Piping and Wiring for Outdoor Unit
54
Air-to-Water Heat Pump
Connecting the communication cable to the Outdoor Unit
< Diagram for Connecting Power cable & Communication cable >
The communication cable is intended for
communication between the external
Gateway PI485(Modbus Converter) and the
internal input/output module.
Gateway PI485(Modbus Converter) is an
accessory.
After you assemble the an Gateway PI485
(Modbus Converter) on the C/box(Outdoor
Unit),
Connect Cables. (
①
CN-OUT,
②
CN-PWR )
After routing the plated cable between Indoor
unit and Outdoor unit , connect four cables you
connect to the connection clips Bus_A [+] /
Bus_B [-] / GND / 10 V on the Gateway
PI485(Modbus Converter) module.
Gateway PI485(Modbus Converter) is located
on the Outdoor Unit as shown in the picture
below.
CN-PWR
CN-OUT
X5
BUS-B
BUS-A
GND
10 V
Communication cable
❈
Field install PI485 (Modus Converter)
Indoor Power
supply
N
L
Switch
Power cable
10V (4)
GND (3)
BUS-A (1)
BUS-B (2)