Chapter 3 - Quick Start Up
33
3.2
Operation using Control Terminals
1.
Install a potentiometer on terminals V1, VR,
5G and connect wiring as shown below.
2.
Apply AC power.
3.
Confirm that the DRV 03 is set at ‘Fx/Rx-1’.
4.
LCD:
Press
▲
key to move DRV 04.
7-Seg:
Rotate encoder knob until ‘04’ is
displayed.
5.
LCD:
Press
PROG
key.
7-Seg:
Press
PROG/ENT
key.
6.
LCD:
Press
▲
key and set at ‘V1’.
7-Seg:
Rotate encoder knob and set at ‘2’.
7.
LCD:
Press
ENT
key.
7-Seg:
Press
PROG/ENT
key.
8.
Press
SHIFT/ESC
key.
9.
Set the frequency by rotating the
potentiometer.
10.
Close the FX or RX contact to run the
motor.
11.
Open the FX or RX contact to stop the
motor.
LCD Display
7-Segment Display
DRV
►
T/K 0.0 A
00 STP 0.00Hz
The DRV LED is ON.
DRV
►
Drive mode
03 Fx/Rx-1
DRV
►
Freq mode
04 Keypad-1
DRV
►
Freq mode
04 Keypad-1
DRV
►
Freq mode
04 V1
DRV
►
Freq mode
04 V1
DRV
►
T/V 0.0 A
00 STP 0.00Hz
DRV
►
T/V 0.0 A
00 STP 60.00Hz
The PROG/ENT LED is turned ON.
The PROG/ENT LED is turned ON.
The PROG/ENT LED is turned OFF.
The FWD or REV LED starts blinking.
The RUN LED starts blinking.
The STOP/RESET LED starts blinking. The STOP/RESET LED starts blinking.
1
㏀
, 1/2 W
P1 P2
JOG
CM
P3 FX RX NC
CM BX
RST
I
VR VI
FM 5G