Vertiv
|
Liebert
®
EXM
™
BDC User Manual | Rev. 3 | 01/18 |
17
Figure 10
Cabinet arrangement
1.6
Liebert EXM UPS Bypass Assembly
Figure 11
Liebert EXM UPS bypass assembly connections
The Static Bypass Assembly has three Liebert IntelliSlot
™
interface card bays and connections for ancillary
cabinets (Liebert EXM BDC and battery) and for options.
1.6.1
Liebert EXM BDC Interface
The Liebert EXM BDC interface is on the Auxiliary Terminal Block at J26. Refer to
Figure 12
for circuit details.
Table 2
Liebert EXM BDC interface
Position
Name
Description
J26.1
Q1 STA
Main input switch status signal
J26.5
Q2 STA
Bypass input switch status signal
J26.9
Q3 STA
External maintenance switch status signal
J26, 3, 7, 9
GND
Ground for dry contacts
These contacts cannot be active unless they are set via software.