120 Event Message Help Text
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA
and press RETURN on your keyboard.
CB1 SHUNT TRIP FAIL
Circuit Breaker 1 Shunt Trip Failure
Circuit Breaker 1 failed to trip open when the control issued a command for the circuit breaker to trip.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2
system from a terminal, type
SH
and press RETURN on your keyboard to turn off the audible alarm.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contiguous
United States contact Liebert Global Services, if available in your area. For international areas not covered by Liebert
Global Services, the Liebert authorized distributor can provide technical support.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA
and press RETURN on your keyboard.
CB2 SHUNT TRIP FAIL
Circuit Breaker 2 Shunt Trip Failure
Circuit Breaker 2 failed to trip open when the control issued a command for the circuit breaker to trip.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2
system from a terminal, type
SH
and press RETURN on your keyboard to turn off the audible alarm.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contiguous
United States contact Liebert Global Services, if available in your area. For international areas not covered by Liebert
Global Services, the Liebert authorized distributor can provide technical support.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA
and press RETURN on your keyboard.
HEAT SINK OVERTEMP
Heat Sink Over Temperature
The system heat sink temperature has exceeded the design limits.
Take immediate steps to cool the unit. Remove obstructions from the air inlet in the front of the unit. Remove and
replace the air filter behind the front door. A standard furnace filter can be used.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2
system from a terminal, type
SH
and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
Summary of Contents for Static Transfer Switch 2
Page 2: ......
Page 8: ...vi...
Page 12: ...x...
Page 16: ...4 Channel 4 Channel 5 Channel 6 Channel 7 Channel 8 Channel 9 Channel 10 PRB Notes...
Page 18: ...6...
Page 34: ...22 Options...
Page 62: ...50 Installation Drawings...
Page 90: ...78 Communication Interfaces...
Page 110: ...98 STS2 Touch Screen Display...
Page 146: ...134 Event Message Help Text...
Page 149: ......