Installation/Owner's Manual

6-22

Time-limited running

The time-limited running automatically stops the operation of the unit after the specified time. The time-
limited running can reduce the waste of energy by limiting the individually used time of the unit within a
specific time when the administrator is absent.

In order to set the time-limited running, specify the time and the weekday to operate. The operation
time can be set to 0.5 ~ 4 hours (2 as default) and can be set to any weekday. Set whether to operate
the time-limited running based on 0 oʼclock.

The following figure shows the example for the operation of the time-limited running. The time-limited
running is set to stop the unit by 4 hours on Tuesday and Wednesday from Monday to Thursday.

• The Unit A operates from 22:00 on Monday before applying the time-limited running. The time limited

operation is applied to run the Unit A on Tuesday and to stop at 4:00 after 4 hours.

• The Unit B operates from 22:00 on Tuesday while the time-limited running is applied. Because the

time-limited running is also set to Wednesday, the Unit B stops at 2:00 on Wednesday.

• The Unit C operates from 22:00 on Wednesday while the time-limited running is applied. But, the Unit

C continues to operate with no time limit because the time-limited running is not applied on Thursday.

Reference: Function operation priority

When several functions of AC SMART II are operating simultaneously, it will operate in the
following priority.
1) Emergency stop 

2) Temperature limit operation 

3) Schedule 

4) Auto change over

operation 

5) Basic control (Control/Monitoring) 

6) Time limit operation

6. Auto control menu

Summary of Contents for V-Net AC Smart II

Page 1: ...OWNER S MANUAL Please read this manual carefully before operating your set and retain it for future reference P NO MFL62077702 www lg com TYPE AC Smart II Advanced Control Smart ...

Page 2: ...switch 2 4 Setting individual lock function 2 7 Connecting PI485 to RS485 line 2 9 Installing AC Smart II and connecting line 2 13 Logging in of AC Smart II 2 17 Registering the unit 2 19 Automatically registering the unit 2 19 Directly registering the unit 2 23 Setting the emergency stop interlocking 2 27 3 AC Smart II Menu 3 1 AC Smart II screen configuration 3 1 AC Smart II information entry me...

Page 3: ...hedule group 5 9 Creating schedule pattern 5 11 Adding weekly schedule pattern 5 12 Adding daily schedule pattern 5 18 Setting the schedule pattern in detail 5 23 Applying the schedule 5 28 View the schedule 5 36 Running Stopping the schedule 5 39 6 Auto Control Menu 6 1 Managing operation group 6 2 Creating operating group 6 2 Deleting the operating group 6 7 Renaming the operating group 6 9 Temp...

Page 4: ...ng time search condition 8 6 Saving operating time report file 8 8 9 System Menu 9 1 Registering unit 9 2 Registering new unit automatically 9 3 Directly registering new unit 9 6 Zone Management 9 10 Creating new zone 9 10 Deleting zone 9 14 Renaming zone 9 16 Group Management 9 19 Resetting group 9 19 Creating new group 9 23 Deleting group 9 26 Renaming group 9 28 Unit Management 9 31 Resetting t...

Page 5: ... may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense 10 Environment Setting 10 1 Checking the S W version information 10 2 Password setting 10 3 Language setting 10 5 Screen saver setting 10 7 Alarm setting 10 10 Changin...

Page 6: ...andard parts can cause electric shock explosion injury breakdown Operation To prevent injury to the user or other people and property damage the following instructions must be followed Incorrect operation due to ignoring instruction will cause harm or damage The seriousness is classified by the following indications Meanings of symbols used in this manual are as shown below WARNING CAUTION This sy...

Page 7: ...stablishment specialty store It can cause an accident electric shock explosion injury shock Do not use the power cord near Flammable gas or combustibles such as gasoline benzene thinner etc It may cause an explosion or fire Do not disjoint randomly or repair and remodel the product It may cause fire and electric shock Cire Diluant During usage Do not change or extend the conductor at random It can...

Page 8: ... shock Hold the plug by the head of the power plug when taking it out It may cause electric shock and damage Do not place heavy goods on product It can cause product breakdown That increase in case of product was been flood certainly in the service center or establishment specialty store commit I am responsible for fire and electric shock Protect the product from handling by a children It can caus...

Page 9: ...own and damage to the product Do not place any live part on the surface having water It can cause product breakdown Cire Diluant Use recommended Adapter Otherwise it can result in product breakdown Avoid contact to the metallic goods such as necklace coin key a watch which may touch the battery even for a short time It may cause product breakdown and injury Hold the plug by the head of the power p...

Page 10: ...st with AC Smart Central control from the administrative office of the building where the air conditioners are installed Group management AC Smart can manage the installed air conditioners by zone and group When you use the zone or group setting you can classify the air conditioner by type location etc Through these functions you can conveniently control the air conditioner and by assigning each n...

Page 11: ...tion for protecting the system from power failure and other accidents by which the stability of the system can be improved and the system can be easily recovered from the accident Upgrading the software to the recent version The AC Smart offers the function to upgrade the software to the recent version by which the AC Smart can be stably operated and a new function can be added Web server The AC S...

Page 12: ...te Using the external button to compensate the screen The screen compensation function can be executed by pressing the keyboard button at the top of the AC Smart and then the backlight button When it is hard to execute the screen compensation function by the touch screen you can use this method Caution USB Port and Option card slot USB port is only for SVC and development therefore USB port is not...

Page 13: ... located on the left side is the USB port to connect the USB memory to update the software or back up the data This port supports USB version 1 0 The USB port B Type located on the right side is the USB port to connect the PC This port supports USB version 2 0 Optional card slot For adding optional function In the optional card slot you can insert the optional card provided for the optional functi...

Page 14: ... AC Smart 1 5 AC Smart II components The components of AC Smart are as follows inside the box Open the box of AC Smart and check whether all components are included L G AC Smart II Power adapter Manual CD Quick Guide Power cord ...

Page 15: ...Touch Screen UART USB OS MP2530F or MP2531F Dual CPU ARM926E 360MHz ARM946E 300MHz 128MB DDR 64MB A Bank DDR 64MB B Bank 512MB NAND Flash SD Card support SDHC 8GB For optional card 7 0 WVGA 800 480 TFT LCD AST 01508MR R Display S W x1 Software Key S W x1 S W Input For Fire sensor DC 12V 1A 4 Wire Touch Controller built In RS 485 1Port USB1 1 Host 2Port For service USB2 0 Device 1Port For developme...

Page 16: ...ne PI485 for each outdoor unit and set the DIP switch STEP 4 Connect PI485 and AC Smart Connect the PI485 and AC Smart through the RS485 line STEP 5 Login and register unit Login to AC Smart and register the unit which the address has been assigned to Caution AC Smart installation Installation of AC Smart requires special technology Therefore The installation detail mentioned in this chapter must ...

Page 17: ... II to control Information Maximum permitted communication length and specification The maximum permitted communication length that LG Electronics guarantee is 1 000m In other words the unit installed the farthest from AC SMART II must be installed within 1 000m distance It is recommended to use the communication cable of 0 75mm2 Shield or above AC SMART II PI485 PI485 PI485 Ventilator On Off unit...

Page 18: ...s for indoor unit ventilator On Off unit and AWHP unit You cannot set the same address for the indoor unit ventilator Eco V DX On Off unit and AWHP Make sure not to have duplicate addresses 00 Group number Unit number 00 Group number Unit number Reference Setting address for device When setting the address of a unit Indoor unit ventilator On Off unit AWHP unit it is recommended to set the first di...

Page 19: ...s follows Reference PI485 installation The installation of PI485 may differ by the product of the outdoor unit Therefore refer to PI485 manual or installation technology information to proceed Setting PI485 DIP switch DIP switch Setting Product type Multi V product Excluding CRUN LRA product MPS static speed product with common PCB applied MPS inverter product MPS static speed product without comm...

Page 20: ...to PI485 M manual for detail installation method of PI485 Set the DIP switch as follows depending on the type of outdoor unit PI485 is attached to After setting the DIP switch you must always reset the PI485 Press the reset switch to reset PI485 ON L1 2 3 4 KSDO4H DIP switch Setting Product type Multi V product Excluding CRUN LRA product MPS static speed product with common PCB applied MPS inverte...

Page 21: ...follows LED01G will flash for as many as the connected number of indoor units LED02G and LED03G will flash in switching back and forth When connecting LRA CRUN product LED02G can blink more than LED03G When the LED is abnormal unlike the above description recheck the address setting of the indoor unit and DIP switch setting ON L1 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H LED03G LED02G LED01G ON L1 2 3 4 KSD...

Page 22: ...stallation For PI485 with 4 DIP switches connect the 2PIN connector to the CN_DRY terminal For PI485 with 8 DIP switches set the 5 DIP switch to ON DIP switch Setting Product type Multi V product Excluding CRUN LRA product MPS static speed product with common PCB applied MPS inverter product MPS static speed product without common PCB applied Multi V CRUN LRA product ON 1 4 5 OFF 2 3 6 7 8 ON 2 4 ...

Page 23: ...ature of 20 C sent through the central control command This time this is an example when the 2PIN connector is not connected to CN_DRY terminal or when the DIP switch 5 is not set to ON When you command the Cool operation 20 C setting high fan level temperature lock function through central control the applicable command is transmitted to the remote controller HL Hard Lock message displaying the c...

Page 24: ...5 lines must be connected to BUS_A and BUS_B of PI485 Refer to the following figure to connect the RS485 line ON L1 2 3 4 KSDO4H 10V CND BUS_A BUS_B Reference Connecting RS485 cable to PI485 The shape of PI485 can differ by the number For details refer to the installation manual provided with the PI485 product ...

Page 25: ...rt II Installation The following figure is an example of several units of PI485 connected to AC Smart 100 GND BUS_A BUS_B AC Smart II BUS_A BUS_B ON L1 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H 100 GND BUS_A BUS_B 100 GND BUS_A BUS_B ...

Page 26: ... unit must be connected in BUS format If not AC SMART II can malfunction The left picture shows the correct and incorrect example of RS485 communication connection to of AC SMART II The upper picture shows the correct example of RS485 connection to outdoor unit with AC SMART II in BUS format The bottom picture shows the incorrect example of RS485 connection to outdoor unit with AC SMART II in STAR...

Page 27: ...the order shown as follows 1 Connect the BUS A and BUS B port of PI485 to the A and B terminal of the simple central controller using the RS485 communication cable 2 Set the rotary switch of the simple central controller to align with the group number of the indoor unit to control For example when you want to control the indoor units with the address of 00 0F set the rotary switch to 0 3 Set the D...

Page 28: ... to install AC Smart In order for AC Smart to be installed on the wall there must be a RS485 line near by 2 Fixate the rear panel of AC Smart on the wall top of the RS485 line Fixate the panel using a driver You can fixate the panel as shown below depending on the installation location Reference AC Smart II installation AC Smart is designed to be basically installed on the wall Here we explain the...

Page 29: ...the ʻ ʻ driver to connect the two RS485 communication cable as follows 4 Connect the RS485 socket to the RS485 port located on the rear side of the AC SMART II main unit RS485 RX BUS B RS485 TX BUS A BUS B BUS A Caution RS485 communication cable connection When connecting the RS485 communication cable be careful not to mix the polarities of the two lines ...

Page 30: ...II Emaion transmission SVCNet connection the UTP cable must be connected Connect the UTP cable that can be connected to the Internet on the rear side of the main unit of AC SMART II to the LAN port 6 Connect the power adapter to the power terminal located at the rear side of the main unit of AC Smart ...

Page 31: ... the main unit of AC Smart on the rear penal installed on the wall After hanging the top holes of the top of the main unit to the top of the rear panel push forward and slide in the bottom of the main unit 8 Connect the power cord of the power adapter to the power outlet ...

Page 32: ...e password screen is displayed to enter the password Logging in of AC SMART II When the power is applied to the AC Smart the AC Smart automatically operates When the AC Smart II operates the LG logo screen is initially displayed and then chanted to the login screen The AC Smart II can be logged in with three method such as professional administrator and general user as follows Log in for installat...

Page 33: ...1ʼ which cannot be changed When you correctly enter the password and press OK button you are logged in and can set all functions of the AC Smart 3 When you log in the following menu screen will be displayed and you can use all functions of AC SMART II After enter digital21 press OK button ...

Page 34: ... the unit connected to AC Smart To automatically register the unit proceed in the following order 1 After logging in with installation professional to AC SMART II select the ʻDevice management ʻ menu from the menu Registering the unit Note Login right for registering a unit In order to register a unit to the AC Smart you should log in as installation professional This menu is not displayed on the ...

Page 35: ...ayed Press the Unit Reg button located on the bottom right side 3 ʻDevice registrationʼ screen will be displayed When you press the Auto button the ʻConfirmationʼ screen to check the execution of auto setting will be displayed Press the Yes button Click on Unit Reg button After clicking Auto when the screen is displayed click on Yes button ...

Page 36: ... and displayed at the table located at the bottom of the screen 5 Temporarily store the searched unit When you press OK button the ʻConfirmʼ screen for confirming saving is displayed When you press ʻYesʼ button saving is done and it returns to the previous screen After the device search the result will be displayed To apply to system click on OK button When the Information screen is displayed clic...

Page 37: ...button 7 Current setting will be applied to the system and the message saying that the setting has been saved will be displayed Click on the OK button to complete the registration To apply to system click on Save button click on Yes button When it is saved click on OK button Reference Change information of registered unit When you want to change the information of the registered unit such as name ...

Page 38: ...unit proceed in the order as follows 1 After logging in as installation professional to AC SMART II select the ʻDevice managementʼ menu from the menu 2 When you select the ʻDevice managementʼ menu the following screen will be displayed Press the Device registration button at the bottom right side Press the Device management button Click on Unit ...

Page 39: ...pe of unit Air conditioner Ventilator Eco V DX On Off device AWHP Enter the name of unit The name can be entered to maximum of 20 letters Enter the physical address of the unit The physical address value is a number in the range of 00 FF and cannot be duplicated Enter the model of the unit Maximum of 20 characters can be entered for the model Enter the maximum power consumption of the unit The pow...

Page 40: ...ating the same procedure To save the registered units click on the OK button 5 ʻConfirmʼ screen to temporarily save the current setting is displayed When Yes button is pressed it exits from ʻUnit Registrationʼ screen and returns to the previous screen Click on OK button to apply to system When ʻConfirmʼ screen is displayed click Yes button ...

Page 41: ...ressed ʻConfirmʼ screen to check whether to apply the current setting to the system is displayed Press Yes button 7 Current setting will be applied to the system and the message saying that the setting has been saved will be displayed Click on the OK button to complete the registration Click on Save button to apply to system When it is saved click on OK button ...

Page 42: ...You can use the emergency stop function by connecting the external fire detection sensor to the connection terminal of external non contact point method on the rear side of AC Smart II as shown below Setting the emergency stop interlocking Terminal connected to external fire detection sensor When the fire sensor generates the ON signal the AC Smart stops the operation of all indoor units ...

Page 43: ...creen AC SMART II Menu This displays the function provided by AC SMART II When you press the function to execute it will change to the applicable function screen When you log in to AC SMART II the menu selection screen is displayed AC SMART II screen configuration Reference General user authority login When you log in as general user this screen will not be displayed and it will directly switch to...

Page 44: ...cution screen You can operate the function for each menu from the Function execution screen Message window Message window notifies the user of various types of information depending on the functional operation and status of AC Smart When the user selects a specific function the execution screen of the applicable function is displayed The example of Control Monitoring menu is used hereafter Log out...

Page 45: ...n the screen But if the software keyboard does not appear on the screen press the keyboard button located on the top part of AC SMART II to activate the software keyboard on the screen Also if you want to close the keyboard on the screen while using AC SMART II press the keyboard button to close the keyboard on the screen Software keyboard Keyboard Keyboard button Caution Use of stylus pen When en...

Page 46: ...ional When you log on with the installation professional you can set all the functions related to installation and related functions of SMART II But it is recommended to use the installation professional only when changing the key setting related to the installation Log in for administrator When you log on as the installation professional you can use all the functions excluding the ʻAdvanced envir...

Page 47: ...ware keyboard and password entry screen are displayed 2 The password is ʻdigital21ʼ which cannot be changed When you correctly enter the password and press OK button you are logged in and can set all functions of the AC Smart 3 After the login the following menu screen will be displayed and you can use all the functions of AC SMART II Software keyboard When you press this for 5 seconds the passwor...

Page 48: ... AC SMART II 3 After the login the following menu screen will be displayed and you can use all functions excluding the ʻAdvanced environment settingʼ menu Software keyboard Press Administrator button to display the password input screen Logging in as administrator Reference Administrator login password When logging in as administrator for the first time on AC SMART II the password is not set You c...

Page 49: ...as follows 1 When you press ʻGeneral userʼ button it is directly logged into the AC Smart with no password input procedure 2 When logged into the AC Smart only the functions of the ʻControl Monitoringʼ menu can be used and other menus cannot be selected If pressing general user button Log In without input password ...

Page 50: ...of groups to be configured according to installed location or executing function Group Logical set of units to be configured according to installed location or executing function Unit Smallest controlled unit installed at the indoor such as air conditioner or ventilator Control Monitoring menu screen is configured as follows Can change the information display format between icon and table format D...

Page 51: ...p or Unit Indoor unit ventilator Eco V DX On Off AWHP through the following icons When you set the information display format of the screen to ʻIconʼ the screen will be displayed as follows Zone group and unit status display ICON Zone Group Indoor unit Ventilator Eco V DX On Off unit AWHP unit Normal operation Alarm Not in operation When you set the information display format of the screen ʻSimple...

Page 52: ...o mode Auto mode Auto mode Icon Description Icon Description Icon Description Unit type When you set the information display format to ʻSimpleʼ the screen will be displayed as follows Indoor unit Ventilator Eco V DX AWHP Cool mode Dehumidifier mode Heating mode Cool mode Heating mode Fan mode General mode Heating mode Auto mode Auto mode Auto mode Icon Description Icon Description Icon Description...

Page 53: ...basically displayed in Icon format But you can change the display format to Table format When you change the drop down box at the top right corner of Control Monitoring menu to Details you can change the information of Icon format into Table format Alarm Description Alarm Description Alarm Description 242 error Communication error 251 error 128 room expansion kit error Other error But if you set t...

Page 54: ...s Icon and it is the same icon as the one shown when the information display method is set to ʻSimpleʼ Schedule or auto control function is displayed as Icon When schedule is set When temperature limit operation is set When auto switch operation is set When time limit operation is set When there is an error on the unit the error code is displayed Wind direction setting on the unit is displayed Fan...

Page 55: ...en is not displayed Zone Group and Unit monitoring There is a ʻMonitoringʼ tab at the bottom of the Control Monitoring menu The Monitoring tab shows the detail information of the selected Zone Group and Unit The monitoring information of Zone and Group and the monitoring information of the unit can be shown differently by the characteristics Zone Group monitoring information The monitoring informa...

Page 56: ...t temperature Total number of units included in the Zone or Group designated by the user is displayed Total number of units in operation within the Zone or Group designated by the user is displayed Number of units with communication error Code 242 or expansion kit error Code 251 among the units in the Zone or Group designated by the user is displayed Number of units operating in cool mode is displ...

Page 57: ...displayed Set temperature of indoor unit is displayed The operating mode of the unit is displayed Cool When the unit is in cool operation Heat When the unit is in heat operation Auto When the unit is in auto operation Indoor temperature Set temperature Mode Reference What is auto operation Auto operation refers to the method of operating the unit automatically to maintain optimal environment by me...

Page 58: ... enables the Fan level lock function so that the user cannot individually control the fan level of the indoor unit Fan level unlock This disables the Fan level lock function Set temperature lock This enables the Set temperature lock function so that the user cannot individually control the indoor temperature setting Set temperature unlock This disables the set temperature lock function When there ...

Page 59: ...ction enabled Disabled Condition with lock function disabled When there is no alarm in the current ventilator this is displayed as ʻ0ʼ In case of an alarm the applicable alarm code is displayed Current fan level is displayed Installation Owner s Manual 4 10 4 AC Smart II Menu Ventilator monitoring information Ventilator monitoring information shows the current operating mode and setting In case of...

Page 60: ...For the AWHP unit the control temperature can be selected between air temperature and water temperature and it is displayed as follows On Off unit monitoring tab AWHP unit monitoring tab When control temperature is set to air temperature AWHP unit monitoring tab When control temperature is set to water temperature Information displayed on On Off unit monitoring tab is as follows Item Description T...

Page 61: ...ode of the currently set AWHP unit is displayed Cool When operating in cool mode Heat When operating in heat mode Auto When operating in auto mode Lock function setting to disable all functions of the AWHP unit through the remote controller by the user is displayed Enabled Condition with lock function enabled Disabled Condition with lock function disabled When there is no alarm in the AWHP unit th...

Page 62: ...oor unit function Reference Zone Group and Unit control method For details on the control method refer to Control Monitoring operation section in page 4 20 Operate Stop Zone or Group Set the operating mode fan level and lock function Set the desired indoor temperature Average indoor temperature is displayed Detail control screen to control the Zone or Group in detail is displayed Apply the current...

Page 63: ...vel lock is enabled In this case when you resolve this issue by operating the temperature lock and mode lock simultaneously When the 2PIN of PI485 is connected it is recommended that you use both the temperature lock and mode lock Ventilator control When you select the ventilator from the Control Monitoring screen the control tab is displayed as follows and you can directly control the ventilator ...

Page 64: ...you can set both the air and water temperature from the unit control item of AC SMART II the actual operation will be done based on the temperature set by the remote controller Air Water temperature can be set from the control tab but in actual operation the unit operates based only on the temperature set in the remote controller of the two Operate Stop AWHP unit Set the operating mode and lock fu...

Page 65: ...of the unit proceed according to the following description 1 Select Control Monitoring menu from the menu of AC Smart When you select the Control Monitoring menu the following Control Monitoring screen is displayed Designate the target to execute the various function of the unit from the screen with zone group or unit displayed You can press the Up All Zones All Groups or All Units button to desig...

Page 66: ...ed temperature from SET TEMP in the range of 18 C 30 C When the desired temperature is higher than the indoor temperature it operates in fan mode Auto It evaluates the indoor and outdoor condition and maintains the optimal condition automatically You can set the fan level of the unit Low This sets the fan level to low Med This sets the fan level to med High This sets the fan level to high You can ...

Page 67: ...uto This measures the indoor temperature and outdoor temperature and automatically controls inlet and outlet With this the balance of the indoor air is maintained to maintain the optimal condition This sets the fan speed of the ventilator You can adjust the level by considering the indoor level of contamination Low This sets the fan level to low High This sets the fan level to high Super This sets...

Page 68: ...nctions of AWHP unit cannot be changed individually All unlock Disable the all lock function You can operate stop the AWHP unit Operate Set to turn on the power of AWHP unit Stop Set to turn off the power of AWHP unit You can operate stop the heat tank On Set turn on the heat tank Off Set turn off the heat tank Item Description Air temperature Water temperature Heat tank temperature Mode Lock Oper...

Page 69: ... of Zone Group and Unit Detail control screens for Zone Group and Unit are different But the controlling method is the same For example all types of units can be controlled for the Zone or Group But on the other hand the detail control screen by unit can only control the applicable unit in detail 1 When you select the ʻControl Monitoringʼ menu the following screen will be displayed Designate the t...

Page 70: ... The unit evaluates the indoor condition and maintains optimal condition automatically Dehumidify This operates the indoor unit to run dehumidifier operation When you set this during the rainy season or when it is humid the dehumidifier will remove the humidity effectively When you set to this mode When you set up for this mode you cannot set the desired temperature Fan This operates the indoor un...

Page 71: ...ntrol the indoor temperature setting Set temperature unlock This disables the set temperature lock function You can limit the indoor temperature to be within a certain temperature range Here the user cannot individually set the indoor temperature out of the set temperature range Fan level Wind direction LOCK Maximum Minimum temperature setting Ventilator Eco V DX Item Description You can set the o...

Page 72: ... power save Ventilator operates in the most efficient condition to save the power consumption Disable power save This disables the power save function Enable quick operation This enables the unit to operate in maximum performance to prevent the expansion of contaminated indoor air or humidity to other space It is recommended to use this when the indoor contamination is severe Disable quick operati...

Page 73: ...wer of AWHP unit Stop Set to turn off the power of AWHP unit You can set the operating mode of the AWHP unit Cool Operate in cool mode Heat Operate in heat mode Auto Judges the indoor condition and automatically maintains optimal condition Set so that AWHP unit cannot be operated individually All lock Set the all lock function so that all functions of AWHP unit cannot be changed individually All u...

Page 74: ...chedule for group pattern and period Schedule pattern Unit designating the certain operation of air conditioner in week or day unit Schedule group Collection of units Indoor unit and ventilator applied with same schedule pattern Generally you must follow the following procedure to set the schedule Reference Schedule group Schedule group is different from the logical or physical group referred to i...

Page 75: ...sing the schedule Manage schedule group Schedule group is a gathering of devices to perform same movement If pressing Group edit button Group edit screen which can create revise and remove schedule group is presented Name of currently selected group and list of units included in the applicable group are displayed List of currently registered schedule groups is displayed You can create rename or de...

Page 76: ...ule menu the following schedule screen is displayed To create a new schedule group click on the Edit group button 2 Edit group screen is displayed To create a new schedule group click on the Add button Add group screen to enter the name of the schedule group to create is displayed Click on Edit group button When you click on Add button Add group screen is displayed 5 Schedule menu ...

Page 77: ...roup has been created in Group Now select the unit to be added to the schedule group from the unit list on the right and press the button to add to the schedule group After entering the group name click on OK button Check created schedule group After selecting units from the list click on the button to add the units to the schedule group 5 Schedule menu ...

Page 78: ...AC Smart 5 5 5 Click on the Save button to save the current setting Information screen to confirm the saving process is displayed Press the Save button to save the setting 5 Schedule menu ...

Page 79: ...ton located at the bottom left corner of the ʻEdit groupʼ screen you can create the same group as the basic control group set for control and monitoring from the ʻSettingʼ menu as a schedule group When you click on Basic group setting button same group as the one composed from Setting menu is automatically created as a schedule group 5 Schedule menu ...

Page 80: ...e screen is displayed To rename the schedule group click on the Edit group button 2 Edit group screen is displayed Select the schedule group to rename and click on the Rename button Group name screen to enter the name of the schedule group to change is displayed Click on Edit group button After selecting the schedule group when you click on Rename button Rename group screen is displayed 5 Schedule...

Page 81: ...o change click on the OK button 4 Check whether the name of the applicable schedule group has changed in Group and click on the Save button to save the current setting After entering the schedule group name click on OK button Press the Save button to save the setting 5 Schedule menu ...

Page 82: ... Schedule menu the following schedule screen is displayed To delete the schedule group click on the Edit group button 2 Edit group screen is displayed Select the schedule group to delete and click on the Delete button The applicable schedule group will be deleted Press the Group edit button After selecting schedule group to delete click on Delete button 5 Schedule menu ...

Page 83: ...s Manual 5 10 3 Check whether the applicable schedule group has been deleted from Group click on the Save button to save the current setting Check whether schedule group is deleted clicking on Save button 5 Schedule menu ...

Page 84: ...g the operation of the unit in weekly or daily pattern The pattern created through the schedule pattern wizard can be applied to the Group as a schedule through schedule wizard to be described in the next section Schedule pattern wizard can be configured through total of 4 steps as shown below 1 Select schedule pattern type 2 Add Edit schedule pattern 3 Enter schedule pattern name 4 Edit schedule ...

Page 85: ...II the following screen will be displayed To create a schedule pattern press the Schedule pattern wizard button 2 Schedule pattern edit wizard screen is displayed To create a new weekly schedule pattern select Add Edit weekly schedule pattern and press the Next button Press Schedule pattern wizard button After selecting Add Edit weekly schedule pattern press the Next button 5 Schedule menu ...

Page 86: ...stage 3 of weekly schedule edit wizard the process is the same as adding the weekly pattern Reference Edit weekly schedule pattern In stage 2 of schedule pattern edit wizard you can rename edit delete the existing schedule pattern To rename the schedule pattern press the Rename schedule pattern button and enter the new name To delete the schedule pattern select the schedule pattern to delete and p...

Page 87: ...and press the Next button 5 Select the time to operate the unit from Select time or Schedule time item Set the unit operation from Control setting item Refer to the following table to set the operation Enter the weekly schedule pattern name and press the Next button 5 Schedule menu ...

Page 88: ...he ventilator You can adjust the fan level considering the level of indoor contamination Low This sets the fan speed to low Med This sets the fan speed to med High This sets the fan speed to high You can lock all the functions of the air conditioner so that the user cannot control the air conditioner individually All lock Use the lock function All unlock Do not use the lock function Set temperatur...

Page 89: ...ern and apply daily You can apply the daily schedule pattern when creating or editing the weekly schedule pattern When you press the Apply daily schedule pattern at stage 4 of the schedule edit pattern wizard you can open the daily schedule pattern and apply to specific day Also you can set a specific schedule pattern for several days Select the schedule pattern at stage 4 of schedule edit pattern...

Page 90: ...AC Smart 5 17 7 Message saying that the schedule pattern edit is completed is displayed Press the OK button to complete the editing Press the OK button to end the wizard 5 Schedule menu ...

Page 91: ... the following screen will be displayed To create a schedule pattern press the Schedule pattern wizard button Press the Schedule pattern wizard button 2 Schedule pattern edit wizard screen is displayed To create a new daily schedule pattern select Add Edit weekly schedule pattern and press the Next button After selecting Add Edit daily schedule pattern press the Next button 5 Schedule menu ...

Page 92: ...tern name as in stage 3 of daily schedule edit wizard the process is the same as adding the daily pattern Information Rename Delete schedule pattern In stage 2 of schedule pattern edit wizard you can rename edit delete the existing schedule pattern To rename the schedule pattern press the Rename schedule pattern button and enter the new name To delete the schedule pattern select the schedule patte...

Page 93: ... press the Next button Enter the daily schedule pattern name and press the Next button 5 Select the time to operate the unit from Select time or Schedule time item Set the unit operation from Control setting item Refer to the following table to set the operation 5 Schedule menu ...

Page 94: ...ndition and automatically maintains the optimal condition This sets the fan speed of the ventilator You can adjust the fan level considering the level of indoor contamination Low This sets the fan speed to low Med This sets the fan speed to med High This sets the fan speed to high You can lock all the functions of the air conditioner so that the user cannot control the air conditioner individually...

Page 95: ...ove process to additionally set the schedule When the schedules are all set press the End button Press the Apply schedule button to add the schedule After setting all the schedules press the End button 7 Message saying that the schedule pattern edit is completed is displayed Press the OK button to complete the editing Press the OK button to end the wizard 5 Schedule menu ...

Page 96: ... weekly or daily schedule pattern wizard press the Advanced button Stage 4 of schedule pattern wizard Press the Advanced button After setting the schedule press the Apply button 2 Schedule detail setting screen to set the detail operation of the unit is displayed After setting the schedule press the Apply button Refer to the following table for operations that can be selected from Advanced 5 Sched...

Page 97: ...You can adjust the setting considering the level of indoor contamination Low This sets the fan speed to low Med This sets the fan speed to med High This sets the fan speed to high Auto This sets to automatically measure the indoor level of contamination and maintain the optimal condition This sets the automatic rotation of the fan You can set the lock function of air condition so that the user can...

Page 98: ...ng the indoor level of contamination Low This sets the fan level to low High This sets the fan level to high Super This sets the fan level to maximum speed Auto This is set to maintain the optimal condition by measuring the indoor level of contamination automatically You can set the lock function so that the user cannot operate the ventilator individually All lock This is set so that the ventilato...

Page 99: ...operation The user can set the desired indoor temperature You can set the operation and stopping of the Eco V DX Operation You can operate the Eco V DX Stop You can stop the operation of the Eco V DX You can set the operating mode of the indoor unit function of Eco V DX Cool This operates the indoor unit to run cool operation Execute when the indoor temperature is high Heat This operates the indoo...

Page 100: ... Cool Operate in cool mode Heat Operate in heat mode Auto Judges the indoor condition and automatically maintains optimal condition Set so that AWHP unit cannot be operated individually All lock Set the all lock function so that all functions of AWHP unit cannot be changed individually All unlock Disable the all lock function Air temperature Water temperature Hot water temperature Operation Mode L...

Page 101: ...nd schedule pattern AC SMART II provides the schedule wizard to make the schedule application easy Schedule wizard is composed of 6 stages as shown below But the schedule copy between Groups is done in a separate 2 stage process 1 Add Edit schedule 2 Add Edit schedule 3 Select schedule start and end date 4 Apply set weekly schedule pattern 5 Check Edit schedule 6 Set exception day to exclude from ...

Page 102: ...utton Press the Schedule wizard button 2 Schedule wizard screen is displayed Select Add Edit schedule and select the Group to apply the schedule to Press the Next button Press Add Edit schedule and then select the Group and then press the Next button Reference Creating schedule group To create and apply a new schedule group refer to the Managing schedule group section in page 82 to create a new sc...

Page 103: ...e wizard you can edit the applied period of the existing schedule and delete the existing schedules To edit the schedule period press the Edit schedule period button to set the new period To delete the schedule select the schedule period to delete and press the Delete schedule button After editing the schedule period and deleting the schedule the wizard does not proceed to the next stage 5 Schedul...

Page 104: ...dule pattern To apply the weekly schedule pattern select the Apply item and select the weekly schedule pattern to apply If you do not want to apply the weekly schedule pattern select Do not apply item and you can directly enter in stage 5 1 Use the calendar to enter the start and end date 2 Press the Next button 1 Set whether to apply the weekly schedule pattern 2 Press the Next button 5 Schedule ...

Page 105: ...schedule period not to apply the schedule To register as exception day select the day from the calendar and press the Register exception day button 1 Check and edit schedule information Press the Next button Reference Schedule edit When editing the schedule the setting for the input item is the same as that of schedule pattern For details on the setting items refer to the Creating schedule pattern...

Page 106: ...he schedule setting 8 When you see the screen to enter the name of exception day enter the name of the exception day and press the OK button And then Next button 9 Check the exception day setting and press the End button 1 After entering the name of exception day press the OK button 2 Press the Next button 1 Check the setting 2 Press the End button 5 Schedule menu ...

Page 107: ...ting Information Renaming Deleting exception day In the exception day edit screen you can rename or delete the exception day To rename the exception day select the name of the exception day and press the Rename button to enter the new name To delete the exception day select the exception day and press the Delete button Press the OK button 5 Schedule menu ...

Page 108: ... start screen and press the Next button 2 Set the original schedule group and applied period to copy the schedule from and select the target group to copy the schedule to and then press the Next button When the schedule wizard ending screen is displayed press the OK button Select the Copy schedule between groups item and press the Next button 1 Select group and period 2 Press the Next button 5 Sch...

Page 109: ...schedule group You can select and view the schedule set in 1 week unit You can view the weekly schedule detail by time zone You can view the number and operation of the schedule You can view the scheduled operation by unit in detail Reference Schedule group and schedule setting In the schedule view you can only check the schedule group and schedule details that have been set Therefore if the sched...

Page 110: ...hedule group and period to check you can check the schedule When you select the schedule group and period you can check the schedule Information View schedule detail When you press the View detail button the View schedule detail screen will be displayed In this screen you can check the schedule operation by unit in detail 5 Schedule menu ...

Page 111: ...dit the existing schedule After editing the schedule press the End button to end editing the schedule 1 Edit existing schedule 2 Press the End button to end the edit Reference Edit schedule When editing the schedule the setting for the input item is the same as that of schedule pattern setting For description of detail setting item refer to the Creating schedule pattern section 5 Schedule menu ...

Page 112: ...m the schedule menu Check whether the schedule group and schedule are operating You can select to stop the schedule of individual or all group You can select the group to stop when stopping the schedule by group Apply the schedule run stop setting You can cancel the schedule run stop setting Check whether the schedule is run 5 Schedule menu Running Stopping the schedule ...

Page 113: ...xt to the schedule group to run If you want to stop all schedules select the ʻStop all Group scheduleʼ button After selecting press the Apply button 3 Message on schedule run stop setting is displayed Press the OK button to end the setting 1 Setting of schedule run Press the OK button 2 Press the Apply button 5 Schedule menu ...

Page 114: ...um and minimum temperature and by monitoring the indoor temperature Auto change over operation Function to maintain optimal indoor temperature through the automatic switching of air conditioner operating mode Cool heat Time limited operation Automatically stop running after the set time by controlling the running time of Indoor unit ventilator Eco V DX On Off AWHP In the auto control menu you can ...

Page 115: ...ting criteria Temperature limit operation and auto change over operation are functions targeted only to the indoor units Therefore the Group can only be created or edited for the indoor units and cannot Indoor unit ventilator Eco V DX On Off AWHP Reference Auto changer over operation group setting If the outdoor unit is not a changer over type and not a synchronized type always set one outdoor uni...

Page 116: ...operation and auto change over group the Edit group button is located at the bottom right side of the screen 2 ʻEdit groupʼ screen is displayed To create a new operating group press the Add button ʻAdd groupʼ screen will be displayed to enter the name of the group When you press the Add button Add group screen is displayed 6 Auto control menu ...

Page 117: ... unit to include in the newly created group from the unregistered unit list and press the button to move to the registered unit list After entering the group name press the OK button Click on After selecting the unit from the list of unregistered unit press the button to include the unit to the applicable groupSave button to apply to system Check whether the group is created 6 Auto control menu ...

Page 118: ...AC Smart 6 5 Press the Save button 5 Press the Save button to save the setting When creating the group is completed it will return to the previous screen 6 Auto control menu ...

Page 119: ...the top right side of the screen you can create the same operating group as the basic control group you set in control and monitoring from the Unit management menu When you press the Set basic group button the same group as the group configured through the Setting menu will automatically be created as the operating group 6 Auto control menu ...

Page 120: ...it group button located at the bottom of ʻAuto controlʼ screen 2 ʼEdit groupʼ screen is displayed Select the operating group to delete and press the Delete button The applicable group will be deleted Press the Edit group button After selecting the group to delete press the Delete button 6 Auto control menu ...

Page 121: ...g drive group is created at group name Then select the device to be included at created group from un registered device list and move it to registered device list by pressing button Check whether the group is deleted Press the Save button 6 Auto control menu ...

Page 122: ...cated at the bottom of the ʻAuto controlʼ screen Press the Edit group button 2 ʻEdit groupʼ screen is displayed Select the group to rename and press the Rename button ʻRename groupʼ screen will be displayed to enter the name of the group After selecting the operating group press the Rename button 6 Auto control menu ...

Page 123: ...group name press the OK button 4 Check whether the name of the applicable group has been changed in the ʻGroup nameʼ and press the Save button to save the setting When the renaming of the group is completed it will return to the previous screen After checking that the group has been renamed press the Save button 6 Auto control menu ...

Page 124: ...tdoor temperature or overheating from indoor temperature etc To execute the temperature limit operation function the user enters the maximum and minimum temperature as follows AC Smart operates as follows based on the entered value When the indoor temperature higher than the set temperature the cooling function of the indoor unit will run to lower the indoor temperature below the set temperature W...

Page 125: ... This is the minimum temperature lT set for indoor temperature Operating method of temperature limit mode is displayed Average This is the method of operating the temperature limit operation function based on the average temperature detected for the indoor units within the group Fixed This is the method of operating the temperature limit operation function based on the temperature detected from th...

Page 126: ...ect the Auto control menu the following auto control screen is displayed Click on the Set option button Click on Set option button 2 The ʻCondition settingʼ screen is displayed Select the temperature limit operation group to set the temperature limit operation function and set each item For detailed description on the setting item refer to the following table Set each item 6 Auto control menu ...

Page 127: ... Indoor temperature can be measured in one of the three methods below Average This is the method of operating the temperature limit function based on the average temperature detected for the indoor units within the group Fixed This is the method of operating the temperature limit function based on the temperature detected from the first registered indoor unit within the group This sets whether to ...

Page 128: ... current information changes Click on the Close button to move to the prior screen 5 Exception of time setting using the temperature limit control function can be set to a non work hours If the exceptional option button appears in the presence of the group Click on Close button to return to prior screen 6 Auto control menu ...

Page 129: ...setting up non work time non operating to select a start time and end time 7 When you have completed all the setting click on the Save button The ʻInformationʼ screen to ask to save will be displayed Click on the Yes button 6 Auto control menu ...

Page 130: ... drops below the temperature difference from the reference temperature it runs the heat operation to raise the indoor temperature But when the temperature deviates from the indoor temperature range by the control monitoring or schedule etc the temperature is not controlled by this function When the setting or temperature criteria is changed while the auto change over function is in operation the c...

Page 131: ...e difference is displayed Fixed Method of operating the Auto change over operation function based on the temperature detected by applicable indoor unit by designating the representative indoor unit to operate based on the set temperature within the group Operating Method of operating the Auto change over operation function based on the temperature detected by applicable indoor unit by designating ...

Page 132: ...ng screen will be displayed To set the auto change over operation press the Condition setting button 2 The ʻCondition settingʼ screen is displayed Select the temperature limit operation group to set the function and set each item Refer to the following table for detailed description of each setting item Press the Condition setting button from the Auto change over operation tab Set each item 6 Auto...

Page 133: ...indoor units within the group Operating This is the method of operating the auto change over function based on the average temperature of the operating indoor units within the group Fixed This is the method of operating the auto change over function based on the temperature detected from the first registered indoor unit within the group This sets whether to execute the auto change over operation f...

Page 134: ...e setting is saved the Save button will be deactivated and will be reactivated when the current information changes Click on the Close button to move to the prior screen Click on Close button to return to prior screen 6 Auto control menu ...

Page 135: ...nd Wednesday from Monday to Thursday The Unit A operates from 22 00 on Monday before applying the time limited running The time limited operation is applied to run the Unit A on Tuesday and to stop at 4 00 after 4 hours The Unit B operates from 22 00 on Tuesday while the time limited running is applied Because the time limited running is also set to Wednesday the Unit B stops at 2 00 on Wednesday ...

Page 136: ...of time limited running group Whether the time limited running is used or not for the said group Limited running time specified for the said group Group name En Disable Time Item Description Name of each unit within the time limited running group Whether the time limited running of the current unit is operated or not Remaining time until the operation of the said unit stops Unit name Status Rest t...

Page 137: ...the following screen will be displayed To set the time limit operation press the Condition setting button 2 ʻCondition settingʼ screen is displayed Select the temperature limit operation group to set the function and set each item Refer to the following table for detailed description of each setting item Press the Condition setting button from the Time limited operation tab Set each item 6 Auto co...

Page 138: ...and more than one weekday can be selected Set whether to perform the time limited running or not Apply Perform the time limited running After Hourʼs Timer Perform the time limited running with exceptional time No apply The time limited running is not performed Group name Operation Stop standby time Select Day Enable Disable 3 When finishing all settings press Save button ʻInformationʼ screen to co...

Page 139: ...e current information is changed it is activated again Click Close button to return to the previous screen ʻAfter Hourʼs Timerʼ set please proceed along the following order 1 After selecting the set time and day of week After Hourʼs Timer select Click Close button to return to the previous screen 6 Auto control menu ...

Page 140: ...imit control function to select a start time and end time 3 If the day is not selected in the previous step you can not set the days and times To set all the settings you have completed the time of the day Save button is set to apply 6 Auto control menu ...

Page 141: ...yed in table format in order with the latest showing first You can classify view according to the period or type of history You can refresh view the history with the latest information The type of information shown on screen is as follows Item Description Order of the event of change in setting or unit condition Date of the event for the setting or control condition change is displayed Time of the...

Page 142: ...lowing order 1 Click on the Condition setting button Record search condition to classify and search the event by history code and period is displayed 2 Designate the history code or history period and click on the Apply button For detailed description of the setting item refer to the following chart When you click on Condition setting button History search condition screen is displayed After setti...

Page 143: ...emotely Previous 1 week This sets the history list to display the event that occurred one week back from the current time Previous 1 month This sets the history list to display the event that occurred one month back from the current time Set Period This displays the event that occurred only in the specific period Designate the period by pressing the calendar picture displayed in start and end date...

Page 144: ...creen the setting information and changes can occur This information is not immediately reflected to the history screen currently displayed To view the latest history information click on the Refresh button The history displayed on the screen is refreshed to the latest information Click on Refresh button 7 History menu ...

Page 145: ...be deleted All Error Delete button to access the installers have access to the History menu will appear 1 All Error Delete button code value E is deleted all records and historical information are rearranged 2 When the installer access privileges history at the bottom of the screen All Error delete button appears 7 History menu ...

Page 146: ... menu the following screen will be displayed You can view the operating time and statistical value of the indoor unit during a specific period You can view the monthly operating time in 3 months 6 months and 1 year from a specific time Reference Statistical information The statistical function provides the operating time of the indoor unit This does not provide operating time information for venti...

Page 147: ...ewing Reset button is only activated when logged in as installation expert The following information of accumulative time operation is displayed in table format Item Description Name of target to search the accumulative operating time is displayed This is displayed in applicable Zone Group or Indoor unit according to the condition setting Total operating time of the target set for the period is di...

Page 148: ...ss the ʻAccumulative operating timeʼ tab from the statistical menu and set the period to search the accumulative operating time from the ʻPeriodʼ item Press the button to select the dates And then press the Refresh button Set the period to search for the accumulative operating time and press the Refresh button 2 The following information about the accumulative operating time is displayed 8 Statist...

Page 149: ...ondition and target of the monthly operating time You can reset the monthly operating time information You can save the monthly operating time information as a file You can refresh view the monthly operating time information with the latest information Reset button is only activated when logged in as installation expert The following information of accumulative time operation is displayed in table...

Page 150: ...and set the month to set as basis to search the monthly operating time from ʻPeriodʼ item When you press the button you can select the year and month and the period to search the operating time 3 months 6 months 1 year and then press the Refresh button For the monthly operating time set the period to search and press the Refresh button 2 The following information for monthly operating time is disp...

Page 151: ... condition for the monthly operating time in the same way 1 Press the Condition setting button located at the ʻAccumulative operating timeʼ tab ʻCondition settingʼ screen to set the search unit and target is displayed When you press the Condition setting button the Condition setting screen will be displayed 3 Set the search unit and target and press the Apply button Refer to the following table fo...

Page 152: ...w by Unit Zone selection Set the Zone to show the usage information Group selection Set the Group within the Zone to show the usage information View setting Target setting 3 Message to confirm to save the changed information is displayed Press the Yes button 4 Accumulative operating time information is shown on the screen according to the set condition Press the Yes button 8 Statistical menu ...

Page 153: ...n example You can also save the accumulative operating time in the same way 1 With the external USB memory connected to AC SMART II search the monthly operating time When the search result of the monthly operating time is shown on the screen press the Save file button After searching the statistical information press the Save file button 2 ʻSave file asʼ screen is displayed Enter the name of the E...

Page 154: ...tistical information The Reset button is only activated when logged on as installation specialist authority Information Refreshing to latest statistical information While thetatistical information is displayed on the statistical menu the units connected to AC SMART II are still operating And the statistical information on the screen is not updated in real time To view the latest statistical inform...

Page 155: ... based on the configuration of Zone Group and Unit set from the unit management menu Zone and Group configuration is displayed in tree format You can add delete rename the Zone or Group List of Groups registered in the Zone or Units registered in the Group is displayed You can register a new unit or edit delete the information of the existing unit Unregistered Group or Unit is displayed Press the ...

Page 156: ... to register edit the indoor unit ventilator Eco V DX on off unit and AWHP unit You can interface with other external central controller The connected units can be automatically searched and registered Number of registered units is displayed by the type of connected units You can add a new unit or edit delete the information of the existing unit List of currently registered units is displayed Refe...

Page 157: ...splayed Press the Unit registration button located at the bottom right side of the screen will be displayed To create a schedule pattern press the Schedule pattern wizard button Press the Register unit button 2 ʻEdit unitʼ screen to register the unit will be displayed Click on the Auto setting When the ʻInformationʼ screen to check unit auto setting click on the Yes button Click on Auto setting bu...

Page 158: ...able located below the screen After the unit is searched the result is displayed 4 Temporarily save the searched unit When you press the OK button the ʻOKʼ screen to confirm to save will be displayed Press the Yes button to save and return to the previous screen Press the OK button to save and when the OK screen is displayed press the Yes button 9 System Menu ...

Page 159: ...k whether to apply the current setting will be displayed Click on the Yes button To apply to system click on Save button and click on Yes button 6 The setting to now will be applied to the system and you will see a message saying that you have completed saving the setting on the screen Click on the OK button to complete the registration When it is saved click on OK button 9 System Menu ...

Page 160: ...order 1 Press the Register unit button located at the bottom of the ʻUnit managementʼ menu Press Register unit button 2 Edit unit screen to register the unit is displayed Enter the information of the unit and click on the Add button Refer to the following chart for information to enter After entering unit information Click on Add button 9 System Menu ...

Page 161: ... FF and cannot be duplicated Enter the model of the unit You can enter up to 20 characters Enter the maximum power consumption value The power consumption must not exceed the set value You can enter up to 5 digits Type Unit name Address Model Capacity 3 Added unit information is displayed in the table Repeat the process in the same method to register all units to add To save the registered unit cl...

Page 162: ...ick on Yes button 5 Lastly you must register the temporarily saved unit setting to the system When you click on the Save button the current setting will be applied to the system and the screen will display the message saying that saving process has been completed Click on the OK button to complete the registration To apply to system click on Save button When saving is completed click on Yes button...

Page 163: ...rrent setting will be applied to the system and a message saying that the saving is completed will be displayed on the screen Press the OK button to complete the registration When the saving is completed press the OK button 9 System Menu ...

Page 164: ... the following screen is displayed To create a new zone click on AC Smart which is the highest node of the System tree List of unregistered units is displayed in Unregistered unit on the right side of the screen When you click on the highest node unregistered unit is displayed Reference When the unregistered unit is not shown When you initially execute AC Smart and have not executed the process of...

Page 165: ...een to enter the name of the new zone to create is displayed When you press the Add button the Zone Group Name screen is displayed 3 After entering the name of the zone to create click on the OK button To apply to system click on Save button When saving is completed click on OK button 9 System Menu ...

Page 166: ...ode of AC Smart node Check whether zone has been created 5 Click on the Save button to save the setting Message confirming to save will be displayed on screen Click on the Yes button After clicking on Save button when Information screen is displayed click on Yes button 9 System Menu ...

Page 167: ...splayed When you click on the OK button the save process will be completed Click on OK button to complete saving Reference Reflecting changed unit list After saving the setting the list of changed units Renamed deleted unit information will be reflected to the schedule auto control and statistical function 9 System Menu ...

Page 168: ...e to delete from the System tree and click on the Delete button After selecting zone to delete click on Delete button 2 Applicable zone is deleted Check whether the applicable zone has been deleted from the System tree Unit included in zone to delete is transferred to Unregistered unit Check whether zone has been deleted Can check whether unit included in applicable zone is in Unregistered unit 9 ...

Page 169: ...screen Click on the Yes button After clicking on Save button when Information screen is displayed click on Yes button 4 After the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed Click on OK button to complete saving 9 System Menu ...

Page 170: ... menu of AC Smart When you select the System menu the following screen is displayed Select the zone to rename from System tree Select zone to rename 2 Click on the Rename button Rename zone screen to enter the name of zone is displayed When you click on Rename button Rename zone screen is displayed 9 System Menu ...

Page 171: ... Manual 9 17 After renaming the zone click on OK button Check whether zone has been renamed 3 After renaming the zone click on the OK button 4 Check whether the applicable zone has been renamed in System tree 9 System Menu ...

Page 172: ...ck on the Yes button After clicking on Save button when Information screen is displayed click on Yes button 6 After the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed Click on OK button to complete saving 9 System Menu ...

Page 173: ...evices When executing some control command to specific group the devices included at group carry out same control command as well Resetting group To reset the group proceed in the following order 1 Select the System menu from the menu of AC Smart When you select the System menu the following screen is displayed Click on the name of the zone to reset the group from the System tree Select the group ...

Page 174: ... any zone Use the and button to include or delete the group Exclude group by clicking on button and excluded group is displayed in Unregistered unit 3 Select the zone to include the excluded group Registered unit displays the group including the applicable zone Select the excluded group After selecting zone select group to include 9 System Menu ...

Page 175: ...splayed in Registered unit Click on button to move designated group Applicable group displayed in Registered unit 5 Click on the Save button to save the setting Message confirming to save will be displayed on screen Click on the Yes button After clicking on Save button when Information screen is displayed click on Yes button 9 System Menu ...

Page 176: ...2 6 After the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed Click on OK button to complete saving 9 System Menu ...

Page 177: ...n you select the System menu the following screen is displayed Select the zone to include the new group to from the System tree Select zone to include newly created group 2 Click on Add button in system tree screen Group name screen to enter the name of the group to create is displayed When you click on Add button Group name screen is displayed 9 System Menu ...

Page 178: ... name of the group to create click on the OK button After entering the group name click on OK button 4 Check whether the applicable group is created in the lower node of the selected zone Check whether the group is created 9 System Menu ...

Page 179: ...screen Click on the Yes button After clicking on Save button when Information screen is displayed click on Yes button 6 After the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed Click on OK button to complete saving 9 System Menu ...

Page 180: ...ou select the System menu the following screen is displayed Select the group to delete from System tree and click on the Delete button After selecting the group to delete click on the Delete button 2 Applicable group is deleted Check whether the applicable group is deleted from the System tree Check whether group is deleted 9 System Menu ...

Page 181: ... screen is displayed click on Yes button 4 After the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed The unit included in the deleted group is moved to the Unregistered unit When you click on OK button the saving is completed Can check the unit included in deleted group in Unregistered unit 9 Syste...

Page 182: ... of AC Smart When you select the Setting menu the following screen is displayed Select the group to rename from the System tree Select group to rename 2 Click on the Rename button Rename group screen to enter the name of the group is displayed When you click on Rename button Rename zone screen is displayed 9 System Menu ...

Page 183: ...29 3 After renaming the group click on the OK button After renaming Group click on OK button 4 Check whether the name of the applicable group has been renamed in the System tree Check whether the group has been renamed 9 System Menu ...

Page 184: ...ck on the Yes button After clicking on Save button when Information screen is displayed click on Yes button 6 After the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed Click on OK button to complete saving 9 System Menu ...

Page 185: ...nit proceed in the following order 1 Select the System menu from the menu of AC Smart When you select the System menu the following screen is displayed Click on the name of the group to reset the unit from the System tree The unit included in the applicable group will be displayed in the Registered unit list Select the unit to reset After selecting group select the unit to reset 9 System Menu ...

Page 186: ...unit not assigned to any group is displayed in the Unregistered unit list Press the and button to add or delete the unit Press the button to exclude unit Excluded unit is displayed in Unregistered unit 3 Select the group and unit to add the excluded unit to After selecting the group select unit to add 9 System Menu ...

Page 187: ...gistered unit list Press the to move the designated unit Applicable unit will be displayed in the Registered unit 5 Click on the Save button to save the current setting Message confirming to save will be displayed on screen Click on the Yes button After clicking the Save button When the Information screen is displayed click on the Yes button 9 System Menu ...

Page 188: ...fter the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed Click on OK button to complete the save process 9 System Menu ...

Page 189: ...u from the menu of AC Smart When you select the Setting menu the following screen is displayed Click on the Unit Reg button located on the right side of the screen Click on Unit Reg button 2 Edit unit screen is displayed Select the unit to delete from the registered unit list and click on the Delete button The applicable unit will be deleted After selecting the unit to delete click on the Delete b...

Page 190: ...it screen will end and return to the prior screen Click on Yes button to save to system 4 Lastly you must register the setting of the unit temporarily saved Click on the Save button to save the setting Message confirming to save will be displayed on screen Click on the Yes button Click on Save button to apply to system When Information screen is displayed click on Yes button 9 System Menu ...

Page 191: ...Manual 9 37 5 After the setting process is displayed on the screen the save complete message is displayed When you click on the OK button the save process will be completed Click on OK button to complete save 9 System Menu ...

Page 192: ...rt When you select the System menu the following screen is displayed Click on the Unit Reg located on the right side of the screen Click on Unit Reg button 2 Edit unit screen is displayed Select the unit to change the information of from the unit list Change the information of the selected unit Refer to the following chart for the information entered After selecting the unit to edit Change the inf...

Page 193: ...cal address value is between 00 and FF and cannot be duplicated Enter the model of the unit You can enter up to 20 characters Enter the maximum power consumption value The power consumption must not exceed the set value You can enter up to 5 digits Type Unit name Address Model Capacity 3 Click on the Modify button The applicable unit information is changed When you click on the Modify button chang...

Page 194: ...en will end and return to the prior screen 5 Lastly you must register the setting of the unit temporarily saved Click on the Save button to save the setting Message confirming to save will be displayed on screen Click on the Yes button Click on Yes button to save to system Click on Save button to apply to system When Information screen is displayed click on Yes button 9 System Menu ...

Page 195: ...se the external central controller operates as master while the AC Smart operates as slave When the external central controller operates as master the external central controller gets the right to control some functions So when the AC Smart operates as slave you cannot use schedule automatic control and detailed lock functions ON L1 2 3 4 KSDO4H Multi V ON L1 2 3 4 KSDO4H Multi V LG NET 1 MENU SEL...

Page 196: ...tom and press OK button When interconnecting with the external central controller in order to automatically register the unit at the AC Smart the address range should be specified not to conflict with the address set the other controller When you Auto button the screen to specify the range is displayed Click Control link button Click Auto button Check the interconnection and click OK button Specif...

Page 197: ...inistrator password Set language displayed on screen Set screen saver and monitor OFF setting to protect the LCD panel Set the alarm to notify the user of error in the unit Set the temperature unit Celsius Fahrenheit displayed on screen Set system date and time Calibrate screen coordinate for touch screen This section describes how to use the Environment Setting menu to check and set the operating...

Page 198: ...u you can check the version of the AC SMART II software The AC Smart can use the USB memory to upgrade the software Therefore the user should be able to check the version of the current software and upgrade the version of the software when necessary Check the S W version 10 Environment Setting ...

Page 199: ...u To set a new administrator password proceed as follows 1 When you click on ʻPasswordʼ tab from the ʻEnvironment Settingʼ menu the screen to set the password will be displayed Enter the information for each item and press the Apply button For detail description of the entry item refer to the following table Enter the information about the item and click OK button Item Description Enter the passwo...

Page 200: ...assword will be displayed Press the Yes button Click Yes button to save changed password 3 The message that the password is changed is displayed Click OK button to finish setting the password Click Conform button to finish setting the password 10 Environment Setting ...

Page 201: ...ench German Dutch Italian Русский When you set the supported language all menu and message provided through the AC SMART II screen will be displayed in the set language To change the language displayed on the screen proceed as follows 1 When you press the ʻLanguageʼ tab from the ʻEnvironment Settingʼ menu the screen to set the language will be displayed Select the language to display and press the...

Page 202: ...I When you see the message asking to restart press Yes to restart AC SMART II Click Yes button to restart the AC Smart 3 After the AC Smart is restarted the login screen is displayed The login screen of the said language is displayed according to the language setting 10 Environment Setting ...

Page 203: ...minimize the power consumption Select whether to use the screen saver Select the theme of the screen saver Select the standby time to operate the screen saver You can set the password on the screen saver to confirm before returning to previous screen You can preview the selected theme of the screen saver Select the standby time to turn off the power of the monitor You can set the screen saver opti...

Page 204: ...review button you can check the selected screen saver Set You can set the screen saver option by the selected theme You can add or delete the image from the screen saver image list or set the image changing speed Preview You can preview the screen saver of the selected theme Standby time Set the standby time for the screen saver to operate When there is no entry to AC SMART II for the set time the...

Page 205: ... s Manual 10 9 2 Message to confirm to save the screen saver setting is displayed Press the Yes button to complete the screen saver setting Press Yes button to save the changed screen saver setting 10 Environment Setting ...

Page 206: ...the information of each item and press the Apply button For detail description of each item refer to the following table After setting the alarm press the Apply button Item Description You can set whether to use the Alarm function Use Set to use the Alarm function Do not use Set not to use the Alarm function You can set the time to display the Alarm Continuously display Set to continuously display...

Page 207: ...whether to save the Alarm setting is displayed Press the Yes button to complete the Alarm setting Press the Yes button to save the changed alarm setting 3 In case of an error in the future the following alarm screen will be displayed 10 Environment Setting ...

Page 208: ...displayed on the screen proceed as follows 1 When you press the ʻTemperature displayʼ tab from the ʻEnvironment Settingʼ menu the screen to set the temperature unit will be displayed Select the temperature unit to use and press the Apply button After setting the screen saver press the Apply button 2 To change the displayed temperature you must restart AC SMART II When the screen to confirm to rest...

Page 209: ...Installation Owner s Manual 10 13 3 After restarting AC SMART II the log in screen is displayed Log in to check whether the set temperature unit is displayed on the screen 10 Environment Setting ...

Page 210: ...d the ventilator at the time setting If you change the date and time it can affect the schedule time limit operation and usage statistics function Set the current time Select the time zone of the region where AC SMART II is installed Select the date Keep the following steps to set the time of the AC Smart system 1 When you press the ʻDate Time tabʼ from the ʻEnvironment Settingʼ menu the screen to...

Page 211: ...lick apply button Item Description Set the date year month day Select the time a m p m hour minute second Select the time zone according to the reference area After reset a AC Smart timezone information change will be applied Date Current time Standard time zone 3 When you press the OK button the time setting will be completed and the ʻDate Time propertiesʼ screen will be closed to return to the p...

Page 212: ...brate the touch screen Information Using the external button of the AC Smart to calibrate the screen The screen calibration function can be executed by pressing Backlight button and Keyboard button at once located at the top of the AC Smart When you cannot perform this menu because of the incorrect screen coordinate use this method to calibrate the screen Keep the following steps to calibrate the ...

Page 213: ...ibrationʼ tab Press the Re Calibrate button 3 The cross symbol is displayed at the center of the screen Touch the center of the cross with the stylus Repeat this for top left top right bottom left and bottom right cross symbol When the cross is displayed at the center press the center of the cross 10 Environment Setting ...

Page 214: ...system or not Press the screen with the touch pen to apply it to the system 5 Return to the previous ʻStylus propertiesʼ screen Press the OK button to end the screen calibration and return to the previous screen Click the screen to use the current setting When press ok button return to previous screen 10 Environment Setting ...

Page 215: ...the statistical calculations of the operating time Set the upgrade to maintain the latest version software Backup and restore the database to protect important information Press the tab to select each function of the environment setting menu Reference Authentication of Advanced Environment Setting menu Advanced Environment Setting menu can only be used by the installation ID and the menu will not ...

Page 216: ...ditioner by using the web server function of the AC Smart So the network setting of the AC Smart consists of the remote service setting for the SVCNet connection and the adapter network setting for the IP setting In the ʻNetworkʼ tab you can set the remote service and network adapter to communicate with the external system Select whether to use the remote service Select the service server address ...

Page 217: ...ication Item Description CHECK SMART Select whether to use the function for sending the information of the AC Smart to the SVCNet Enter the server address of the SVCNet Enter the server port of the SVCNet Specify the period to update the information at the SVCNet by minute Enter the IP address set at the current AC Smart Enter the information about the location where the current AC Smart is instal...

Page 218: ...age confirming that the network setting has been saved will be displayed Pres the Yes button to complete the network setting Save changed network setup by pressing Yes button 11 Introduction to Advanced Environment setting ...

Page 219: ... tab from ʻAdvanced Environment Settingʼ menu the screen to set the network will be displayed Press the Network adapter setting button Press the Network adapter setting button 2 It will switch to the screen to set the network adapter information When you press the ʻCS89001ʼ icon twice the ʻCS8900 settingʼ screen to set the network will be displayed When you press the CS89001 icon twice CS8900 sett...

Page 220: ...tab to select whether to set the IP address of the additional DNS Domain Name Server When you enter the IP address of the DNS enter the additional information as shown at the below table Set the IP address Set the name server Item Description Enter the IP address to be set at the AC Smart Enter the subnet mask for the IP address Enter the IP address of the gateway IP Address Subnet mask Default ga...

Page 221: ...ondary DNS Primary WINS Secondary WINS 5 Press OK button to apply the current network information setting to the system ʻCS8900 Ethernet Driver settingʼ screen is ended and it returns to the previous adapter network setting screen Finally when you press X button at the top right on the screen setting the adapter network is finished Click X button to return to the initial screen Click OK button to ...

Page 222: ...the email address to send to Set to have email sent once a day when there is no error Set the email transmission frequency 10 min unit for the error Reference Email error notification In order to stop receiving the email in error situation you must resolve the error and maintain the error free condition Reference Email account information The Email screen has dummy values pre entered to help the u...

Page 223: ...email setting screen will be displayed You must first set the account to send the email Press the Account management button Press Account button 2 When the ʻEmail account settingʼ screen is displayed enter the email account information For detail description of each setting item refer to the following table 11 Introduction to Advanced Environment setting ...

Page 224: ... User name E mail address Sending mail server Server information SMTP User name Password Log on by using the SPA Security Password Authentication Sending mail server port Server information Log on information 3 Press Account setting test to make sure that the set account is correct Setting the e mail account can be finished by passing this test But for the email account information that has been t...

Page 225: ...ssfully performed the finish message is displayed Press OK button to end testing Click OK button 5 When it returns to ʻE mail account settingʼ screen press Apply button to save the set account information Press the Apply button 11 Introduction to Advanced Environment setting ...

Page 226: ...isplayed Press the Yes button to save the setting Press the Yes button 7 When it returns to the email setting screen enter the email information For description of each item refer to the following table Enter email information 11 Introduction to Advanced Environment setting ...

Page 227: ...thin 1 hour by 10 minutes Also even when no error is occurred it can be set to be automatically sent once a day Email usage setting Enter the e mail subject Enter receive Email address Sending Frequency setting 8 When the screen returns to the email setting screen you must save the email information entered When you press the Apply button screen to confirm to save the email setting will be display...

Page 228: ...e the 30th does not exist for February You can set the reference date to calculate the operating time of the indoor unit from the ʻStatistical reference dateʼ tab 1 When you select ʻStatistical reference dateʼ from ʻAdvanced Environment Settingʼ menu the following screen will be displayed Enter the statistical reference setting item and press the Apply button For detail description of each entry i...

Page 229: ...s button to save the changed statistical reference date 3 Message to ask whether to save the statistical reference date to the current month is displayed Press the Yes button to complete the statistical reference date setting Press the Yes button to save the statistical reference date setting 11 Introduction to Advanced Environment setting ...

Page 230: ...device containing the software update image The name of the upgrade file of AC SMART II saved in the USB memory must be acsmart_firmware dat Keep the following steps to upgrade the software of the AC Smart II Software 1 When you select the ʻS W upgradeʼ tab from the ʻAdvanced Environment Settingʼ menu the following setting screen will be displayed When the message confirming to restart the AC Smar...

Page 231: ...g that it takes some time to upgrade the software is displayed Press OK button Click OK button 3 Message showing that it requires time to upgrade the software is displayed Press the OK button Click OK button 11 Introduction to Advanced Environment setting ...

Page 232: ...e procedure of the S W upgrade is finished the message showing that the system is to be restarted is displayed When you press OK button upgrading is ended And then the AC Smart is restarted and the Login screen is displayed Click OK button 11 Introduction to Advanced Environment setting ...

Page 233: ... SMART II to the USB memory A Type or restore the database saved in the USB memory to AC SMART II Note Before backing up and restoring the database Before backing up and restoring the database the left USB port of the AC Smart should be connected to the USB device containing the database After the database is successfully restored the software of the AC Smart is restarted Back up the database of A...

Page 234: ... the database press the Proceed button next to the DB back up item Press the Proceed button 2 When the ʻDB Managerʼ screen to back up the database is displayed the process to back up the database will automatically proceed When the backup is completed the DB Manager screen will be closed to return to the previous screen DB Manger screen is displayed to show the database back up process 11 Introduc...

Page 235: ...tabase press the Proceed button next to the DB restore item Press the Proceed button 2 ʻDB Managerʼ screen to read the database is displayed and the screen to confirm to restart the system is also displayed When you press the Yes button the database restoring process will automatically proceed 1 DB Manager screen and restart confirmation screen are displayed 2 Press the Yes button to precede the D...

Page 236: ...AC Smart 11 22 3 When the database is successfully restored the AC Smart program is restarted and the Login screen is displayed 11 Introduction to Advanced Environment setting ...

Page 237: ...g The method to set the network information for the web server function of AC SMART II refer to the ʻNetworkʼ section of the ʻAdvanced Environment Settingʼ menu Web server log in To use the web server function of AC SMART II you must follow the log in process In the log in screen you can set the language Korean English and temperature unit Celsius Fahrenheit Control Monitoring menu Control Monitor...

Page 238: ...can grant or delete access to connect to the web server of AC SMART II to control the units to users other than the administrators Zone setting menu In the Zone setting menu you can set specific users other than the administrator to control only units included in specific Zone Reference Manual for web server For detail method on connecting to web server function of AC SMART II and control monitori...

Page 239: ......

Reviews: