Chapter 2 - Operation 

 
 

25

 

2.4

 

Operation Method 

 

The iS5 has several operation methods as shown below. 
 

Operation Method 

Function 

Function Setting 

Operation using 

Keypad

 

Run/Stop command and frequency are set only through the 
keypad. 

DRV 03: Keypad 
DRV 04: Keypad-1 or -2 

Operation using  

Control Terminals

 

Closing FX or RX terminal performs Run/Stop.  
Frequency reference is set through V1 or I or V1+I terminal. 

DRV 03: Fx/Rx-1 or -2 
DRV 04: V1 or I or V1+I 

Run/Stop is performed by the keypad.  
Frequency reference is set through the V1 or I or V1+I 
terminal. 

DRV 03: Keypad-1 or -2 
DRV 04: V1 or I or V1+I 

Operation using both 

Keypad and Control 
Terminals

 

Closing FX or RX terminal performs Run/Stop.  
Frequency reference is set through the keypad. 

DRV 03: Fx/Rx-1 or -2 
DRV 04: Keypad-1 or -2 

Operation using  

Option Board 

Operation using option board.  
The iS5 has five option boards and three sub-boards.  

Option Boards:

 RS485, Device-Net, F-Net, ProfiBus and 

ModBus 

Sub-Boards:

 Sub-A Board, Sub-B Board and Sub-C Board 

(Please refer to ‘

Chapter 6 - Options’

 for more information.) 

 

 
 

Summary of Contents for SV008iS5-2

Page 1: ...ng sicher und setzen Sie die Kabel keinen mechanischen Belastungen aus ACHTUNG Brandschutzmaßnahmen 1 Montieren Sie den Umrichter auf einer nicht brennbaren Oberfläche Montage auf oder in der Nähe brennbarer Materialien kann zu Brandausbruch führen 2 Beschädigte Geräte müssen vom Netz getrennt werden und dürfen nicht weiter betrieben werden Mißachtung kann Folgeschäden Unfälle oder Feuer nach sich...

Page 2: ... unwirksam sein 7 Installieren Sie einen Entstörfilter um Störungen die vom Umrichter ausgehen zu minimieren 8 Installieren Sie im Falle von Störungen der Eingangsspannung eine Drosselspule Blindleistungskompensationskondensatoren oder Generatoren können durch hochfrequente Störungen überhitzen und beschädigt werden 9 Durch Spannungsspitzen können die Isolierungen der Motoren zerstört werden Verwe...

Page 3: ...vigation LCD Bedienteil 20 2 2 4 7 Segment Display 22 2 2 5 Einstellung der Parameter 7 Segment Bedienteil 23 2 2 6 Parameter Navigation 7 Segment Bedienteil 24 2 3 Steuerungsmethoden 25 KAPITEL 3 Schnellstart 27 3 1 Betrieb mittels Bedienteil 28 3 2 Bedienung mittels Signalanschlüssen 29 3 3 Bedienung mittels Bedienteil und Signalanschlüssen 30 3 3 1 Frequenzeinstellung durch externes Signal Ein ...

Page 4: ... 54 5 5 Wartung 55 5 5 1 Vorsichtsmaßnahmen 55 5 5 2 Routine Inspektionsarbeiten 55 5 5 3 Periodische Wartungsarbeiten 55 5 5 4 Auswechseln der Sicherung 55 5 6 Tägliche und periodische Wartungsarbeiten 56 KAPITEL 6 Anhang A Parameter nach Verwendung 57 KAPITEL 7 Anhang B Parameter nach Funktion 58 KAPITEL 8 Anhang C Peripheriegeräte 60 Konformitätserklärung 63 ...

Page 5: ...C 1 2 Umgebungsbedingungen 9 Kontrollieren Sie die Umweltbedingungen am Montageort Die Umgebungstemperatur muß zwischen 10 C 14 F und 40 C 104 F liegen Die relative Luftfeuchtigkeit muß unter 90 nicht kondensierend betragen Der Aufstellungsort darf nicht höher als 1000 m liegen 9 Der Umrichter darf keiner direkten Sonneneinstrahlung ausgesetzt werden und ist gegen Vibrationen zu schützen 1 3 Monta...

Page 6: ...en vom Umrichter ferngehalten werden Montieren Sie den Umrichter in einer sauberen Umgebung oder in einem geschlossenen Schaltschrank der das Eindringen von Fremdkörpern verhindert Bei der Montage im Schaltschrank ist auf gute Kühlung zu achten insbesondere wenn mehrere Umrichter in einem Schaltschrank untergebracht werden bzw wenn ein Ventilator im Schaltschrank eingebaut ist Unkorrekte Montage k...

Page 7: ...Maße in mm inches Gehäuse kW Umrichtertype W1 W2 H1 H2 D1 0 75 SV008iS5 2 4 1 50 SV015iS5 2 4 2 20 SV022iS5 2 4 Gehäuse 1 4 00 SV037iS5 2 4 150 5 91 130 5 12 284 11 18 269 10 69 156 5 6 16 5 50 SV055iS5 2 4 Gehäuse 2 7 50 SV075iS5 2 4 200 7 87 180 7 09 355 13 98 340 13 39 182 5 7 19 ...

Page 8: ...e 4 18 5 22 kW Maße in mm inches Gehäuse kW Umrichtertype W1 W2 H1 H2 D1 15 SV110iS5 2 4 Gehäuse 3 20 SV150iS5 2 4 250 9 84 230 9 06 385 15 16 370 14 57 201 7 91 25 SV185iS5 2 4 Gehäuse 4 30 SV220iS5 2 4 304 11 97 284 11 18 460 18 11 445 17 52 234 9 21 ...

Page 9: ... für VR V1 I Störmelderelais max AC250V 1A max DC30V 1A Multifunktionsausgang Relais 1 max AC250V 1A max DC30V 1A Werkseinstellung Ein Anmerkung Leistungsanschlüsse Signalanschlüsse 1 Die Anschlußkonfiguration ist abhängig von der Umrichtertype Siehe Kapitel 1 7 Leistungsanschlüsse 2 Das analoge Eingangssignal kann Spannung Strom oder beides sein 3 Falls eine DC Drossel installiert wird muß die Br...

Page 10: ...S5 4 SV220iS5 4 R S T G P1 P2 N U V W Symbol Bedeutung R S T AC Netzanschluß 3 Phasen 200 230VAC oder 380 460VAC G Erdung P Positiver DC Anschluß Anschlußklemmen der DB Einheit P P5 Die Installation ist erforderlich falls eine höhere Einschaltdauer 30 ED der Bremse gewünscht wird P1 P2 Anschluß für externe Drossel P1 P2 und DB Einheit P2 P1 N Negativer DC Anschluß Anschlußklemme für DB Einheit N N...

Page 11: ...en R S T G N B1 B2 U V W Fig 1 Anschluß des Bremswiderstandes Typ A 1 7 2 Typ B Konfiguration Bei Umrichtern dieser Konfiguration können Bremswiderstand und oder DB Einheit angeschlossen werden R S T G P N B1 B2 U V W Fig 2 Anschluß des Bremswiderstandes Typ B R S T G P N B1 B2 U V W Fig 3 Anschluß von Bremswiderstand und DB Einheit Typ B Motor Bremswiderstand 3 Phasen Netzeingang Motor 3 Phasen N...

Page 12: ...2 entfernt werden R S T G P1 P2 N U V W Figur 4 Anschluß von DC Drossel und DB Einheit Typ B WARNUNG Statische Aufladung bzw Fehlerströme zwischen Gehäuse Leistungselektronik und Netzanschluß können elektrische Schläge verursachen Erden Sie daher immer zuerst das Gehäuse Leistungsanschluß G und schließen Sie erst dann die Netzversorgung an Motor 3 Phasen Netzanschluß DB Einheit DC Drossel Bremswid...

Page 13: ... Umrichters beeinflussen Die Installation von Filtern am Eingang des Umrichters kann diese Störungen reduzieren 9 Installieren Sie am Ausgang des Umrichters keine Blindleistungskompensation Entstörfilter oder Überspannungsableiter Diese Geräte oder der Umrichter können beschädigt werden 9 Stellen Sie sicher daß vor Anschlußarbeiten die Zwischenkreis Ladekontrolle auf AUS ist Die Kondensatoren blei...

Page 14: ...2 11 kW M5 26 14 5 14 5 6 0 6 0 10 10 15 kW M5 26 22 6 22 6 16 10 6 8 18 5 kW M6 45 38 8 38 8 16 10 6 8 400V Gerät 22 kW M6 45 38 8 38 8 25 16 4 6 Netz und Motoranschluß R S T G N B1 B2 U V W 3 Das angegebene Drehmoment ist unbedingt einzuhalten Lockere Schrauben können Kurzschlüsse und Störungen verursachen Zu fest angezogene Schrauben können die Klemmen beschädigen und ebenfalls Kurzschlüsse und...

Page 15: ...uittierung Start Stop Kontakte CM Masse Masse für Start Stop Kontakte NC Nicht verwendet VR Spannungsversorgung 10V Spannungsversorgung für analoge Frequenzeinstellung Max 12V 100mA V1 Drehzahl Sollwert Spannung Drehzahl Sollwerteingang 0 10V Widerstand des Einganges 20 kOhm I Drehzahl Sollwert Strom Drehzahl Sollwerteingang DC 4 20mA Widerstand des Einganges 250 Ohm Eingangssignal Analoge Frequen...

Page 16: ...hlüsse und verlegen Sie diese Leitungen getrennt von den Leistungsanschlüssen oder anderen Leitungen für Netzspannung 9 Verwenden Sie 1 5mm 22AWG Litzenkabel für die Signalanschlüsse Steuerkreisanschluß Bein eingeschaltetem Signalanschluß ist die Stromrichtung wie unten abgebildet M ist die Masse für die Eingangssignalanschlüsse ACHTUNG Keine Spannung an die Signalanschlüsse FX RX P1 P2 P3 JOG BX ...

Page 17: ...montiert Falls das Bedienteil nicht ordnungsgemäß montiert ist wird am Display nichts angezeigt Kontrollboard Steuerungsklammleiste Relaisausgang Klemmleiste Bedienteil Anschluß CN3 Sub Board Anschluß Klemmleiste für Netzanschluß und Signalanschlüsse Optionsboard Anschluß Sub Board Optionsboard ...

Page 18: ...und dgl Funktionsmenü 1 FU1 FU1 LED Grundlegende Parameter wie Maximalfrequenz Drehmomentboost oder dgl Funktionsmenü 2 FU2 FU2 LED Anwendungsparameter wie Frequenzsprünge Frequenzlimit etc Input Output Menü I O I O LED Parameter für Sequenzbetrieb Einstellung der Multifunktionsanschlüsse automatischer Betrieb etc Sub Board Menü EXT EXT LED Dieses Menü wird bei Vorhandensein eines Subboards angeze...

Page 19: ... und Ab Pfeile werden zum Bewegen durch die und Änderung der Daten verwendet Rückwärtslauf Die Rückwärts LED blinkt wenn der Motor beschleunigt oder verzögert Die Programm Taste dient zum Umschalten auf den Programmier modus Die Enter Taste wird zum Bestätigen eines eingegebenen Wertes benutzt SHIFT Bewegen des Cursors im Programmiermodus ESC Sprung auf DRV00 Vorwärtslauf Die Vorwärts LED blinkt w...

Page 20: ...3 die Sequenznummer Schritt 4 Ausgangsstrom Zeigt den Ausgangsstrom 5 Parameter Zeigt den Code des jeweiligen Parameters an Verwenden Sie die Auf Ab Tasten zur Navigation durch die 0 99 Codes 6 Betriebsstatus Zeigt die Betriebsart an STP Stop FWD Vorwärts REV Rückwärts DCB Gleichstrombremsen LOP Verlust des Signales vom Optionsboard DPRAM Fehler LOR Verlust des Signales vom Optionsboard Kommunikat...

Page 21: ...hseln Sie durch Drücken der PROG Taste in den Programmiermodus der Cursor blinkt jetzt 4 Mit SHIFT ESC bewegen Sie den Cursor an die gewünschte Stelle 5 Drücken Sie die Auf oder Ab Tasten zum Verändern der Parameter 6 Geben Sie den eingestellten Wert mit ENT ein Der Cursor hört zu blinken auf Anmerkung Daten können nicht verändert werden wenn 1 Der Parameter im Betrieb nicht verändert werden kann ...

Page 22: ...FU1 Dec pattern 06 Linear FU2 Last trip 3 03 I O V1 freq y1 03 0 00 Hz DRV Freq mode 04 KeyPad 1 FU1 Stop mode 07 Decel FU2 Last trip 4 04 I O V1 volt x2 04 10 00 V DRV Step freq 1 05 10 00 Hz FU1 DcSt value 08 50 FU2 Last trip 5 05 I O V1 freq y2 05 60 00 Hz FU1 Stall Level 60 150 FU2 Para lock 94 0 I O Way1 2D 60 Forward MODE MODE MODE MODE I O Jump code 00 1 MODE MODE MODE MODE DRV Drive mode 0...

Page 23: ...nur wenn ein Sub Board installiert ist I O EXT Optionsmenü Blinkt wenn Parameter DRV 24 EXT ausgewählt ist Leuchtet wenn das Sub Board Menü ausgewählt ist Dieses Menü erscheint nur wenn ein Optionsboard installiert ist FU2 I O EXT Anwendungsmenü Blinkt wenn Parameter DRV 25 FUN2 ausgewählt ist 7 Segment Display Drehschalter Dient zum Navigieren durch Menüs und Parameter und wird zum Ändern der Par...

Page 24: ...ückwärts Zweites Zeichen d DC Bremsen J Jog Signaleingang 1 8 Schrittfrequenzeingang Zeigt den jeweiligen Schritt im automatischen Betrieb an Beide Zeichen Bei Signalverlust LP Verlust des Signales vom Optionsboard DPRAM Fehler Lr Verlust des Signales vom Optionsboard Kommunikations Netzwerkfehler Lv Verlust des analogen Frequenzsignales V1 0 10V LI Verlust des analogen Frequenzsignales I 4 20mA L...

Page 25: ...arametercode 20 angezeigt wird 2 Drücken Sie PROG ENT um in das FUN1 Menü zu wechseln 3 Drehen Sie am Drehschalter bis der gewünschte Parametercode angezeigt wird 4 Drücken Sie PROG ENT um in den Programmiermodus zu wechseln das Display blinkt 5 Mit SHIFT ESC bewegen Sie den Cursor an die gewünschte Stelle 6 Drehen Sie den Drehschalter zum Verändern des Parameters 7 Geben Sie den so eingestellten ...

Page 26: ...2 EX T D RV FU 1 I O FU 2 EX T D RV FU 1 I O FU 2 EX T D RV FU 1 I O FU 2 EX T D RV FU 1 I O FU 2 EX T D RV FU 1 I O FU 2 EX T D RV FU 1 I O FU 2 EX T D RV FU 1 I O FU 2 EX T D RV FU 1 I O FU 2 EX T PROG ENT D R V FU 1 I O FU 2 EX T D R V FU 1 I O FU 2 EX T D R V FU 1 I O FU 2 EX T Drehschalter FU1 Group Code DRV Menü FU2 Group Code I O Group Code PROG ENT PROG ENT SHIFT ESC PROG ENT ...

Page 27: ...r I oder V1 I Der EinAus Befehl wird über das Bedienteil erteilt Die Sollfrequenz wird mit Hilfe der Anschlüsse V1 oder I oder V1 I eingestellt DRV 03 Keypad 1 oder 2 DRV 04 V1 oder I oder V1 I Bedienung mittels Bedienteil und Signalanschlüssen Der EinAus Befehl wird durch Schließen der Kontakte FX oder RX erteilt Die Sollfrequenz wird mit Hilfe des Bedienteiles eingestellt DRV 03 Fx Rx 1 oder 2 D...

Page 28: ......

Page 29: ...ontieren wie in Kapitel 1 3 beschrieben z Montieren Sie den Umrichter an einem trockenen sauberen Platz z Lassen Sie seitlich und oberhalb des Umrichters genügend Freiraum z Die Umgebungstemperatur muß unter 40 C 104 F liegen z Falls zwei oder mehrere Umrichter in einem Gehäuse untergebracht werden sollen ist zusätzliche Kühlung erforderlich 2 Umrichter anschließen wie in Kapitel 1 7 Leistungsansc...

Page 30: ...gewählt 9 LCD Drücken Sie die ENT Taste um den Wert abzuspeichern 7 Seg Drücken Sie die PROG ENT Taste um den Wert abzuspeichern 10 LCD Drücken Sie FWD oder REV um den Motor zu starten 7 Seg Drücken Sie RUN um den Motor zu starten 11 Drücken Sie STOP RESET um den Motor zu stoppen LCD Display 7 Segment Display DRV T K 0 0 A 00 STP 0 00Hz DRV Cmd freq 00 0 00Hz DRV Cmd freq 00 60 00Hz DRV K K 0 0 A ...

Page 31: ...die PROG ENT Taste 8 Drücken Sie die SHIFT ESC Taste 9 Setzen Sie die Sollfrequenz mit Hilfe des Potentiometers 10 Schließen Sie den FX oder RX Kontakt um den Motor zu starten 11 Öffnen Sie den FX oder RX Kontakt um den Motor zu stoppen LCD Display 7 Segment Display DRV T K 0 0 A 00 STP 0 00Hz Die DRV LED leuchtet DRV Drive mode 03 Fx Rx 1 DRV Freq mode 04 Keypad 1 DRV Freq mode 04 Keypad 1 DRV Fr...

Page 32: ...f 0 6 LCD Drücken Sie die ENT Taste 7 Seg Drücken Sie die PROG ENT Taste 7 Bestätigen Sie die Eingabe DRV 04 auf V1 8 Drücken Sie die SHIFT ESC Taste Setzen Sie die Frequenz durch Drehen am Potentiometer 9 LCD Drücken Sie die FWD bzw REV Taste 7 Seg Drücken Sie die RUN Taste P1 P2 JOG CM P3 FX RX NC CM BX RST I VR VI FM 5G 4 20mA Signal 1Ohm 1 2 W P1 P2 JOG CM P3 FX RX NC CM BX RST I VR VI FM 5G D...

Page 33: ...durch Drehen am Drehknopf 8 LCD Drücken Sie die ENT Taste zum Speichern 7 Seg Drücken Sie PROG ENT zum Speichern 9 Schließen Sie FX oder RX um den Motor zu starten 10 Öffnen Sie FX oder RX um den Motor zu stoppen LCD Display 7 Segment Display P1 P2 JOG CM P3 FX RX NC CM BX RST I VR VI FM 5G DRV T K 0 0 A 00 STP 0 00Hz Die DRV LED leuchtet DRV Drive mode 03 Fx Rx 1 DRV Freq mode 04 Keypad 1 DRV T K...

Page 34: ... Startfrequenz bis Maximalfrequenz 0 01 30 00 Hz Ja DRV 08 Ausgangsstrom Current 08 Motorstrom RMS A DRV 09 Motordrehzahl Speed 09 Drehzahl in 1 min 1 min DRV 10 Zwischenkreisspannung DC link Vtg 10 Interne DC Zwischenkreisspannung V DRV 11 Benutzerdefinierte Displayanzeige User disp 11 Festgelegt in FU2 73 DRV 12 Fehleranzeige Fault 12 Keine none 0 Vorw DRV 13 Motordrehrichtung Am LCD Display nic...

Page 35: ...ng DcBr value 10 0 bis 200 1 50 Nein FU1 11 DC Bremszeit DcBr time 11 0 bis 60 sec 0 1 1 0 sec Nein FU1 12 Start Bremsspannung DcSt value 12 0 bis 200 1 50 Nein FU1 13 Start Bremszeit DcSt time 13 0 bis 60 sec 0 1 0 0 sec Nein FU1 20 Maximalfrequenz Max freq 20 40 bis 400 Hz 0 01 60 00 Hz Nein FU1 21 Knickfrequenz Base freq 21 30 bis FU1 20 0 01 60 00 Hz Nein FU1 22 Startfrequenz Start freq 22 0 1...

Page 36: ...a No 0 Nein FU1 50 Elektronischer Thermoschutz ETH ETH select 50 Yes 1 Ja Nein Ja FU1 5110 Elektron Temperatur niveau für 1 Minute ETH 1 min 51 FU1 52 bis 200 1 150 Ja FU1 52 Elektron Temperatur niveau Dauerbetrieb ETH cont 52 50 bis FU1 51 1 100 Ja Self cool 0 Eigen belüftet FU1 53 Art der Motorkühlung Motor type 53 Forced cool 1 Fremd belüftet Self cool Ja FU1 54 Überlast Warngrenze OL level 54 ...

Page 37: ...tere Sprungfrequenz 2 Jump lo 2 13 FU1 22 bis FU2 14 0 01 20 00 Hz Nein FU2 14 Obere Sprungfrequenz 2 Jump Hi 2 14 FU2 13 bis FU1 20 0 01 25 00 Hz Nein FU2 15 Untere Sprungfrequenz 3 Jump lo 3 15 FU1 22 bis FU2 16 0 01 30 00 Hz Nein FU2 16 Obere Sprungfrequenz 3 Jump Hi 3 16 FU2 15 bis FU1 20 0 01 35 00 Hz Nein FU2 17 Startkurve für S Beschl Verzögerungskurve Start Curve 17 0 bis 100 1 40 Nein FU2...

Page 38: ...nd des Motors Rs 42 0 bis 5 Ohm 0 001 Nein FU2 4316 Rotorwiderstand des Motors Rr 43 0 bis 5 Ohm 0 001 Nein FU2 44 Streuinduktivität des Motors Lsigma 44 0 bis 30 mH 0 001 15 Nein FU2 45 P Verstärkung für sensorlose Regelung SL SL P gain 45 0 bis 32767 1 32767 Ja FU2 46 I Verstärkung für sensorlose Regelung SL SL I gain 46 0 bis 32767 1 3276 Ja No 0 Nein FU2 47 PID Regelung Proc PI mode 47 Yes 1 J...

Page 39: ...ges PID Out Inv 57 Yes 1 Ja No Nein FU2 58 PID Ausgangsskalierung PID OutScale 58 0 bis 999 9 0 1 100 Nein FU2 59 PID P2 Verstärkung PID P2 gain 59 0 bis 100 0 1 100 Nein FU2 60 Skalierung der P Verstärkung P gain Scale 60 0 bis 100 0 1 100 Nein FU2 69 Beschleunigungs Verzög erungs Wechselfrequenz Acc Dec ch F 69 0 bis FU1 20 Nein Max freq 0 FU2 70 Referenzfrequenz für Beschleunigung Verzögerung A...

Page 40: ...l 2nd Stall 87 30 bis 150 1 150 Nein FU2 88 2 zulässiges Temperatur niveau für 1 Minute 2nd ETH 1min 88 FU2 89 bis 200 1 150 Ja FU2 89 2 zulässiges Temperatur niveau für Dauerbetrieb 2nd ETH cont 89 50 bis FU2 88 Maximal 150 1 100 Ja FU2 90 2 Motornennstrom 2nd R Curr 90 1 bis 200 A 0 1 3 6 A Nein No 0 Nein FU2 91 Parameter in das Bedienteil einlesen Para Read 91 Yes 1 Ja No Nein No 0 Nein FU2 92 ...

Page 41: ...I O 04 Maximale Eingangsspannung V1 V1 volt x2 04 0 bis 10 V 0 01 10 00 V Ja I O 05 Zur maximalen Eingangsspannung gehörige Frequenz V1 freq y2 05 0 bis FU1 20 0 01 60 00 Hz Ja I O 06 Abtastrate für I Signaleingang I filter 06 0 bis 10000 ms 1 10 ms Ja I O 07 Minimaler Eingangsstrom I I curr x1 07 0 bis 20 mA 0 01 4 00 mA Ja I O 08 Zum minimalen Eingangs strom gehörige Frequenz I freq y1 08 0 bis ...

Page 42: ...es Multifunktionseingangs P1 P1 define 12 Interlock4 32 Speed L Ja I O 13 Definition des Multifunktionseingangs P2 P2 define 13 Speed M Ja I O 14 Definition des Multifunktionseingangs P3 P3 define 14 Siehe oben Speed H Ja I O 15 Status der Eingangs signalanschlüsse In status 15 000000000 bis 111111111 I O 16 Status der Ausgangs signalanschlüsse Out status 16 0000 bis 1111 I O 17 Abtastrate für Mul...

Page 43: ...00 sec 0 1 40 0 sec Ja I O 34 Verzögerungszeit 5 Dec time 5 34 0 bis 6000 sec 0 1 40 0 sec Ja I O 35 Beschleunigungszeit 6 Acc time 6 35 0 bis 6000 sec 0 1 30 0 sec Ja I O 36 Verzögerungszeit 6 Dec time 6 36 0 bis 6000 sec 0 1 30 0 sec Ja I O 37 Beschleunigungszeit 7 Acc time 7 37 0 bis 6000 sec 0 1 20 0 sec Ja I O 38 Verzögerungszeit 7 Dec time 7 38 0 bis 6000 sec 0 1 20 0 sec Ja Frequency 0 Freq...

Page 44: ... O 54 Durchgangszeit zum ersten Schritt von Seq 1 Seq1 1T 54 0 1 bis 6000 sec 0 1 1 1 sec Ja I O 55 Konstantdrehzahlzeit des ersten Schrittes von Seq 1 Seq1 1S 55 0 1 bis 6000 sec 0 1 1 1 sec Ja Reverse 0 Rückwärts I O 56 Motordrehrichtung im ersten Schritt von Seq 1 Seq1 1D 56 Forward 1 Vorwärts Forward Ja I O 57 Erste Schrittfrequenz von Sequenz 2 Seq1 2F 57 0 01 bis FU1 20 0 01 21 00 Hz Ja I O ...

Page 45: ... M 1 Speed H 2 XCEL L 3 XCEL M 4 XCEL H 5 Dc brake 6 2nd Func 7 Exchange 8 Reserved 9 Up 10 Down 11 3 Wire 12 Ext Trip A 13 Ext Trip B 14 iTerm Clear 15 Open loop 16 Main drive 17 Analog hold 18 XCEL stop 19 P Gain2 20 SEQ L 21 SEQ M 22 SEQ H 23 Manual 24 Go step 25 Hold step 26 Trv Off Lo 27 Trv Off Hi 28 Interlock1 29 Interlock2 30 Interlock3 31 EXT 02 Definition des Multifunktionseinganges P4 P...

Page 46: ...e 14 Reference 2 None Nein A B 0 EXT 15 Impuls Eingangssignal F pulse set 15 A 1 A B Ja EXT 16 Anzahl der Pulse des Drehimpulsgebers Encoders F pulse num 16 360 bis 4096 1 1024 Nein EXT 17 Abtastrate für Impuls Signaleingang F filter 17 0 bis 10000 ms 1 10 ms Ja EXT 18 Minimalfrequenz des Impulssignales F pulse x1 18 0 bis 100 kHz 0 01 0 00 kHz Ja EXT 19 Zur minimalen Pulsfrequenz gehörige Ausgang...

Page 47: ... Q2 Q2 define 31 FDT 2 Ja EXT 32 Definition des Multi funktionsausganges Q3 Q3 define 32 Wie oben FDT 3 Ja Frequency 0 Current 1 Voltage 2 EXT 34 LM Lastmeterausgang LM mode 34 DC link Vtg 3 Current Ja EXT 35 LM Skalierung LM adjust 35 100 bis 200 1 100 Ja Frequency 0 Current 1 Voltage 2 EXT 40 AM1 Analogausgang 1 Ausgang AM1 mode 40 DC link Vtg 3 Frequency Ja EXT 41 AM1 Skalierung AM1 adjust 41 1...

Page 48: ...tr 05 2 50 1 15 Ja COM 10 Device Net ID MAC ID 10 0 63 1 0 Ja 125 kbps 0 250 kbps 1 COM 11 Device Net Baudrate Baud Rate 11 500 kbps 2 125 kbps Ja 20 0 21 1 100 2 COM 12 Device Net Ausgangsport Output Instance Out Instance 12 101 3 20 Nein 70 0 71 1 110 2 COM 13 Device Net Eingangsport Input Instance In Instance 13 111 3 70 Nein COM 17 PLC Option Stationsnummer Station ID 17 0 bis 63 1 1 Ja COM 20...

Page 49: ... HEX 0000 HEX Ja COM 44 Eingang 4 Input 4 44 0000 57FF HEX 0000 HEX Ja COM 45 Eingang 5 Input 5 45 0000 57FF HEX 0000 HEX Ja COM 46 Eingang 6 Input 6 46 0000 57FF HEX 0000 HEX Ja COM 47 Eingang 7 Input 7 47 0000 57FF HEX 0000 HEX Ja COM 48 Eingang 8 Input 8 48 0000 57FF HEX 0000 HEX Ja COM 52 ModBus ModBus Mode 52 ModBus RTU ModBus RTU Ja COM 99 Zurück zum Hauptmenü Nicht angezeigt 99 Nicht verfüg...

Page 50: ... freq 2 12 0 bis FU1 20 0 01 49 99 Hz Ja APP 13 Startfrequenz von Zusatzmotor 3 Start freq 3 13 0 bis FU1 20 0 01 49 99 Hz Ja APP 14 Startfrequenz von Zusatzmotor 4 Start freq 4 14 0 bis FU1 20 0 01 49 99 Hz Ja APP 15 Stopfrequenz von Zusatzmotor 1 Stop freq 1 15 0 bis FU1 20 0 01 15 00 Hz Ja APP 16 Stopfrequenz von Zusatzmotor 2 Stop freq 2 16 0 bis FU1 20 0 01 15 00 Hz Ja APP 17 Stopfrequenz von...

Page 51: ...ng gehörige Frequenz V2 freq y1 EXT 09 Maximale Spannung für V2 Signaleingang V2 volt x2 EXT 10 Zur maximalen Spannung gehörige Frequenz V2 freq y2 EXT 14 Einstellung des Impuls Signaleinganges F mode EXT 15 Impuls Eingangssignal F pulse set EXT 16 Anzahl der Impulse F pulse num EXT 17 Abtastrate für Impuls Signaleingang F filter EXT 18 Minimale Pulsfrequenz F pulse x1 EXT 19 Zur minimalen Pulsfre...

Page 52: ...n beschädigten Ventilator oder verstopfte Kühlschlitze E Thermal ETH Elektronischer Thermoschutz Der interne elektronische Thermoschutz stellt Überlast des Motors fest und unterbricht den Ausgang Beim Betrieb eines polumschaltbaren Motors oder mehrerer Motoren funktioniert diese Sicherheitseinrichtung nicht in diesen Fällen ist ein separater Schutz des Motors vorzusehen Zulässige Motorüberlastung ...

Page 53: ...t 4 Kurzschluß am Umrichterausgang 5 Die Bremse des Bremsmotors schaltet zu schnell 6 Der Umrichter überhitzt aufgrund eines defekten Kühlventilators 1 Beschleunigungs Verzögerungszeit erhöhen 2 Stärkeren Umrichter verwenden 3 Betrieb erst nach Motorstillstand aufnehmen 4 Verkabelung kontrollieren 5 Einstellung der Bremse korrigieren 6 Kühlventilator kontrollieren Achtung Um Folgeschäden an den IG...

Page 54: ...ontrollieren 2 Leitungen verstärken 3 Magnetschalter ersetzen Überstrom 2 1 Kurzschluß zwischen IGBT 2 Kurzschluß am Umrichterausgang 3 Beschleunigungs Verzögerungszeit ist im Verhältnis zum Trägheitsmoment der Last zu niedrig eingestellt 1 IGBT überprüfen 2 Verdrahtung am Umrichterausgang prüfen 3 Beschleuniguns Verzögerungszeit erhöhen Phasenverlust am Ausgang 1 Magnetschalter am Umrichterausgan...

Page 55: ...enz zwischen Sollfrequenz und Ist Drehzahl ist zu groß Ist das Frequenzsignal korrekt Eingangssignal kontrollieren Sind die folgenden Parameter korrekt eingestellt Unteres Frequenzlimit FU1 24 Oberes Frequenzlimit FU1 25 Einstellung der analogen Signaleingänge I O 1 10 Ist das Eingangssignal von Störungen beeinflußt Geschirmte Kabel verwenden Die Beschleunigung oder Verzögerung erfolgt zu ruckarti...

Page 56: ...N 50 kOhm oder größer Überprüfen des Ladewiderstandes Meßpunkt Widerstand wenn die Bauteile in Ordnung sind Klemmen des Schalters Abhängig vom Umrichtermodell DB Dynamische Bremse IGBT Optional Meßpunkt Widerstand wenn die Bauteile in Ordnung sind B2 N 50 kOhm oder größer G N einige kOhm Prüfen der IGBT Meßpunkt Widerstand wenn die Bauteile in Ordnung sind B2 N 50 kOhm oder größer G N einige kOhm ...

Page 57: ...d der hochfrequenten PWM Spannung falsche Werte an 5 5 2 Routine Inspektionsarbeiten Prüfen Sie vor Inbetriebnahme des Umrichters Die Umgebungsbedingungen Die korrekte Kühlung Vibrationen Unzulässige Wärmeentwicklung 5 5 3 Periodische Wartungsarbeiten Prüfen Sie die Schrauben und Muttern auf festen Sitz und Korrosion Bei Bedarf festziehen oder ersetzen Reinigen Sie den Kühlventilator mit Hilfe von...

Page 58: ...zitätsmeßgerät prüfen Keine Fehler Min 85 der angegebenen Kapazität Kapazitäts meßgerät Relais Prüfung auf Scheppergeräusche im Betrieb Prüfung auf Beschädigungen Ο Ο Hörprobe Visuelle Prüfung Kein Fehler Leistungsteil Wider stand Isolation auf Beschädigungen prüfen Kontakte des Widerstandes auf Unterbrechungen prüfen Ο Ο Optische Prüfung Anschlüsse abklemmen und Widerstand messen Kein Fehler Der ...

Page 59: ... einschränken FU1 23 25 Frequenzlimit I O 1 10 Analogeingang einstellen Motor vor Überhitzung schützen FU1 50 53 ETH FU2 30 Motornennleistung Frequenzschritte festlegen I O 12 14 Definition der Multifunktionseingänge I O 20 27 Jog Schrittfrequenzen FU1 23 25 Frequenzlimit Betrieb mit Konstantdrehzahl I O 20 Jog Frequenz Frequenzbereiche überspringen FU2 10 16 Frequenzsprünge Bremsvorgänge planen I...

Page 60: ...wollen FU1 23 25 Wenn hohes Anzugsmoment erforderlich ist FU1 26 28 Wenn Sie die U f Kennlinie an Ihre Anwendung anpassen wollen FU1 29 Wenn Sie eine individuelle U f Kennlinie benötigen FU1 30 37 Wenn Sie die Ausgangspannung einstellen wollen FU1 38 Wenn Sie die Energiesparfunktion verwenden wollen FU1 39 Wenn Sie den Motor vor Überhitzung schützen wollen FU1 50 53 Wenn Sie ein Signal ausgeben wo...

Page 61: ...4 Wenn Sie den Status der Ein und Ausgänge ermitteln wollen I O 15 16 Wenn Sie die Antwortzeiten der Signaleingänge ändern möchten I O 17 Wenn Sie den Motor mit Konstantdrehzahl bzw Drehzahlschritten betreiben möchten I O 20 24 Wenn Sie die 1 7 Beschleunigungs und Verzögerungszeit einstellen möchten I O 25 38 Wenn Sie den FM Ausgang nutzen wollen I O 40 41 Wenn Sie das Frequenzerkennungsniveau ein...

Page 62: ... A SV185iS5 2 18 2 ABS203a EBS203 SMC 80P 35 3 35 3 25 4 100 A 0 12 mH 96 A 0 49 mH 91 A SV220iS5 2 22 ABS203a EBS203 SMC 100P 50 2 35 3 25 4 125 A 0 10 mH 112 A 0 42 mH 107 A SV008iS5 4 0 75 ABS33a EBS33 SMC 10P 2 5 14 2 5 14 2 5 14 6 A 8 63 mH 2 8 A 28 62 mH 2 7 A SV015iS5 4 1 5 ABS33a EBS33 SMC 10P 2 5 14 2 5 14 2 5 14 10 A 4 81 mH 4 8 A 16 14 mH 4 6 A SV022iS5 4 2 2 ABS33a EBS33 SMC 20P 2 5 14...

Page 63: ...en Hauptabschnitt 2 Prüfung der Störfestigkeit gegen die Entladung statischer Elektrizität EMV Grundnorm IEC 61000 4 2 1995 ENV 50140 1993 Elektromagnatische Verträglichkeit EMV Störfestigkeitsgrundnorm Ausgesendete elektromagnetische Funkfrequenzfelder Störfestigkeitsprüfung ENV 50204 1995 Prüfung der Störfestigkeit gegen hochfrequente elektromagnatische Felder von digitalen Funktelefonen EN 6100...

Page 64: ...korrekt sind 2 Um optimale Wirkung zu erzielen sollte der Filter möglichst nahe bei den Leistungsanschlüssen zum Einsatz kommen 3 Die Montagestelle für den Filter muß sorgfältig gemäß den Abmessungen vorbereitet werden Insbesondere ist auf gute Erdung zu achten indem Farbe etc von den Montagebohrungen und Auflageflächen entfernt wird 4 Befestigen Sie den Filter sicher 5 Schließen Sie die Stromvers...

Page 65: ...ormen wird bestätigt EN50178 1997 EN 50081 2 1993 EN 55011 1994 EN 50082 2 1995 EN 61000 4 2 1995 ENV 50140 1993 ENV 50204 1995 EN 61000 4 4 1995 ENV 50141 1993 EN 61000 4 8 1993 Beschreibung des Produktes Frequenzumrichter Power Conversion Equipment Model SV iS5 Series Adresse SEVA Schulz GmbH Lether Gewerbe Strasse 10 26197 Großenkneten OT Ahlhorn Deutschland ...

Page 66: ...r after the inverter installation 8 Do not operate the switches with wet hands Doing so may result in electrical shock 9 Electrical shock may occur if the cable insulation is damaged Insure proper mounting of equipment to minimize excess stress on power cables CAUTION Fire Prevention 1 Install the inverter on a non combustible surface Installing the inverter on or near combustible materials can re...

Page 67: ...installed in power input circuit 5 Do not modify or alter anything inside inverter 6 CAUTION Motor might not be protected by electronic thermal function of inverter 7 Install noise filter to minimize potential noise interference on equipment installed near inverter 8 In case of input voltage unbalance install AC reactor Power Factor capacitors and generators may become overheated and damaged due t...

Page 68: ...avigation LCD Keypad 20 2 3 7 Segment Keypad 21 2 3 1 7 Segment Keypad Display 22 Two digits when the reference is lost 22 2 3 2 Procedure for Setting Data 7 Segment Keypad 23 2 3 3 Parameter Navigation 7 Segment Keypad 24 2 4 Operation Method 25 Option Board 25 CHAPTER 3 QUICK START PROCEDURES 31 3 1 Operation using Keypad 32 3 2 Operation using Control Terminals 33 3 3 Operation using Keypad and...

Page 69: ...oubleshooting 61 5 4 How to Check Power Components 62 5 5 Maintenance 63 5 5 1 Precautions 63 5 5 2 Routine Inspection 63 5 5 3 Periodical Inspection 63 5 5 4 Internal Fuse Replacement 63 5 6 Daily and Periodic Inspection Items 64 APPENDIX A FUNCTIONS BASED ON USE 65 APPENDIX B PARAMETERS BASED ON APPLICATION 66 APPENDIX C PERIPHERAL DEVICES 68 DECLARATION OF CONFORMITY 69 ...

Page 70: ... 50 60Hz 185 25 HP 220 30 HP UL Listed UL508C 1 2 Environmental Conditions 9 Verify ambient condition for the mounting location Ambient temperature should not be below 14ºF 10ºC or exceed 104ºF 40ºC Relative humidity should be less than 90 non condensing Altitude should be below 3 300ft 1 000m 9 Do not mount the inverter in direct sunlight and isolate it from excessive vibration 1 3 Mounting 9 The...

Page 71: ...erter in high temperature or high humidity locations 9 Do not install the inverter in a location where oil mist combustible gas or dust is present Install the inverter in a clean location or in an enclosed panel free of foreign substance 9 When installing the inverter inside a panel with multiple inverters or a ventilation fan use caution If installed incorrectly the ambient temperature may exceed...

Page 72: ... 7 5 10 HP mm inches Frame HP Model Number W1 W2 H1 H2 D1 1 SV008iS5 2 4 2 SV015iS5 2 4 3 SV022iS5 2 4 Frame 1 5 SV037iS5 2 4 150 5 91 130 5 12 284 11 18 269 10 69 156 5 6 16 7 5 SV055iS5 2 4 Frame 2 10 SV075iS5 2 4 200 7 87 180 7 09 355 13 98 340 13 39 182 5 7 19 ...

Page 73: ...P Frame 4 25 30 HP mm inches Frame HP Model Number W1 W2 H1 H2 D1 15 SV110iS5 2 4 Frame 3 20 SV150iS5 2 4 250 9 84 230 9 06 385 15 16 370 14 57 201 7 91 25 SV185iS5 2 4 Frame 4 30 SV220iS5 2 4 304 11 97 284 11 18 460 18 11 445 17 52 234 9 21 ...

Page 74: ...R V1 I Fault output relay lless than AC250V 1A lless than DC30V 1A Multi function output relay1 lless than AC250V 1A lless than DC30V 1A Factory setting Run Note Main Circuit Terminals Control Circuit Terminals 1 The terminal configuration varies depend on the model number Please refer to the 1 7 Power terminals 2 Analog speed command may be set by Voltage Current or both 3 When installing the DC ...

Page 75: ... U V W Symbols Functions R S T AC Line Voltage Input 3 Phase 200 230VAC or 380 460VAC G Earth Ground P Positive DC Bus Terminal DB Unit P P5 Connection Terminals DB Unit may be added when more braking duty More than 30 ED is required P1 P2 External DC Reactor P1 P2 and DB Unit P2 P1 Connection Terminals N Negative DC Bus Terminal DB Unit N N2 Connection Terminal B1 B2 Dynamic Braking Resistor B1 B...

Page 76: ... 1 7 2 Type B Configuration A Dynamic Braking Resistor or a Dynamic Braking Unit may be added to iS5 series inverters that have a Type B configuration power terminal strip As standard this type of configuration has in R S T G P N B1 B2 U V W Figure 2 Type B Dynamic Braking Resistor Installation R S T G P N B1 B2 U V W Figure 3 Type B Additional Dynamic Braking Unit and Resistor Installation Motor ...

Page 77: ...To Install a DC Bus Choke R S T G P1 P2 N U V W Figure 4 Type C Dynamic Braking Unit DC Bus Choke Installation WARNING Normal stray capacitance between the inverter chassis and the power devices inside the inverter and AC line can provide a high impedance shock hazard Refrain from applying power to the inverter if the inverter frame Power terminal G is not grounded Motor 3 Phase Power Input Dynami...

Page 78: ...munication equipment near the inverter To reduce noise install line noise filters on the input side of the inverter 9 Do not use power factor capacitor surge killers or RFI filters on the output side of the inverter Doing so may damage these components 9 Always check whether the LCD and the charge lamp for the power terminal are OFF before wiring terminals The charge capacitor may hold high voltag...

Page 79: ...15 HP M5 26 14 5 14 5 5 5 5 5 10 10 20 HP M5 26 22 6 22 6 14 8 6 8 25 HP M6 45 38 8 38 8 14 8 6 8 400V Class 30 HP M6 45 38 8 38 8 22 14 4 6 Power and Motor Connection R S T G N B1 B2 U V W 3 Apply the rated torque to terminal screws Loose screws can cause of short circuit or malfunction Tightening the screws too much can damage the terminals and cause a short circuit or malfunction 4 Use copper w...

Page 80: ...act Inputs NC Not Used VR Frequency Setting Power 10V Used as Power for Analog Frequency Setting Maximum Output is 12V 100mA V1 Frequency Reference Voltage Used for 0 10V Input Frequency Reference Input Resistance is 20 KΩ I Frequency Reference Current Used for 4 20mA Input Frequency Reference Input Resistance is 250 Ω Input signal Analog frequency setting 5G Frequency Setting Common Terminal Comm...

Page 81: ...wer circuits and other high voltage circuits 9 Use 1 25mm 22AWG stranded cables for control terminal connection Control Circuit Terminal The control input terminal of the control circuit is ON when the circuit is configured to the current flows out of the terminal as shown in the following illustration CM terminal is the common terminal for the contact input signals CAUTION Do not apply voltage to...

Page 82: ...low The LCD output will not be displayed on the keypad if the keypad is not connected properly Control Board Control Terminal Block Relay Output Terminal Block Keypad Connector CN3 Sub Board Connector Power Supply Input Gate Drive Signal Output Connector Socket Option Board Connector Sub Board Option Board ...

Page 83: ...arameters Function 1 Group FU1 FU1 LED Max Frequency Amount of Torque Boost etc Basic Related Parameters Function 2 Group FU2 FU2 LED Frequency Jumps Max Min Frequency Limit etc Basic Application Related Parameters Input Output Group I O I O LED Multi Function Terminal Setting Auto Operation etc Parameters needed for Sequence Operation Sub Board Group EXT EXT LED Displayed when Sub Board is Instal...

Page 84: ... through and change data Reverse Run Button The Reverse Run LED blinks when the drive Accels or Decels The Program Button is used to go into programming mode to change data The Enter Button is used to enter changed data within a parameter SHIFT This button is used to move cursor across display in programming mode ESC This button is used to move the program code to DRV 00 form any program code Forw...

Page 85: ...via Sub board J Jog terminal input 1 8 Step frequency operation During Auto operation 2 and 3 display the sequence number step 4 Output Current Displays the Output Current during operation 5 Parameter Code Displays the code of a group Use the Up Down key to move through 0 99 codes 6 Operating Status Displays the operation information STP Stop Status FWD During Forward operation REV During Reverse ...

Page 86: ...roup in Jump code except DRV group 3 Press PROG key to go into the programming mode the cursor starts blinking 4 Press SHIFT ESC key to move the cursor to the desired digit 5 Press or keys to change the data 6 Press ENT key to enter the data The cursor stops blinking Note Data cannot be changed when 1 The parameter is not adjustable during the inverter is running Refer to the function table in Cha...

Page 87: ...00 V FU1 Dec pattern 06 Linear FU2 Last trip 3 03 I O V1 freq y1 03 0 00 Hz DRV Freq mode 04 KeyPad 1 FU1 Stop mode 07 Decel FU2 Last trip 4 04 I O V1 volt x2 04 10 00 V DRV Step freq 1 05 10 00 Hz FU1 DcSt value 08 50 FU2 Last trip 5 05 I O V1 freq y2 05 60 00 Hz FU1 Stall Level 60 150 FU2 Para lock 94 0 I O Way1 2D 60 Forward MODE MODE MODE MODE I O Jump code 00 1 MODE MODE MODE MODE DRV Drive m...

Page 88: ...en a Sub Board is installed I O EXT Option Group Blinks when the parameter code is located on DRV 24 EXT Lit when Option group is selected This group appears only when an Option Board is installed FU2 I O EXT Application Group Blinks when the parameter code is located on DRV 25 FUN2 7 segment display Encoder knob Used to move you through parameter groups and parameter code Also used to change data...

Page 89: ...r Reverse operation Second digit d DC Braking J Jog Terminal Input 1 8 Step Frequency Input Displays the Step of the Auto operation Two digits when the reference is lost LP Loss of Reference from the Option Board DPRAM fault Lr Loss of Reference from the Option Board Communication network fault Lv Loss of Analog Frequency Reference V1 0 10V LI Loss of Analog Frequency Reference I 4 20mA LX Loss of...

Page 90: ... group 2 Press PROG ENT key to go into the FUN1 group 3 Rotate the encoder knob until the desired parameter code is displayed 4 Press PROG ENT key to go into the programming mode then the display blinks 5 Press SHIFT ESC key to move the cursor to the desired digit 6 Rotate the encoder knob to change the data 7 Press PROG ENT key to enter the changed data In FUN2 Group 1 Rotate the encoder knob unt...

Page 91: ...V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T PROG ENT D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T D R V FU 1 I O FU 2 E X T Encoder Knob FU1 Group Code DRV Group FU2 Group Code I O Group Code PROG ENT PROG ENT SHIFT ESC PROG ENT ...

Page 92: ...DRV 04 V1 or I or V1 I Run Stop is performed by the keypad Frequency reference is set through the V1 or I or V1 I terminal DRV 03 Keypad 1 or 2 DRV 04 V1 or I or V1 I Operation using both Keypad and Control Terminals Closing FX or RX terminal performs Run Stop Frequency reference is set through the keypad DRV 03 Fx Rx 1 or 2 DRV 04 Keypad 1 or 2 Operation using Option Board Operation using option ...

Page 93: ......

Page 94: ... the inverter before applying AC power 1 Mounting the inverter mount the inverter as described in 1 3 Mounting z Install in a clean dry location z Allow a sufficient clearance around top and sides of inverter z The ambient temperature should not exceed 40 C 104 F z If two or more inverters are installed in an enclosure add additional cooling 2 Wiring the inverter connect wiring as described in 1 7...

Page 95: ... to save the data 7 Seg Press PROG ENT key to save the data 10 LCD Press FWD or REV key to start motor 7 Seg Press RUN key to start motor 11 Press STOP RESET key to stop motor LCD Display 7 Segment Display DRV T K 0 0 A 00 STP 0 00Hz DRV Cmd freq 00 0 00Hz DRV Cmd freq 00 60 00Hz DRV K K 0 0 A 00 STP 60 00Hz DRV Drive mode 03 Fx Rx 1 DRV Drive mode 03 Fx Rx 1 DRV Drive mode 03 Keypad DRV Drive mod...

Page 96: ...Set the frequency by rotating the potentiometer 10 Close the FX or RX contact to run the motor 11 Open the FX or RX contact to stop the motor LCD Display 7 Segment Display DRV T K 0 0 A 00 STP 0 00Hz The DRV LED is ON DRV Drive mode 03 Fx Rx 1 DRV Freq mode 04 Keypad 1 DRV Freq mode 04 Keypad 1 DRV Freq mode 04 V1 DRV Freq mode 04 V1 DRV T V 0 0 A 00 STP 0 00Hz DRV T V 0 0 A 00 STP 60 00Hz The PRO...

Page 97: ...ROG ENT key 7 Confirm that the DRV 04 is set at V1 8 Press SHIFT ESC key Set the frequency by rotating the potentiometer 9 LCD Press FWD or REV key 7 Seg Press RUN key P1 P2 JOG CM P3 FX RX NC CM BX RST I VR VI FM 5G 4 to 20mA signal 1 1 2 W P1 P2 JOG CM P3 FX RX NC CM BX RST I VR VI FM 5G DRV 04 must be set at V1 DRV 04 must be set at I DRV T K 0 0 A 00 STP 0 00Hz The DRV LED is ON DRV Drive mode...

Page 98: ...save the data 7 Seg Press PROG ENT key to save the data 9 Close the FX or RX contact to run the motor 10 Open the FX or RX contact to stop the motor LCD Display 7 Segment Display P1 P2 JOG CM P3 FX RX NC CM BX RST I VR VI FM 5G DRV T K 0 0 A 00 STP 0 00Hz The DRV LED is ON DRV Drive mode 03 Fx Rx 1 DRV Freq mode 04 Keypad 1 DRV T K 0 0 A 00 STP 0 00Hz DRV Cmd freq 00 0 00Hz The PROG ENT LED is tur...

Page 99: ...Chapter 3 Quick Start Up 36 Blank Page ...

Page 100: ...r Text mark e nicht defini ert DRV 01 Acceleration Time Acc time 01 0 to 6000 0 1 10 0 sec Yes Fehle r Text mark e nicht defini ert DRV 02 Deceleration Time Dec time 02 0 to 6000 0 1 20 0 sec Yes Fehle r Text mark e nicht defini ert Keypad 0 Fx Rx 1 1 DRV 03 Drive Mode Run Stop Method Drive mode 03 Fx Rx 2 2 Fx Rx 1 No Fehle r Text mark e nicht defini ert Keypad 1 0 Keypad 2 1 V1 2 I 3 DRV 04 Freq...

Page 101: ...ark e nicht defini ert DRV 08 Output Current Current 08 The Load Current in RMS A Fehle r Text mark e nicht defini ert DRV 09 Motor Speed Speed 09 The Motor Speed in rpm rpm Fehle r Text mark e nicht defini ert DRV 10 DC link Voltage DC link Vtg 10 The DC Link Voltage inside inverter V Fehle r Text mark e nicht defini ert DRV 11 User Display Selection User disp 11 Selected in FU2 73 User Disp Fehl...

Page 102: ...rk e nicht defini ert DRV 14 Target Output Frequency Display TAR OUT 14 0 00 Hz Yes Fehle r Text mark e nicht defini ert DRV 155 Reference Feedback Frequency Display REF FBK 15 0 00 Hz Yes Fehle r Text mark e nicht defini ert DRV 20 FU1 Group Selection Not displayed in LCD keypad 20 Not available Press PROG ENT key 1 Yes Fehle r Text mark e nicht defini ert 5 Code DRV 15 appears only when FU2 47 i...

Page 103: ...t mark e nicht defini ert DRV 236 EXT Group Selection 23 Fehle r Text mark e nicht defini ert DRV 24 COM Group Selection 24 1 Yes Fehle r Text mark e nicht defini ert DRV 25 APP Group Selection 25 1 Yes Fehle r Text mark e nicht defini ert 6 Code DRV 23 through DRV 24 appears only when a Sub Board or an Option Board is installed ...

Page 104: ...orward Prev 1 FU1 03 Run Prevention Run Prev 03 Reverse Prev 2 None No Fehle r Text mark e nicht defini ert Linear 0 S curve 1 U curve 2 Minimum 3 FU1 05 Acceleration Pattern Acc pattern 05 Optimum 4 Linear No Fehle r Text mark e nicht defini ert Linear 0 S curve 1 U curve 2 Minimum 3 FU1 06 Deceleration Pattern Dec pattern 06 Optimum 4 Linear No Fehle r Text mark e nicht defini ert Decel 0 DC bra...

Page 105: ...0 to 60 sec 0 1 0 0 sec No Fehle r Text mark e nicht defini ert FU1 20 Maximum Frequency Max freq 20 40 to 400 Hz 0 01 60 00 Hz No FU1 21 Base Frequency Base freq 21 30 to FU1 20 0 01 60 00 Hz No FU1 22 Starting Frequency Start freq 22 0 1 to 10 Hz 0 01 0 50 Hz No Fehle r Text mark e nicht defini ert No 0 FU1 23 Frequency Limit selection Freq limit 23 Yes 1 No No FU1 248 Low Limit Frequency F limi...

Page 106: ...2 User V F Frequency 2 User freq 2 32 0 to FU1 20 0 01 30 00 Hz No FU1 33 User V F Voltage 2 User volt 2 33 0 to 100 1 50 No FU1 34 User V F Frequency 3 User freq 3 34 0 to FU1 20 0 01 45 00 Hz No FU1 35 User V F Voltage 3 User volt 3 35 0 to 100 1 75 No FU1 36 User V F Frequency 4 User freq 4 36 0 to FU1 20 0 01 60 00 Hz No FU1 37 User V F Voltage 4 User volt 4 37 0 to 100 1 100 No Fehle r Text m...

Page 107: ...30 sec 0 1 10 0 sec Yes Fehle r Text mark e nicht defini ert No 0 FU1 56 Overload Trip Selection OLT select 56 Yes 1 Yes Yes FU1 57 Overload Trip Level OLT level 57 30 to 150 1 180 Yes FU1 58 Overload Trip Delay Time OLT time 58 0 to 60 sec 1 60 0 sec Yes Fehle r Text mark e nicht defini ert FU1 59 Stall Prevention Mode Selection Stall prev 59 000 to 111 Bit Set bit 000 No FU1 60 Stall Prevention ...

Page 108: ...1 20 0 01 5 00 Hz No FU2 08 Dwell Time Dwell time 08 0 to 10 sec 0 1 0 0 sec No Fehle r Text mark e nicht defini ert No 0 FU2 10 Frequency Jump Selection Jump freq 10 Yes 1 No No FU2 1111 Jump Frequency 1 Low Jump lo 1 11 FU1 22 to FU2 12 0 01 10 00 Hz No FU2 12 Jump Frequency 1 High Jump Hi 1 12 FU2 11 to FU1 20 0 01 15 00 Hz No FU2 13 Jump Frequency 2 Low Jump lo 2 13 FU1 22 to FU2 14 0 01 20 00...

Page 109: ...ection Trip select 19 00 to 11 Bit Set 00 Yes Fehle r Text mark e nicht defini ert No 0 FU2 20 Power ON Start Selection Power on run 20 Yes 1 No Yes Fehle r Text mark e nicht defini ert No 0 FU2 21 Restart after Fault Reset RST restart 21 Yes 1 No Yes Fehle r Text mark e nicht defini ert FU2 22 Speed Search Selection Speed Search 22 0000 to 1111 Bit Set 0000 No Fehle r Text mark e nicht defini ert...

Page 110: ...to 10 1 0 Yes Fehle r Text mark e nicht defini ert FU2 27 Delay Time Before Auto Restart Retry Delay 27 0 to 60 sec 0 1 1 0 sec Yes Fehle r Text mark e nicht defini ert 0 75kW 0 1 5kW 1 2 2kW 2 3 7kW 3 5 5kW 4 7 5kW 5 11 0kW 6 15 0kW 7 18 5kW 8 FU2 30 Rated Motor Selection Motor select 30 22 0kW 9 12 No Fehle r Text mark e nicht defini ert FU2 31 Number of Motor Poles Pole number 31 2 to 12 1 4 No...

Page 111: ...ext mark e nicht defini ert FU2 3414 No Load Motor Current RMS Noload Curr 34 0 5 to 200 A 1 No Fehle r Text mark e nicht defini ert FU2 36 Motor Efficiency Efficiency 36 70 to 100 1 13 No Fehle r Text mark e nicht defini ert FU2 37 Load Inertia Inertia rate 37 0 to 1 1 0 No Fehle r Text mark e nicht defini ert 13 This value is automatically entered according to the rated motor set in FU2 30 If di...

Page 112: ...tance of Motor Rs 42 0 to 5 ohm 0 001 No FU2 4316 Rotor Resistance of Motor Rr 43 0 to 5 ohm 0 001 No FU2 44 Leakage Inductance of Motor Lsigma 44 0 to 30 mH 0 001 15 No Fehle r Text mark e nicht defini ert FU2 45 P Gain for Sensorless Control SL P gain 45 0 to 32767 1 32767 Yes Fehle r Text mark e nicht defini ert FU2 46 I Gain for Sensorless Control SL I gain 46 0 to 32767 1 3276 Yes Fehle r Tex...

Page 113: ...ht defini ert Ramp freq 0 FU2 50 PID Output Direction Selection PID Out Dir 50 Target freq 1 Ramp freq No Fehle r Text mark e nicht defini ert I 0 V1 1 FU2 51 PID Feedback Signal Selection PID F B 51 V2 2 I No FU2 52 P Gain for PID Control PID P gain 52 0 to 999 9 0 1 300 0 Yes FU2 53 I Gain for PID Control PID I time 53 0 to 32 0 sec 0 1 30 sec Yes FU2 54 D Gain for PID Control PID D time 54 0 to...

Page 114: ...tput Scale PID OutScale 58 0 to 999 9 0 1 100 No Fehle r Text mark e nicht defini ert FU2 59 PID P2 Gain PID P2 gain 59 0 to 100 0 1 100 No Fehle r Text mark e nicht defini ert FU2 60 P Gain Scale P gain Scale 60 0 to 100 0 1 100 No Fehle r Text mark e nicht defini ert FU2 69 Accel Decel Change Frequency Acc Dec ch F 69 0 to FU1 20 No Fehle r Text mark e nicht defini ert FU2 70 Reference Frequency...

Page 115: ...2 0 01 sec Yes Fehle r Text mark e nicht defini ert FU2 72 Power On Display PowerOn disp 72 0 to 12 1 0 Yes Fehle r Text mark e nicht defini ert Voltage 0 Watt 1 FU2 73 User Display Selection User disp 73 Torque 2 Voltage Yes Fehle r Text mark e nicht defini ert FU2 74 Gain for Motor Speed Display RPM factor 74 1 to 1000 1 100 Yes Fehle r Text mark e nicht defini ert None 0 FU2 75 DB Dynamic Braki...

Page 116: ...attern 2nd V F 84 User V F 2 Linear No FU2 85 2nd Forward Torque Boost 2nd F boost 85 0 to 15 0 1 2 0 No FU2 86 2nd Reverse Torque Boost 2nd R boost 86 0 to 15 0 1 2 0 No FU2 87 2nd Stall Prevention Level 2nd Stall 87 30 to 150 1 150 No FU2 88 2nd Electronic Thermal Level for 1 minute 2nd ETH 1min 88 FU2 89 to 200 1 150 Yes FU2 89 2nd Electronic Thermal Level for continuous 2nd ETH cont 89 50 to F...

Page 117: ...tection Para Lock 94 0 to 255 1 0 Yes Fehle r Text mark e nicht defini ert FU2 99 Return Code Not displayed 99 Not available PROG ENT or SHIFT ESC 1 Yes Fehle r Text mark e nicht defini ert 4 4 Input Output Group I O Keypad Display Setting Range Code Description LCD 7 Segment LCD 7 Segment Units Factory Default Adj During Run Page I O 00 Jump to Desired Code Jump code Not displayed 1 to 84 Not ava...

Page 118: ...s 1 10 ms Yes I O 07 I Input Minimum Current I curr x1 07 0 to 20 mA 0 01 4 00 mA Yes I O 08 Frequency Corresponding to I Input Minimum Current I freq y1 08 0 to FU1 20 0 01 0 00 Hz Yes Fehle r Text mark e nicht defini ert I O 09 I Input Maximum Current I curr x2 09 0 to 20 mA 0 01 20 00 mA Yes I O 10 Frequency Corresponding to I Input Maximum Current I freq y2 10 0 to FU1 20 0 01 60 00 Hz Yes Feh...

Page 119: ...Q H 23 Manual 24 Go step 25 Hold step 26 Trv Off Lo 27 Trv Off Hi 28 Interlock1 29 Interlock2 30 Interlock3 31 Interlock4 32 I O 13 Multi function Input Terminal P2 Define P2 define 13 Speed M Yes I O 14 Multi function Input Terminal P3 Define P3 define 14 Same as Above Speed H Yes Fehle r Text mark e nicht defini ert I O 15 Terminal Input Status In status 15 000000000 to 111111111 I O 16 Terminal...

Page 120: ...I O 27 Acceleration Time 2 Acc time 2 27 0 to 6000 sec 0 1 30 0 sec Yes I O 28 Deceleration Time 2 Dec time 2 28 0 to 6000 sec 0 1 30 0 sec Yes I O 29 Acceleration Time 3 Acc time 3 29 0 to 6000 sec 0 1 40 0 sec Yes I O 30 Deceleration Time 3 Dec time 3 30 0 to 6000 sec 0 1 40 0 sec Yes I O 31 Acceleration Time 4 Acc time 4 31 0 to 6000 sec 0 1 50 0 sec Yes I O 32 Deceleration Time 4 Dec time 4 32...

Page 121: ...U1 20 0 01 30 00 Hz Yes I O 43 Frequency Detection Bandwidth FDT band 43 0 to FU1 20 0 01 10 00 Hz Yes Fehle r Text mark e nicht defini ert FDT 1 0 FDT 2 1 FDT 3 2 FDT 4 3 FDT 5 4 OL 5 IOL 6 Stall 7 OV 8 LV 9 OH 10 Lost Command 11 Run 12 Stop 13 Steady 14 INV line 15 COMM line 16 Ssearch 17 Step pulse 18 Seq pulse 19 Ready 20 Trv ACC 21 Trv DEC 22 I O 44 Multi Function Auxiliary Contact Output Def...

Page 122: ...4 9600 bps Yes Fehle r Text mark e nicht defini ert None 0 FreeRun 1 I O 48 Operating selection at Loss of Freq Reference Lost command 48 Stop 2 None Yes I O 49 Waiting Time after Loss of Freq Reference Time out 49 0 1 to 120 sec 0 1 1 0 sec Yes Fehle r Text mark e nicht defini ert None 0 Auto A 1 I O 50 Auto Sequence Operation selection Auto mode 50 Auto B 2 None No I O 51 Sequence Number Selecti...

Page 123: ...Step of Sequence 2 Seq1 2S 59 0 1 to 6000 sec 0 1 1 1 sec Yes Reverse 0 I O 60 Motor Direction of 1st Step of Sequence 2 Seq1 2D 60 Forward 1 Forward Yes Fehle r Text mark e nicht defini ert I O 99 Return Code Not displayed 99 Not available PROG ENT or SHIFT ESC 1 Yes 4 5 External Group EXT EXT group appears only when the corresponding Sub Board is installed Keypad Display Setting Range Code Descr...

Page 124: ...ed 9 Up 10 Down 11 3 Wire 12 Ext Trip A 13 Ext Trip B 14 iTerm Clear 15 Open loop 16 Main drive 17 Analog hold 18 XCEL stop 19 P Gain2 20 SEQ L 21 SEQ M 22 SEQ H 23 Manual 24 Go step 25 Hold step 26 Trv Off Lo 27 Trv Off Hi 28 Interlock1 29 Interlock2 30 Interlock3 31 EXT 02 Multi Function Input Terminal P4 Define P4 define 02 Interlock4 32 XCEL L Yes Fehle r Text mark e nicht defini ert EXT 03 Mu...

Page 125: ... 1 10 ms Yes EXT 07 V2 Input Minimum Voltage V2 volt x1 07 0 to 10 V 0 01 0 00 V Yes EXT 08 Frequency Corresponding to V2 Input Minimum Voltage V2 freq y1 08 0 to FU1 20 0 01 0 00 Hz Yes EXT 09 V2 Input Maximum Voltage V2 volt x2 09 0 to 10 V 0 01 10 00 V Yes EXT 10 Frequency Corresponding to V2 Input Maximum Voltage V2 freq y2 10 0 to FU1 20 0 01 60 00 Hz Yes Fehle r Text mark e nicht defini ert ...

Page 126: ...m Frequency F pulse x1 18 0 to 100 kHz 0 01 0 00 kHz Yes Fehle r Text mark e nicht defini ert EXT 19 Frequency Output Corresponding to Pulse Input Minimum Frequency F freq y1 19 0 to FU1 20 0 01 0 00 Hz Yes EXT 20 Pulse Input Maximum Frequency F pulse x2 20 0 to 100 kHz 0 01 10 00 kHz Yes EXT 21 Frequency Output Corresponding to Pulse Input Maximum Frequency F freq y2 21 0 to FU1 20 0 01 60 00 Hz ...

Page 127: ... 11 Run 12 Stop 13 Steady 14 INV line 15 COMM line 16 Ssearch 17 Step pulse 18 Seq pulse 19 Ready 20 Trv ACC 21 Trv DEC 22 EXT 30 Multi Function Output Terminal Q1 Define Q1 define 30 MMC 23 FDT 1 Yes Fehle r Text mark e nicht defini ert EXT 31 Multi function Output Terminal Q2 Define Q2 define 31 FDT 2 Yes EXT 32 Multi function Output Terminal Q3 Define Q3 define 32 Same as Above FDT 3 Yes Fehle ...

Page 128: ...utput Selection AM2 mode 42 DC link Vtg 3 DC link Vtg Yes EXT 43 AM2 Output Adjustment AM2 adjust 43 100 to 200 1 100 Yes Fehle r Text mark e nicht defini ert EXT 99 Return Code Not displayed 99 Not available PROG ENT or SHIFT ESC 1 Yes 4 6 Communication Group COM COM group appears only when the corresponding Option Boards are installed Please refer to the option manual for detail Keypad Display S...

Page 129: ...e Net Input Instance In Instance 13 111 3 70 No COM 17 PLC Option Station Number Station ID 17 0 to 63 1 1 Yes COM 20 Profibus ID Profi MAC ID 20 0 to 127 1 1 Yes COM 30 Output Number Output Num 30 0 to 8 1 3 Yes COM 31 Output 1 Output 1 31 0000 57FF HEX 000A HEX Yes COM 32 Output 2 Output 2 32 0000 57FF HEX 000E HEX Yes COM 33 Output 3 Output 3 33 0000 57FF HEX 000F HEX Yes COM 34 Output 4 Output...

Page 130: ... Return Code Not displayed 99 Not available PROG ENT or SHIFT ESC 1 Yes 4 7 Application Group APP Keypad Display Setting Range Code Description LCD 7 Segment LCD 7 Segment Units Factory Default Adj During Run Page APP 00 Jump to Desired Code Jump code Not displayed 0 to 99 Not available 1 1 Yes Fehle r Text mark e nicht defini ert None 0 Traverse 1 MMC 2 APP 01 Application Mode Selection App Mode ...

Page 131: ...ert APP 04 Traverse Accel Time Trv Acc Time 04 0 to 6000 sec 0 1 2 0 sec Yes Fehle r Text mark e nicht defini ert APP 05 Traverse Decel Time Trv Dec Time 05 0 to 6000 sec 0 1 3 0 sec Yes Fehle r Text mark e nicht defini ert APP 06 Traverse Offset Hi Setting Trv Off Hi 06 0 0 to 20 0 0 1 0 0 Yes Fehle r Text mark e nicht defini ert APP 07 Traverse Offset Lo Setting Trv Off Lo 07 0 0 to 20 0 0 1 0 0...

Page 132: ...2 12 0 to FU1 20 0 01 49 99 Hz Yes APP 13 Start Frequency of Aux Motor 3 Start freq 3 13 0 to FU1 20 0 01 49 99 Hz Yes APP 14 Start Frequency of Aux Motor 4 Start freq 4 14 0 to FU1 20 0 01 49 99 Hz Yes Fehle r Text mark e nicht defini ert APP 15 Stop Frequency of Aux Motor 1 Stop freq 1 15 0 to FU1 20 0 01 15 00 Hz Yes APP 16 Stop Frequency of Aux Motor 2 Stop freq 2 16 0 to FU1 20 0 01 15 00 Hz ...

Page 133: ...t mark e nicht defini ert APP 21 The Number of Aux Motor Nbr Aux s 21 0 to 4 1 4 Yes Fehle r Text mark e nicht defini ert No 0 APP 22 PID Bypass Selection Regul Bypass 22 Yes 1 No Yes Fehle r Text mark e nicht defini ert APP 23 Sleep Delay Time Sleep Delay 23 0 to 9999 sec 0 1 60 0 sec Yes Fehle r Text mark e nicht defini ert APP 24 Sleep Frequency Sleep Freq 24 0 to FU1 20 0 01 19 00 Hz Yes Fehle...

Page 134: ...o Change Mode Selection AutoCh Mode 26 0 to 2 1 1 Yes Fehle r Text mark e nicht defini ert APP 27 Auto Change Time AutoEx intv 27 00 00 to 99 00 00 01 70 00 Yes APP 28 Auto Change Level AutoEx level 28 0 to 100 0 1 20 Yes Fehle r Text mark e nicht defini ert No 0 APP 29 Inter Lock Selection Inter lock 29 Yes 1 No Yes Fehle r Text mark e nicht defini ert APP 30 Actual Value Display Actual Value 30 ...

Page 135: ...lay in Percentage Actual Perc 31 Yes Fehle r Text mark e nicht defini ert None 0 V1_Draw 1 I_Draw 2 APP 3224 Draw Mode Selection Draw Mode 32 V2_Draw 3 None Yes Fehle r Text mark e nicht defini ert APP 33 Draw Size Setting DrawPerc 33 0 to 150 0 1 100 Yes Fehle r Text mark e nicht defini ert 24 Code APP 32 through APP 33 appears only when APP 01 is set to Draw ...

Page 136: ...lse set EXT 16 Encoder Pulse Selection F pulse num EXT 17 Filtering Time Constant for Pulse Input Signal F filter EXT 18 Pulse Input Minimum Frequency F pulse x1 EXT 19 Frequency Output corresponding to Pulse Input Minimum Frequency F freq y1 EXT 20 Pulse Input Maximum Frequency F pulse x2 EXT 21 Frequency Output corresponding to Pulse Input Maximum Frequency F freq y2 EXT 22 P Gain for PG Option ...

Page 137: ...Chapter 4 Options 74 ...

Page 138: ...Heat Sink Over Heat The inverter turns off its output if the heat sink over heats due to a damaged cooling fan or an alien substance in the cooling fan by detecting the temperature of the heat sink E Thermal ETH Electronic Thermal The internal electronic thermal of the inverter determines the over heating of the motor If the motor is overloaded the inverter turns off the output The inverter cannot...

Page 139: ...e run LOP Displayed when option frequency reference is lost DPRAM time out LOR Displayed when option frequency reference is lost Communication network fault LOV Displayed when V1 analog frequency reference is lost LOI Displayed when I analog frequency reference is lost LOX Displayed when sun board V2 ENC analog frequency reference is lost Inv OLT IOLT Inverter Overload The inverter turns off its o...

Page 140: ...s when Fuse Open Trip occurs Heat Sink Overheat 1 Cooling fan damaged or an alien substance inserted 2 Cooling system has faults 3 Ambient temperature high 1 Exchange cooling fans and or eliminate alien substance 2 Check for alien substances in the heat sink 3 Keep ambient temperature under 40 Electronic Thermal 1 Motor has overheated 2 Load is larger than inverter rating 3 ETH level too low 4 Sel...

Page 141: ...onnection between inverter and keypad 2 Inverter CPU malfunction 1 Check connector 2 Exchange inverter Operating Method when the Speed Reference is Lost LOP Loss of reference from the Option LOR Remote LOV V1 LOI I LOX Sub V2 ENC Eliminate cause of fault Inverter Overload 1 Load is larger than inverter rating 2 Selected incorrect inverter capacity 1 Increase motor and or inverter capacity 2 Select...

Page 142: ...ed and the Reference is Too Large Is the frequency reference signal correct Check the level of the input signal Is the following parameter setting is correct Lower Limit Frequency FU1 24 Upper Limit Frequency FU1 25 Analog Frequency Gain I O 1 10 Is the input signal line influenced by external noise Use a shielded wire The Inverter Does Not Accelerate or Decelerate Smoothly Is the acceleration dec...

Page 143: ...ms or more R S T N 50 k ohms or more Charge Resistor Check Check point Resistance to be Good Contactor terminals Depending on model DB Dynamic Braking IGBT Option Check point Resistance to be Good B2 N 50 k ohms or more G N A few kilo ohms IGBT Module Check Check point Resistance to be Good B2 N 50 k ohms or more G N A few kilo ohms R G E G E G E G E G E G E S T U V W G E P1 P2 B1 N Dynamic Brakin...

Page 144: ...outine Inspection Be sure to check the following before operation The conditions of the installation location The conditions of the drive cooling Abnormal vibration Abnormal heating 5 5 3 Periodical Inspection Are there any loose bolt nut or rust caused by surrounding conditions If so tighten them up or replace them Tighten up or replace Are there any deposits inside the drive cooling fan If so re...

Page 145: ...pacitance measuring device No fault Over 85 of the rated capacity Capacitance Measuring Device Relay Is there any chattering noise during operation Is there any damage to the contact Ο Ο Auditory check Visual check No fault Main Circuit Resistor Is there any damage to the resistor insulation Is the wiring in the resistor damaged open Ο Ο Visual check Disconnect one of the connections and measure w...

Page 146: ...r Lower Limit I O 1 10 Analog Frequency Setting Motor Overheat Protection FU1 50 53 Electronic Thermal FU2 30 Rated Motor Multi Step Operation I O 12 14 Define the Multi Function Input Terminals I O 20 27 Jog Multi Step Frequency FU1 23 25 Frequency Upper Lower Limit Jog Operation I O 20 Jog Frequency Frequency Jump Operation FU2 10 16 Frequency Jump Timing the Electronic Brake Operation I O 42 43...

Page 147: ...ue is needed for loads such as elevators Manual Auto Torque Boost FU1 26 28 When you want to select an appropriate output characteristic V F characteristic according to loads FU1 29 When you want to se up your own V F pattern FU1 30 37 When you want to adjust the output voltage of the inverter FU1 38 When you want to use the energy saving function FU1 39 When you want to protect the motor from ove...

Page 148: ... status of the input output terminals I O 15 16 When you want to change the response time of the input terminals I O 17 When you want to use the JOG and multi step speed operation I O 20 24 When you want to change the 1st 7th acceleration deceleration time I O 25 38 When you want to use the FM meter terminal output I O 40 41 When you want to set the frequency detection level I O 42 43 When you wan...

Page 149: ... 5 34 mH 14 A SV075iS5 4 10 ABS33a EBS33 SMC 20P 3 5 12 3 5 12 3 5 12 30 A 1 14 mH 20 A 4 04 mH 19 A SV110iS5 4 15 ABS53a EBS53 SMC 20P 5 5 10 5 5 10 8 8 35 A 0 81 mH 30 A 2 76 mH 29 A SV150iS5 4 20 ABS63a EBS63 SMC 25P 14 6 8 8 8 8 45 A 0 61 mH 38 A 2 18 mH 36 A SV185iS5 4 25 ABS103a EBS103 SMC 35P 14 6 8 8 14 6 60 A 0 45 mH 50 A 1 79 mH 48 A SV220iS5 4 30 ABS103a EBS103 SMC 50P 22 4 14 6 14 6 70...

Page 150: ...ed for compliance with EN50178 1997 EN 50081 2 1993 EN 55011 1994 EN 50082 2 1995 EN 61000 4 2 1995 ENV 50140 1993 ENV 50204 1995 EN 61000 4 4 1995 ENV 50141 1993 EN 61000 4 8 1993 Type of Equipment Inverter Power Conversion Equipment Model Name SV iS5 Series Address SEVA Schulz GmbH Lether Gewerbe Str 10 26197 Ahlhorn Germany ...

Reviews: