112 Specifications
15.2.11 RS-232 Interface Parameters
The service terminal interface parameters are the following settings and cannot be changed.
15.2.12 Maintenance Bypass
The STS2 is configured to allow the unit’s electronics to be bypassed to either input source for
maintenance without interruption of power to the load.
The STS2 is furnished with key-interlocked maintenance bypass breakers to configure the bypass.
STS2 units have all electronics isolated from the input, output, and bypass connections to allow
safe servicing of any components without access to hazardous voltages when the unit is in mainte-
nance bypass.
See
10.4 - Maintenance Bypass
on page 61 for instructions using the Color LCD Graphical Dis-
play unit and
14.2.3 - Maintenance Bypass
on page 104 for instructions using the LED units.
15.2.13 Fuseless Design
All STS2 units are fuseless and are UL rated for use with upstream circuit breakers only.
15.2.14 Options
The following options are available for the STS2:
See
6.0 - Options
on page 18 for more information.
Table 25
RS-232 Settings
Parameter
Setting
Interface
RS-232 Using EIA Voltage Levels
Baud Rate
9600
Parity None
Number of Data Bits
8
Number of Stop Bits
1
Hardware Flow Control
Off
Terminator <CR>
<LF>
Handshaking Not
supported
Structure Full
duplex
Local Echo
Off
• Redundant Output Breaker
• Seismic Floor Stand
• Input Junction Boxes and Cable
• Export Crating
• Comms Board w/SiteScan and Modem Interface
• Internal Modem
• Input Contact Isolator Board
• Remote Source Selection
• Programmable Relay Board
• Key Lockout Switch
• Network Interface Card (NIC)
Summary of Contents for Static Transfer Switch 2
Page 2: ......
Page 8: ...vi...
Page 12: ...x...
Page 16: ...4 Channel 4 Channel 5 Channel 6 Channel 7 Channel 8 Channel 9 Channel 10 PRB Notes...
Page 18: ...6...
Page 34: ...22 Options...
Page 62: ...50 Installation Drawings...
Page 90: ...78 Communication Interfaces...
Page 110: ...98 STS2 Touch Screen Display...
Page 146: ...134 Event Message Help Text...
Page 149: ......