3.2
Torque Requirements
All electrical connections must be tight.
Tables 15
and
16
provide the torque values for the connections to the Liebert EXM BDC. Use these values unless
the equipment is labeled otherwise.
Table 14
Recommended lug sizes (compression type) M12, 1/2" bolt
Cable Size
T&B Copper
Two Hole
T&B Aluminum
Two Hole
#6AWG
256-030695-868
—
#4AWG
256-030695-733
—
#2-3AWG
54811BE
—
#1AWG
54857BE
—
#1/0AWG
256-30695-593
—
#2/0AWG
54862BE
60238
#3/0AWG
54864BE
60244
#4/0AWG
54866BE
60250
250kcmil
54868BE
60256
300kcmil
54870BE
60262
350kcmil
54872BE
60267
400kcmil
54874BE
60269
500kcmil
54876BE
60273
600kcmil
54878BE
60275
700kcmil
54879BE
60277
750kcmil
54880BE
60278
Table 15
Busbar torque for power wiring
Bolt Shaft Size
Torque
Lb-in (Nm)
3/8" (M10)
192 (22)
1/2" (M12)
428 (48)
Table 16
Terminal block torque with compression lugs for control wiring
AWG Wire Size
or Range
Torque
Lb-in (Nm)
#22 - #14
3.5 to 5.3 (0.4 to 0.6)
NOTE
Refer to the manufacturer’s data for proper torque for circuit breaker power connections.