160
COMMISSIONING
ENGLISH
Troubleshooting for Error Code
Display
code
Title
Cause of error
Check point & Normal condition
1
Problem in remote room air sensor
• Incorrect connection between
sensor and PCB(Heater).
• PCB(Heater) fault
• Sensor fault
• Resistance: 10 k
Ω
at 25 centigrade
(unplugged)
→
for Remote room
air sensor
• Resistance: 5 k
Ω
at 25 centigrade
(unplugged)
→
for all sensors
EXCEPT remote room air sensor
• Voltage: 2.5 V DC at 25 centigrade
(plugged) (for all sensors)
• Refer resistance-temperature table
to check in different temperature
2
Problem in refrigerant (inlet side) sensor
6
Problem in refrigerant (outlet side) sensor
8
Problem in water tank sensor
13
Problem in solar pipe sensor
16
Problems in sensors
17
Problem in water-inlet sensor
18
Problem in water-outlet sensor
19
Problem in electric heater outlet sensor
10
BLDC Water pump Lock
Restriction of BLDC Water pump
• BLDC Water pump defect /
assembly condition abnormal
• Fan lock by foreign material
3
Bad communication between remote
controller and unit.
• Incorrect connection between
sensor and PCB(Heater)
• PCB(Heater) fault
• Sensor fault
• Wire connection between remote
controller and Main PCB
assembly(Heater) should be tight
• Output voltage of PCB should be
12 V DC
5
Bad communication between Main PCB
assembly(Heater) and Main PCB
assembly(Inverter) of the unit.
• The connector for transmission is
disconnected
• The connecting wires are
misconnected
• The communication line is broken
• Main PCB assembly(Inverter) is
abnormal
• Main PCB assembly(Heater) is
abnormal
• Wire connection between remote
control panel and Main PCB
assembly(Heater) should be tight.
53
9
PCB program (EEPROM) fault
• Electrical or mechanical damage a
the EEPROM
• This error can not be permitted
14
Problem in flow switch
• Flow switch is open while internal
water pump is working
• Flow switch should be closed
while internal water pump is
working
15
Water pipe overheated
• Abnormal operation of electric
heater
• Leaving water temperature is
above 72 °C.
• If there is no problem in electric
heater control, possible maximum
leaving water temperature is 72 °C
20
Thermal fuse is damaged
• Thermal fuse is cut off by
abnormal overheating of internal
electric heater
• Mechanical fault at thermal fuse
• Wire is damaged
• This error will not be happened if
temperature of electric heater tank
is below 80 °C