HMI SETTINGS
47
ENGLISH
High
classification
error
Low
classification
error
Errors
Error Code
Location name
Error
grade
Notes
CH10xxx
CH10031 ~
CH10040
Sensor type -
outdoor air
CH10031
Outdoor air thermistor error
2
Sensor short-circuited or
disconnected
CH10032
Outdoor air humidity sensor
error
-
Reserved
CH10034
Outdoor air damper feedback
error
3
In case of ± 10%
difference from target
opening
CH10036
Outdoor air thermistor faulty
connection
2
Faulty connection of
sensor power and signal
line
CH10037
Outdoor air humidity sensor
faulty connection
3
Faulty connection of
sensor power and signal
line
CH10039
Outdoor air damper feedback
faulty connection
3
Reserved
Others
Reserved
Reserved
CH10041 ~
CH10050
Sensor type -
mixed air
CH10041
Mixed air thermistor error
2
Sensor short-circuited or
disconnected
CH10044
Mixed air damper feedback
error
3
In case of ± 10%
difference from target
opening
CH10046
Mixed air thermistor faulty
connection
2
Faulty connection of
sensor power and signal
line
CH10049
Mixed air damper feedback
faulty connection
3
Reserved
Others
Reserved
Reserved
CH10051 ~
CH10060
Sensor type -
exhaust air
CH10054
Exhaust air damper feedback
error
3
In case of ± 10%
difference from target
opening
CH10059
Exhaust air sensor feedback
faulty connection
3
Reserved
Others
Reserved
Reserved
CH10061 ~
CH10070
Sensor type -
other
CH10061
Differential pressure sensor
error
3
Sensor short-circuited or
disconnected
CH10062
Static pressure sensor error
3
Sensor short-circuited or
disconnected
CH10063
CO
2
sensor error
3
Sensor short-circuited or
disconnected