100
HMI SETTING
ENGLISH
8. Ventilation Mode Damper Angle
When using the Ventilation mode, set the damper angle in the Normal mode after the warm-
up time.
①
Outdoor Damper
The default outdoor damper is 0 °, and it can be adjusted at an increment/decrement of 1 °
between 0 ° and 90 °.
②
Exhaust Damper
The default exhaust damper is 0 °, and it can be adjusted at an increment/decrement of 1 °
between 0 ° and 90 °.
③
Mixing Damper
The default mixing damper is 90 °, and it can be adjusted at an increment/decrement of 1 °
between 0 ° and 90 °.
- A warning message will appear if the value of each damper is outside the range, at which
time you can re-enter the value.
①
Outdoor Damper Settings
①
Enter the desired input value by using
the key button.
②
Enter the value and then click the 'OK'
button to enter the input value.
②
Exhaust Damper Settings
③
Mixing Damper Settings