Installation Manual
25
ENGLISH
Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
[Air inlet side view]
Control box cover
Indoor
power cord
Remote
controller
cord
Control box cover screw
CAUTION
Power Input
1(L) 2(N)
3
4
5
Terminals on the Indoor Unit
Terminals on the outdoor unit
1(L) 2(N)
3
4
2(N)
1(L)
POWER INPUT
1(L) 2(N)
3
4
5
Terminals on the Indoor Unit
36k Btu
(3
Ø
)
Terminals on the Outdoor Unit
1(L) 2(N)
1(L) 2(N)
3
4
1(L) 2(N)
3
4
5
Terminals on the Indoor Unit
POWER INPUT
30k Btu
24k Btu
(1
Ø
)
(1
Ø
)
Terminals on the Outdoor Unit
1(L) 2(N) 3
N
T
S
R
The power cord connected to the outdoor unit
should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer
or its service agent.
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).
20mm
GN/YL
20mm
GN/YL
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(12/18/24/30/36K)
Capacity
1 Phase
24k/30k
2.5mm
2
Capacity
3 Phase
36k
1.5mm
2
7.5mm
W
ARNING:
Make sure that the screws of the terminal are free from looseness.
Wiring Connection