APPENDIX
125
ENGLISH
Controller Error
Error
Code
List of Errors
Error
Level
Cause
CH100017 Fire Detection (Smoke Detector)
1
The point of contact for fire detection is shorted (Displays the error and runs in HMI Smoke
Detection settings.)
CH10002
Emergency Stop Detection
2
The emergency stop for emergency stop is shorted (Displays the error and shuts down all
the activities.)
CH10003
HMI Communication Error
2
Unable to receive the communication signal from the HMI for more than 30 seconds.
CH10004
BMS Communication Error
2
Unable to receive the communication signal from the BMS for more than 30 seconds.
CH10011
Ventilation Temperature Sensor Error
2
The ventilation temperature sensor is disconnected/short circuited.
CH10013
Ventilation Flow Sensor Error
2
The ventilation flow sensor is disconnected/short circuited. (Error is identified 5 minutes
after the unit is turned on.)
CH10016
Miswired Ventilation Temperature Sensor
2
Miswiring between ventilation temperature sensor power supply and signal cable
CH10017
Miswired Ventilation/Humidity Sensor
3
Miswiring between ventilation humidity sensor power supply and signal cable
CH10018
Miswired Ventilation Flow Sensor
2
Miswiring between ventilation flow sensor power supply and signal cable
CH10021
Supply Temperature Sensor Error
2
The supply temperature sensor is disconnected/short circuited.
CH10023
Supply Flow Sensor Error
2
The supply flow sensor is disconnected/short circuited. (Error is identified 5 minutes after
the unit is turned on.)
CH10026
Miswired Supply Temperature Sensor
2
Miswiring between supply temperature sensor power supply and signal cable
CH10027
Miswired Supply Humidity Sensor
3
Miswiring between supply humidity sensor power supply and signal cable
CH10028
Miswired Flow Humidity Sensor
2
Miswiring between supply flow sensor power supply and signal cable
CH10031
Outdoor Unit Temperature Sensor Error
2
The outdoor unit temperature sensor is disconnected/short circuited.
CH10034
Outdoor Damper Feedback Error
3
The difference between the desired outdoor unit damper angle is over ±10 % (Identified as
an error 3 minutes after changing the angle.)
CH10036
Miswired Outdoor Unit Temperature Sensor
2
Miswiring between outdoor unit temperature sensor power supply and signal cable
CH10037
Miswired Outdoor Unit Humidity Sensor
3
Miswiring between outdoor unit humidity sensor power supply and signal cable
CH10041
Mix Temperature Sensor Error
2
The mixer temperature sensor is disconnected/short circuited.
CH10044
Mix Temperature Damper Feedback Error
3
The difference between the desired mixer damper angle is over ±10 % (Identified as an
error 3 minutes after changing the angle.)
CH10046
Miswiring of Mix Temperature Sensor
2
Miswiring between mixer temperature sensor power supply and signal cable
CH10054
Exhaust Damper Feedback Error
3
The difference between the desired supply damper angle is over ±10 % (Identified as an
error 3 minutes after changing the angle.)
CH10061
Differential Sensor Error
3
The differential sensor is disconnected/short circuited. (Error is identified 5 minutes after
the unit is turned on.)
CH10062
Static Pressure Sensor Error
3
The static pressure sensor is disconnected/short circuited. (Error is identified 5 minutes
after the unit is turned on.)
CH10063
CO2 Sensor Error
3
The CO2 sensor is disconnected/short circuited.
CH10071
Filter Exchange Alarm
3
Exceeded the set value of the differential sensor.
CH10072
Filter Exchange Error
2
The total run time has exceeded 300 hours after the filter replacement alarm is triggered.
CH10101
IO #1 Communication Error between Mod-
ules
2
Unable to receive the communication signal from IO #1 for more than 1 minute.
CH10111
IO #2 Module Communication
2
Unable to receive the communication signal from IO #2 for more than 1 minute.
CH10501
COM #1 Communication Error between
Modules
2
Unable to receive the communication signal from COM #1 for more than 1 minute.
CH10511
COM #2 Communication Error between
Modules
2
Unable to receive the communication signal from COM #2 for more than 1 minute.
CH11002
ODU1 Indoor Sensor (Inlet Pipe) Error
2
The inlet temperature sensor of Indoor Unit #1 of COM #1 is disconnected/short circuited.
CH11005
ODU1 Communication Error (Indoor Unit
↔
Outdoor Unit)
2
Indoor Unit #1 of COM #1 is unable to receive the communication signal from the outdoor
unit for more than 3 minutes.
CH11006
ODU1 Indoor Sensor (Outlet Pipe) Error
2
The outlet temperature sensor of Outdoor Unit # 2 of COM #1 is disconnected/short cir-
cuited.
CH11255
ODU1 Communication Error between Central
Controls
2
Indoor Unit #1 of COM #1 is unable to receive the Central Control communication signal for
more than 3 minutes. (This error occurs only when the Desired Temperature Control Stan-
dard is set to supply.)
CH11XXX ODU1 Displays outdoor unit error code
2
Displays the relevant code as is when an error occurs in the outdoor unit communicating
with Indoor Unit #1 of COM #1.