next to the
≠
0, the PDO
message is sent cyclically and the interval between two messages is the
time set next to the
object = 0, the PDO message is
not sent.
NOTE
Refer to the “7 - Setting-up” section on page 81 for an example of how the
object is to be set.
NOTE
- The transmission of PDO1, PDO2 and PDO3 messages can be enabled (or
disabled) by setting to “0” (or “1”) the most significant bit (MSB) used by PDO
(
180xh
, sub1 object).
- The cyclic transmission or synchronous transmission can be modified by
setting the
180xh
sub 2 object. If you need the position value to be
transmitted every “n” SYNC commands, you must set the “n” value next to the
180xh
sub 2 object: