3.0 SPECIFICATIONS
The following are approved branch breakers for the panel boards used in the EXM BDC.
Listed (DIVQ), Schneider Electric Square D branch circuit breakers:
•
Type QOB, rated 22 kA, 150 A maximum
•
Type QO, rated 22 kA, rated 100 A maximum
•
Type QOB, rated 10 kA, rated 100 A maximum
•
Type QO, rated 10 kA, rated 100 A maximum
Table 6
Physical standards and parameters
Bypass Distribution Cabinet Parameters
Values
Standard Color
Black (ZP-7021)
Front Door Opening (for serviceability)
More than 180°
Degree of Protection for UPS Enclosure
IP 20 (with and without front door open)
Minimum Clearance, Top
24" (610mm)
Minimum Clearance, Back
0" (5" [127mm] when seismic brackets are used)
Minimum Clearance, Sides
0"
Cable Entrance
Top or Bottom
Standards & Conformities
UL 1778 5th Ed.; CSA 22.2 107.3-14
FCC Part 15, Class A; ISTA Procedure 1H; WEEE;
IBC 2012/CBC 2010
Environmental
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
32°F to 86°F (0-30°C) when seismic brackets are used
Relative Humidity
up to 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude Above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) -
1% Maximum kW derate / 100m rise between 1500-3000m
Table 7
Mechanical characteristics, Liebert EXM BDC, 10-100kVA
Dimensions, W x D x H, in (mm)
23.625 x 39.375 x 78.73
Frame Size
mm
Rating
kVA
Weight, lb. (kg)
No Transformer
No Distribution
No Transformer With
Panel Board or
Subfeed Breaker
With Transformer
No Distribution
With Transformer
and Panel Board or
Subfeed Breaker
600
10-40
525 (238)
625 (283)
914 (415)
1014 (460)
600
60
550 (249)
650 (295)
1123 (509)
1223 (555)
600
80
550 (249)
650 (295)
1249 (567)
1349 (612)
600
100
550 (249)
650 (295)
1365 (619)
1465 (665)
Add 27 lb. (12 kg) for monitoring.