Installation Drawings 29
Figure 11 Seismic Anchor Drawing: 100 – 250 Amp STS2
STATICSWITCH2/OUTLINE/PS211105
10/24/02
PS211105
OUTLINE DRAWING
SEISMIC ANCHORING
100 - 250 AMP
STATIC TRANSFER SWITCH 2
5. MOVE CABINET INTO POSITION WITH REAR TABS INTO SLOTS OF
FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR
BRACKET (FIG. 2). THEN ATTACH FRONT FLOOR BRACKETS TO FRONT
CABINET BASE BRACKET BUT DO NOT FULLY TIGHTEN HARDWARE.
6. MARK HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL
FLOOR BRACKETS. UNIT DOOR CAN BE REMOVED FOR BETTER ACCESS.
REINSTALL FRONT FLOOR BRACKETS TO FRONT CABINET BRACKETS WITH
SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).
7. IF SIDE WALLS ARE PRESENT, 5.0 INCH MINIMUM DISTANCE FROM EITHER
SIDE WALL IS REQUIRED.
8. REAR AND FRONT FLOOR BRACKETS, AND REAR AND FRONT CABINET
BASE BRACKETS ARE 1010 STEEL AND APPROX. .25 INCH THICK.
NOTES:
1. RECOMMENDED FLOOR ANCHOR: 1/2" ITW RAMSET/RED HEAD
SELF DRILLING ANCHOR, ICBO #ER-1372 OR EQUIVALENT (NOT
(SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.
2. POSITION REAR FLOOR BRACKETS ON FLOOR AT LEAST .75"
FROM BACK WALL. MARK LOCATION AND DRILL HOLES (FIG. 1) TO
A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.
3. INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING
HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL.
USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).
NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER
BRACKET IS SECURED.
4. INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING
HOLES ON UNDERSIDE OF UNIT WITH BENT FLANGE FACING FRONT.
USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).
NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER
BRACKET IS SECURED.
SYSTEM SEISMIC ANCHORING, FIGURE 1
FLOOR LINE
FLOOR LINE
FRONT CABINET
BASE BRACKET
HARDWARE
SUPPLIED
FRONT DOOR
TOP VIEW
FIGURE 3
FIGURE 2
REAR FLOOR
BRACKET
FLOOR ANCHOR
HARDWARE
(NOT SUPPLIED)
REAR CABINET
BASE BRACKET
BACK
WALL
APPROX 1/2"
FRONT FLOOR
BRACKET
OF CABINET
FLOOR ANCHOR
HARDWARE
NOT SUPPLIED
(335 MM)
(107 MM)
4.2"
(335 MM)
13.2"
13.2"
32.75"
(832 MM)
(107 MM)
(256 MM)
FRONT
10.1"
4.2"
(146 MM)
5.75"
BACK WALL
REAR FLOOR
BRACKET
SEE NOTE (2)
FOR SPACING
SIDE WALL
FRONT FLOOR
BRACKET
SEE NOTE (7)
FOR SPACING
DATE
FILE NAME:
COLUMBUS, OHIO 43229
1050 DEARBORN DRIVE,
REV. NO.
DWG. NO.
V CARMONA
REF. DWG.
CHK BY
DRAWN BY
Summary of Contents for Static Transfer Switch 2
Page 2: ......
Page 8: ...vi...
Page 12: ...x...
Page 16: ...4 Channel 4 Channel 5 Channel 6 Channel 7 Channel 8 Channel 9 Channel 10 PRB Notes...
Page 18: ...6...
Page 34: ...22 Options...
Page 62: ...50 Installation Drawings...
Page 90: ...78 Communication Interfaces...
Page 110: ...98 STS2 Touch Screen Display...
Page 146: ...134 Event Message Help Text...
Page 149: ......