Vertiv
|
Liebert
®
EXM
™
BDC User Manual | Rev. 3 | 01/18 |
37
Table 12
Liebert EXM BDC input currents, dual input, bypass, without transformer
Voltage
3-Ph, 60 Hz
BDC Rating
kVA
Bypass Input
Current
BIB/MBB, A, Max
Bypass Recommended
Upstream Protection, A
Phase
75°C Wire
Current, A Total
Copper
Wire
Aluminum
Wire
Bolt Size
208/120
220/127
10
28
40
3W + N + G
50
(1) #6
(1) #4
M12
208/120
220/127
15
42
70
3W + N + G
85
(1) #4
(1) #2
M12
208/120
220/127
20
56
80
3W + N + G
115
(1) #2
(1) #2
M12
208/120
220/127
30
83
125
3W + N + G
130
(1) 1/0
(1) 2/0
M12
208/120
220/127
40
111
175
3W + N + G
175
(1) 3/0
(1) 4/0
M12
208/120
220/127
60
167
250
3W + N + G
285
(1) 350kcmil
(2) 2/0
M12
208/120
220/127
80
222
350
3W + N + G
400
(2) 3/0
(2) 4/0
M12
208/120
220/127
100
278
450
3W + N + G
460
(2) 4/0
(2) 300 kcmil
M12
Refer to
Figures 26
and
27
for additional details about this system configuration.
Table 13
Liebert EXM BDC output currents
Voltage
3-Ph, 60Hz)
BDC
Rating, kVA
System
Output
Current
A, Max
Phase
Recommended
Upstream
Protection, A
75°C
Wire
Current
A, Total
Copper
Wire
Aluminum
Wire
Bolt
Size
208/120
220/127
10
28
3W + N + G
40
50
(1) #6
(1) #4
M12
208/120
220/127
15
42
3W + N + G
60
85
(1) #4
(1) #2
M12
208/120
220/127
20
56
3W + N + G
70
115
(1) #2
(1) #2
M12
208/120
220/127
30
83
3W + N + G
110
130
(1) 1/0
(1) 2/0
M12
208/120
220/127
40
111
3W + N + G
150
175
(1) 3/0
(1) 4/0
M12
208/120
220/127
60
167
3W + N + G
225
285
(1) 350kcmil
(2) 2/0
M12
208/120
220/127
80
222
3W + N + G
300
400
(2) 3/0
(2) 4/0
M12
208/120
220/127
100
278
3W + N + G
350
460
(2) 4/0
(2) 300kcmil
M12